+
-
A
V
PC Board
Assembly
Input
Transformer
LED AC “ON”
Positive
Red
Yellow
Orange
Black
White
Violet
Test Switch
Optional
Voltmeter
Optional
Ammeter
24-Hour Input Power
Common
120V
277V
Blue
Lamp
Lamp
Single Battery
To Remote Load
Negative
FIGURE 1
1. To test the equipment, depress the TEST switch. The CHARGE indicator will go out and the emergency lights
will illuminate.
2. Release the TEST switch. The emergency lights will go out and the CHARGE indicator will illuminate. The
automatic charger will return and maintain the battery in a fully charged state.
NOTE: Allow the battery to charge for a minimum of 24 hours after installation or after a power failure before
conducting a 90 minute test (see TESTING section). CAUTION: This equipment is furnished with a sophisticated
solid state transfer switch which will automatically disconnect the emergency lights from the battery if the battery has been
discharged to the end of its useful output.
MAINTENANCE
CAUTION: Always turn off AC power to the equipment before servicing. Servicing should be performed only by a qualified service technician.
Use only MANUFACTURER supplied replacement parts.
1. BATTERY: The battery supplied in this equipment requires no maintenance. However, it should be tested periodically (see TESTING
section) and replaced when it no longer operates the connected fixtures for the duration of a 30-second or 90-minute test. The battery
supplied in this equipment has a life expectancy of 5-7 years when used in a normal ambient temperature f 72ºF.
2. OTHER: Clean lenses and replace lamps as required.
TESTING
Paragraph 31-1.3.7 of NFPA 101-1985, Life Safety Code requires that all emergency lighting equipment be functionally tested every 30
days for a minimum of 30 seconds and tested yearly for a full 90-minute duration. Written records of testing are to be kept for
examination by the authority having jurisdiction.
TROUBLE-SHOOTING
1. The emergency lights do not operate.
a. If the charge indicator light is off: check that the circuit breaker for the AC supply is on.
b. if the charge indicator light is on:
• check that the battery is properly connected.
• if remote lights are connected to equipment, turn off AC supply and disconnect remote circuit wires from equipment. Turn on AC
supply and depress the test switch. If equipment-mounted lights are now on, check remote circuit for short or overload
condition and correct as required. Then reconnect circuit wires and restore AC power.
• if problem persists, replace battery.
2. Emergency lights are dim: battery is not fully charged. Allow battery to recharge for 24 hours and then re-test. If lights are still dim,
replace battery.
OPERATION
WARNING:
UNUSED WIRES MUST BE CAPPED USING ENCLOSED WIRE NUTS.