GAS SUPPLY

The  gas  pipeline  can  be  brought  in  through  the  left  side  of  the 

appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 

CAN/CGA-B149 (.1 or .2) installation code.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe 

Inside Diameter

Tubing, Type L

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10ft

0-3m

1/2 in.

12.7mm

3/8 in.

9.5mm

1/2 in.

12.7mm

3/8 in.

9.5mm

11-40ft

4-12m

1/2 in.

12.7mm

1/2 in.

12.7mm

5/8 in.

15.9mm

1/2 in.

12.7mm

41-100ft

13-30m

1/2 in.

12.7mm

1/2 in.

12.7mm

3/4 in.

19mm

1/2 in.

12.7mm

101-150ft

31-46m

3/4 in.

19mm

1/2 in.

12.7mm

7/8 in.

22.2mm

3/4 in.

1.9 mm

Note:

 Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

Note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 

and Fittings.

—  ANS Z21.45 Assembled Flexible Appliance Connectors of Other 

Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having  jurisdiction.  The  state  of  Massachusetts  requires  that  a 

flexible appliance connector cannot exceed three feet in length.

FLEXIBLE GAS LINE CONNECTION

GAS SUPPLY

TEE HANDLE

FLEX TUBING

FLARE SHUT OFF VALVE

FLARE 

FITTING

Figure 7

Gas Supply Pressure (inches w.c.)
Minimum

Normal Maximum

Natural Gas

5.0

7.0

14.0

LP (Propane)

10.8

11.0

14.0

Manifold Pressure (inches w.c.)

Normal (HI)

Natural Gas

3.5

LP (Propane)

10.0

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. 

Where none exists, or where its size or location is not adequate, 

contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

Never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

NOTE:

 The gas controls are equipped with a captured screw type 

pressure test point, therefore it is not necessary to provide a 1/8 in. 

test point up stream of the control.
When using copper or flex connector use only approved fittings. 
The appliance and its individual shut off valve must be disconnected 

from supply piping system during any pressure testing of that system 

at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system 

by closing its individual manual shut off valve during any pressure 

testing of the gas supply piping system at test pressures equal to 

or less than 1/2 psig (3.5kPa).

Attention!

 If one of the procedures results in pressures in excess 

of 1/2 psig (14 in. w.c.) (3.5 kPa) on the fireplace gas valve, it will 

result in a hazardous condition.

Checking Manifold Pressures

Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 

regulator in the gas valve. Natural gas models will have a manifold 

pressure of approximately 3.5 in. w.c. (.871kPa) at the valve outlet 

with the inlet pressure to the valve from a minimum of 5.0 in. w.c. 

(1.245kPa) for the purpose of input adjustment to a maximum of 

14.0 in. w.c. (3.484kPa). Propane gas models will have a manifold 

pressure  approximately  10.0  in.      (2.49kPa)  at  the  valve  outlet 

with the inlet pressure to the valve from a minimum of 10.8 in. w.c. 

(2.68kPa) for the purpose of input adjustment to a maximum of 

 

14.0 in. w.c. (3.484kPa). 

2-7/16”

(61 mm)

8-1/4”

(209.5mm)

Figure 8

Содержание DVLL41FP92N-1

Страница 1: ...convertibleforusewithother gases unless a certified kit is used WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do no...

Страница 2: ...TERMINATION 28 29 DVVK 4F FLEX VENT INSTRUCTIONS 30 FINISHING THE WALL 31 32 DVTL LOG EMBER PLACEMENT 33 DVLL DECORATIVE MEDIA INSTALLATION 34 LIGHTING INSTRUCTIONS 35 OPERATING INSTRUCTIONS 36 37 MA...

Страница 3: ...e and shall be installed for the protection of children and other at risk individuals If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance An...

Страница 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Страница 5: ...ons shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum...

Страница 6: ...th the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from theAmerican National Standards Institute Inc 11 West 42nd St New York...

Страница 7: ...r Opening Front 9 16 in FULL OPEN 9 16 FULL OPEN Height without standoff 24 1 4 in 616 mm 24 1 4 in 616 mm 24 1 4 in 616 mm 24 1 4 in 616 mm Width 51 1 16 in 129 7 cm 51 1 16 in 129 7cm 51 1 16 in 129...

Страница 8: ...eiling 46 3 4 1 17m Figure 2 Combustible Material No greeting cards stockings or ornamentation of any type should be placed on or attached to the fireplace The flow of heat can ignite combustibles ONL...

Страница 9: ...R INSTALLATION FLUSH WALL INSTALLATION CABINET INSTALLATION LOCATING FIREPLACE Note Island and Room Divider installation is possible as long as the horizontal portion of the vent system does not excee...

Страница 10: ...Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases The gas lines must be checked for leaks by the installer This should be done with a soap s...

Страница 11: ...mm MINIMUM CLEARANCE AROUND VENT PIPE Figure 9 2 50 8mm TOP OF VENT PIPE 4 DIAMETER FLUE 6 5 8 DIAMETER INTAKE VENT 3 76mm 1 25 4mm Figure 10 INSTALLATION Attention Horizontal venting through a wall r...

Страница 12: ...andoffs See Figure 12 8 Remove the non combustible board that is shipped between the fireplace and pallet 9 Frame in fireplace with a header across the top IMPORTANT Allow for finished face when setti...

Страница 13: ...headers may rest on the fireplace standoffs Refer to Figure 13 for minimum framing dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMINGMETHODS ANDWALLCOVERINGDETAILSBEFORE FRAMING CONSTR...

Страница 14: ...upports must be positioned so they contact all four 4 perimeter edges on the bottom of the unit and under the center leg supports Two more supports spaced evenly for front and back may be required pen...

Страница 15: ...0 Elbow To Horizontal Out The Wall B A C E D NOTE YOU MUST USE A 2 609 6mm VERTICAL VENT PIPE AS YOUR FIRST SECTION BEFORE INSTALLING THE ELBOW VENT CAP THIMBLE WALL FIRESTOP DVLL DVTL A 62 1 4 in 158...

Страница 16: ...ion is two These elbows can be installed in either the vertical or horizontal run NOTE The first elbow does not get counted Vertical Venting When venting long straight vertical sections use of the ver...

Страница 17: ...s not possible to meet the required vent terminal clearances of 12 in 305mm above grade level a snorkel kit is recommended It allows installation depth down to 7 in 178mm below grade level The 7 in 17...

Страница 18: ...nd H1 H2 is listed as total of maximum horizontal dimensions The maximum vertical and horizontal distances for two 2 90 elbows as shown in Figure 25 is 37 ft 11 28 m FIRE STOP AT CEILING LEVEL H1 H2 V...

Страница 19: ...studs This will avoid any extra framing All vent kit pipes should be assembled on the unit after the unit is moved into the final position Cutting the Hole After the fireplace has been positioned in i...

Страница 20: ...ired vertical is 5 1 52 m H 8 90 11 equivalent horizontal H 2 44 m 90 2 44 m equivalent horizontal From the graph the required vertical is 5 1 52 m Figure 29 If total horizontal needs to be 10 3 05 m...

Страница 21: ...115 Page 21 EXAMPLES TOP VENT RUN H1 H2 V1 Figure 30 If total vertical is to be 9 2 74 m then the maximum allowed horizontal run can be 20 6 10 m H 20 H 6 10 m From the graph the allowed vertical is 2...

Страница 22: ...the fireplace in such a way that minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake an...

Страница 23: ...feet 90cm horizontally from the center line of the regulator I clearance to service regulator vent outlet 6 feet 1 8m minimum J clearance to non mechanical air supply inlet to building or the combust...

Страница 24: ...ar or previously installed component end with four 4 equally spaced indented sections When the internal beads of each starting outer pipe line up rotate pipe section clockwise 90 approximately 3 inche...

Страница 25: ...in place to framing members There MUST BE a 3 inch clearance to combustibles above flue pipe and elbows and 1 inch clearance on both sides and bottom of the flue pipe to combustibles on all horizontal...

Страница 26: ...on and secure the firestop on top of the previously framed hole See Figure 38 NOTE Remove insulation from the framed area in the attic before installing the firestop and or vent pipes A B NAILS 4 REQU...

Страница 27: ...l NOTE Wood screws can and should be replaced with appropriate fasteners for use on stucco brick concrete or other types of siding CAUTION Ifexteriorwallsarefinishedwithvinylsiding ormaterials that co...

Страница 28: ...arby trees adjoining roof lines steep pitched roofs and other similar factors can result in poor draft or down drafting In these cases increasing the vent height may solve this problem 24 MIN 609 6mm...

Страница 29: ...he requirements for these steps NOTE When installing this vent system in a chase it is always good building practice to insulate the chase as you would the outside walls of your home This is especiall...

Страница 30: ...te The flue pipe end without the adapter is to be installed to the Termination Cap 10 Apply sealant to the outside of the flue pipe adapter and connect to the flex flue pipe Then insert the adapter in...

