background image

+

-

A

V

PC Board

Assembly

Input

Transformer

LED AC “ON”

Positive

Red

Yellow

Orange

Black

White

Violet

Test Switch

Optional
Voltmeter

Optional
Ammeter

24-Hour Input Power

Common

120V

277V

Blue

Lamp

Lamp

Single Battery

To Remote Load

Negative

FIGURE 1

1. To test the equipment, depress the TEST switch. The CHARGE indicator will go out and the emergency lights 

will illuminate.

2. Release the TEST switch. The emergency lights will go out and the CHARGE indicator will illuminate. The 

automatic charger will return and maintain the battery in a fully charged state.
NOTE: Allow the battery to charge for a minimum of 24 hours after installation or after a power failure before 
conducting a 90 minute test (see TESTING section). CAUTION: This equipment is furnished with a sophisticated 
solid state transfer switch which will automatically disconnect the emergency lights from the battery if the battery has been 
discharged to the end of its useful output.

MAINTENANCE

CAUTION: Always turn off AC power to the equipment before servicing. Servicing should be performed only by a qualified service technician. 

Use only MANUFACTURER supplied replacement parts.

1. BATTERY: The battery supplied in this equipment requires no maintenance. However, it should be tested periodically (see TESTING 

section) and replaced when it no longer operates the connected fixtures for the duration of a 30-second or 90-minute test. The battery 
supplied in this equipment has a life expectancy of 5-7 years when used in a normal ambient temperature f 72ºF.

2. OTHER: Clean lenses and replace lamps as required.

TESTING

Paragraph 31-1.3.7 of NFPA 101-1985, Life Safety Code requires that all emergency lighting equipment be functionally tested every 30 

days for a minimum of 30 seconds and tested yearly for a full 90-minute duration. Written records of testing are to be kept for 
examination by the authority having jurisdiction.

TROUBLE-SHOOTING

1. The emergency lights do not operate.

a. If the charge indicator light is off: check that the circuit breaker for the AC supply is on.
b. if the charge indicator light is on:

• check that the battery is properly connected.

• if remote lights are connected to equipment, turn off AC supply and disconnect remote circuit wires from equipment. Turn on AC 

supply and depress the test switch. If equipment-mounted lights are now on, check remote circuit for short or overload 
condition and correct as required. Then reconnect circuit wires and restore AC power.

• if problem persists, replace battery.

2. Emergency lights are dim: battery is not fully charged. Allow battery to recharge for 24 hours and then re-test. If lights are still dim, 

replace battery.

OPERATION

WARNING:

UNUSED WIRES MUST BE CAPPED USING ENCLOSED WIRE NUTS.

Отзывы: