Thermal Calibration of WASPs
To ensure the greatest accuracy of the monitored variables, it is advised to do thermal
calibration of each WASP unit. The process of thermal calibration is as follows:
1. Ensure the machinery for which the WASP is to be attached is at operating
temperature.
2. Place the WASP(s) units at their desired mounting points using thermal paste.
Allow 15 minutes for the temperature to stabilize.
3. Using a reference temperature source (ie. IR Temperature Gun
1
), record the
temperature value at the valve cap at the mounting point of the WASP unit.
4. At the NEST, adjust the display temperature to match the value of the thermometer
gun using the temperature calibration function. (See the section on temperature
calibration in the
Setting Temperature Warning, Critical Error, and Offset Limits
section
in the NEST User Manual).
Notes:
1.
IR Temperature Guns commonly have accuracy ratings of +/- 2% and the
readings can be affected by the distance and angle that the measurements are
taken from.