Страница 31: ...ng materials up to 1 in 25 4mm thick may come up to the sides of the unit The Optional Front will overlap the finishing materials 24 1 4 616mm 51 129 5cm 5 8 15 8mm MINIMUM FROM BOTTOM OF UNIT TO TOP...

Страница 32: ...with three screws 6 Hang the decorative front on the four rectangle cut outs on the face of the fireplace 7 Finish around the fireplace you must use only non combustible material to cover the steel f...

Страница 33: ...o breakage if not handled properly The positioning of logs is critical to safe and clean operation of this fireplace Sooting and other problems may result if the logs are not properly and firmly posit...

Страница 34: ...r Empire Comfort Systems dealer Place small rock media only to the outside of the flanged area on the media tray Never place the fiber rocks on top of or next to the burner DECORATIVE MEDIA MUST NOT B...

Страница 35: ...f applicable 2 Open bottom louver assembly 3 Locate On Off gas cock and turn clockwise to OFF Do not force 4 Close bottom louver assembly 1 STOP Read the safety information above 2 Turn OFF electric p...

Страница 36: ...om a spark to pilot system to a standing pilot system 1 There is a switch located on the right side of the Control Module 4 that reads CONTINUOUS PILOT ON OFF This switch will allow the user to select...

Страница 37: ...ng a power outage NOTE All Batteries should be replaced at least once each year preferably at the beginning of the heating season CAUTION Fire or explosion hazard Can cause property damage sever injur...

Страница 38: ...y Back up pack connection and condition of batteries 4 Check the position of the CONTINUOUS PILOT switch on the Control Module If main burner does not come ON when the manual switch and remote control...

Страница 39: ...usehold cleaner and warm water we recommend gas fireplace glass cleaner contact a local dealer for this product After that the glass should be cleaned two or three times during each heating season dep...

Страница 40: ...RCELAIN PANELS DVTL ONLY PLACING THE OPTIONAL PORCELAIN PANELS INTO THE DVTL41 FIREPLACE 1 Locate the left and right side porcelain pieces 2 Place them into the firebox tight against the side walls an...

Страница 41: ...panels through the small tabs and into the center rear slots in the media tray base 4 Place the two B panels through the small tabs and into the outer rear slots in the media tray base 5 Place the th...

Страница 42: ...28450 Nailing Tab Qty 4 20 R11443 Non Combustible Board Qty 2 21 28451 Rear Standoff Qty 4 22 R11258 Non combustible Board 23 R10499 5 PIN Wire Harness 24 R11007 Control Module 25 R10415 Valve Gas 26...

Страница 43: ...33598 6 0115 Page 43 DVLL EXPLODED VIEW Use Only Manufacturer s Replacement Parts Use of Any Other Parts Could Cause Injury Or Death...

Страница 44: ...me Assembly 17 28441 Valve Cover 18 28450 Nailing Tab Qty 4 19 28428 Vertical Vent Baffle Qty 2 20 28451 Rear Standoff Qty 4 21 R11258 Non combustible Board 22 R10499 5 PIN Wire Harness 23 R11007 Cont...

Страница 45: ...Page 45 DVTL EXPLODED VIEW Use Only Manufacturer s Replacement Parts Use of Any Other Parts Could Cause Injury Or Death 1 2 3 3 5 6 8 10 20 4 18 18 21 15 14 13 12 18 11 11 16 17 29 22 23 24 25 27 28...

Страница 46: ...be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number an...

Страница 47: ...LL If in the event the lamp or lens needs to be replaced follow the instructions below 1 Unplug the remote from the junction box or disconnect all power to the fireplace 2 Remove the decorative front...

Страница 48: ...ct Vent Zero Clearance Gas Fireplace Heater INTERMITTENT PILOT MODERN DVLLFP92 N P 3 TRADITIONAL DVTL41BP90 N P 1 EMPIRE EMPIRE Comfort Systems Clearance to Combustibles Back 1 1 2 in 38 mm Side 1 1 2...

Страница 49: ...e Heater INTERMITTENT PILOT MODERN DVLLFP92 N P 3 TRADITIONAL DVTL41BP90 N P 1 DIMENSIONS in inches metric DVLL DVTL A 51 1 16 129 7cm B 44 1 2 113 0cm C 16 1 2 419mm D 36 5 8 930mm E 24 5 8 625mm F 1...

Страница 50: ...e Empire will repair or replace at Empire s option Duties Of The Owner The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the appl...

Страница 51: ...33598 6 0115 Page 51 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Страница 52: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: