background image

1E-138B 

Dari-Kool III-120 Instructions

1.  If  cabinet  openings  or  modifications  have  to  be  made, 

they  must  be  accomplished  in  such  a  manner  as  not  to 

be   detrimental  to  the  cabinet.    Do  not  cut  into  electrical 

enclosures.

2.  Do not route tubing through electrical enclosures or cabinet 

sections containing live metal parts.  The tubing 

 

must be properly supported and protected from sharp edges 

and moving parts.

3.  The  tubing  must  be  mechanically  isolated  from  structural 

building members.

—  Note ———————————————————————

•  Be  careful  not  to  burn  wrapper  on  insulation  when  brazing 

refrigeration lines.

•  All joints should be checked for leaks and the lines evacuated 

according to standard refrigeration practices. 

Figure 3.  Water Valve Installation

4.3

 Refrigerant  Lines

The compressor discharge line size is usually adequate for 

normal installations.  However, if lines are more than 20 feet 

(6 m) long, they should be sized for a maximum of 15 PSIG 

(103 kPa) pressure drop.  (See ASHREA piping tables.)  Lines 

should be installed to pitch toward the Dari-Kool III-120 and 

condensor, and to drop down from the compressor discharge 

to form a 6” (152 mm) trap to prevent oil and liquid refrigerant 

from accumulating on the discharge valve plate.

When two circuits of the Dari-Kool III-120 are connected to 

a single compressor, it is important to size the inlet tubes to 

create a small but equal pressure drop.  This small pressure drop 

is required to insure equal distribution through each circuit.  

This is important to achieve optimum performance, and to 

prevent oil and liquid trapping.  See the following table for 

recommended line sizes.  These diameters and lengths should 

create about a 5 PSI (34 kPa) pressure drop.

When installing a Dari-Kool III-120 on an existing refrigeration 

installation,  extreme  care  must  be  used  not  to  damage  the 

existing system.  If the tubing must be routed into an existing 

cabinet, the following precautions must be taken:

Figure 4.  Manifold for single compressor Installation on inlets only.

Table 1: Recommended Line Sizes

HP 

R-134A Dia.

Length

R-22 Dia.

Length

2

1/4” (6 mm)

12' (4 m)

1/4' (6 mm)

36' (11 m)

3

5/16” (8 mm) 

28' (9 m)

1/4' (6 mm)

12' (4 m)

4

5/16” (8 mm) 

12' (4 m)

5/16' (8 mm)

36' (11 m)

5

3/8” (10 mm)

30' (9 m) 

5/16' (8 mm)

20' (6 m)

6

3/8” (10 mm) 

24' (7 m)

  −

−  

7-1/2

3/8” (10 mm) 

12' (4 m)

3/8' (10 mm) 

36' (11 m)

10

  −

3/8' (10 mm)

12' (4 m)

Содержание Dari-Kool III-120

Страница 1: ...em Disclaimers No warranties are contained in these instructions The division of responsibilities stated above is a general reminder of those provisions in the applicable dealer contract and does not...

Страница 2: ...idelines must be observed 1 The Dari Kool III 120 should be in a clean dry place as close as possible to the compressor to minimize the refrigerant line lengths 2 It should be located with adequate cl...

Страница 3: ...power will have to be applied to the valve in order to close it while checking for leaks DO NOT apply power to the heating element unless it is covered with water 7 The Dari Kool III 120 has dual mag...

Страница 4: ...and condensor and to drop down from the compressor discharge to form a 6 152 mm trap to prevent oil and liquid refrigerant from accumulating on the discharge valve plate When two circuits of the Dari...

Страница 5: ...t used control wires for valve must be isolated The equipment ground must be completed The wiring must conform to local and state electrical codes and must be installed by qualified personnel The diag...

Страница 6: ...efrigerant capacity Condensing unit not to exceed 15 tons 53 kW of R 22 R 404 or R 407 or 7 5 tons 26 kW of R 134A Refer to table for recommended line sizing Figure 6 1 ton 3 5 kW of refrigerant capac...

Страница 7: ...condensing unit capacity of 1 ton each Figure 9 Dari Kool III 120 in parallel with a large condensing unit Add additional Dari Kool III 120 as required Condensing unit is not to exceed 30 105 kW tons...

Страница 8: ...d 15 tons 52 7 kW of R 22 R 404 or R 407 or 7 5 tons 26 kW tons of R 134A Minimum of 3 ton 10 5 kW condensing unit Figure 10 Dual condensing units dual temperature Each condensing unit does not to exc...

Отзывы: