background image

7

EN

  

4.0 - FIRST START-UP

Before commissioning, verify that:

• all of the instructions on the rating plate, including the direction of flow, are observed;
• the holes of the dust cap (

6

) are not clogged.

• IMPORTANT:

 The leak test of the piping must be performed while avoiding to subject the membrane of the 

regulator (therefore, the downstream pipe section) to a pressure higher than 300 mbar. Use special manual gas 

closing devices to prevent damaging the regulator;

• The pressurisation manoeuvre of the equipment must be carried out very slowly so as to avoid possible damage.

NOTE:

 under no circumstances should a blind cap be placed instead of the dust cap (

6

) as the regulator may 

not work;

• Open the downstream vent valve partially;
• Slowly open the upstream shut-off devices (e.g. solenoid valves, OPSO shut-off valve, etc.);
• Wait until the downstream pressure stabilises at the calibration value P2 of the spring (indicated on the plate);
• Close the vent valve;
• Check the tightness of all the system gaskets and check the internal/external tightness of the regulator;
• Open the downstream shut-off valve very slowly;
• Check the operation of the regulator.

  4.1 - RECOMMENDED PERIODIC CHECKS

• Use a suitable calibration tool to ensure the bolts are tightened as indicated in 3.2;

• Check the tightness of the flanged/threaded connections on the system;

• Check the tightness and operation of the regulator;

It is the responsibility of the final user or installer to define the frequency of these checks based on the severity of the service 

conditions.

  4.2 - ADJUSTING THE OUTLET PRESSURE

Before starting the system, make sure that the spring supplied with the regulator is suitable for the desired adjustment 

pressure. The outlet pressure P2 (unless specifically requested) is factory set with the top cover (

4

) positioned as shown in 

3.2 

a

 and with the adjustment screw (

2

) set approximately at the minimum calibration value. 

If the regulator is installed in different positions, check and reset the outlet pressure P2.
Adjust the outlet pressure as follows:
• Unscrew the cap (

1

);

• Unscrew the adjustment screw (

2

) and set it to the minimum calibration allowed (threaded end of the top cover (

4

));

• Start the system or make sure there is a minimum flow downstream of the regulator;
• To increase the pressure calibration downstream of the regulator, tighten the adjustment screw (

2

) to the desired value. 

Perform the reading with a calibrated pressure gauge, installed downstream of the regulator to at least 5 DN (see example in 3.4);

• Screw the cap (

1

) back on and if necessary, seal it in that position using the appropriate seal holes (if present);

• Use pressure outlets (

13

) on the device only for zero flow or very low flow measurements. 

  4.3 - REPLACING THE SPRING

The step must be carried out without gas inside the regulator.

Replace the spring as follows:
• Unscrew and remove the cap (

1

) from the top cover (

4

);

• Completely loosen and take out the adjustment screw (

2

);

• Remove the spring washer (

26

);

• Remove the spring (

3

) from the top cover (

4

) and replace it with the new spring;

• Place the washer (

26

) on the new spring once again;

• Tighten the adjustment screw (

2

) and after starting the system as shown in 4.0, set the outlet pressure to the desired value 

as shown in 4.2;

• Screw the cap (

1

) back on and if necessary, seal it in that position using the appropriate seal holes (if present);

Содержание 35501216

Страница 1: ...SSURE REGULATOR 356 P1 max 500 mbar DN15 DN 20 DN 25 DN 32 DN 40 DN 50 DN 65 DN 80 DN 100 EN EC approval according to EN 88 1 compliant with Regulation EU 2016 426 CE 51CL4012 ED01 MADE IN ITALY II 2G...

Страница 2: ...2 EN INDEX pag English 3 Drawings 10 Dimensions table 1 13 Regulation spring data table 3 14 Diagram 15...

Страница 3: ...2 KEY OF SYMBOLS ATTENTION Attention is drawn to the technical details intended for qualified staff DANGER In the event of inobservance this may cause damage totangiblegoods topeopleand orpets DANGER...

Страница 4: ...downstream of the regulator IMPORTANT install manual gas closing devices e g ball valves upstream and downstream of the regulator to protect it from any pipe leak test If the device is threaded make s...

Страница 5: ...imum torque has been achieved uniformly Common procedures threaded and flanged devices The regulator is normally positioned before the utility Primarily evaluate the possibility of installing the regu...

Страница 6: ...ns provided in this document it does not pose a source of specific hazards in particular under normal operating conditions the regulator emits a flammable substance into the atmosphere ONLY if both th...

Страница 7: ...E Before starting the system make sure that the spring supplied with the regulator is suitable for the desired adjustment pressure The outlet pressure P2 unless specifically requested is factory set w...

Страница 8: ...ary Make sure the sealing O Ring 18 of the bottom cover 16 is inside the relevant groove before putting it back on Reassemble the bottom cover 16 and secure it in its original position being very care...

Страница 9: ...hts of the warranty or compensation for damage The warranty also excludes maintenance work other manufacturers s assembling units making changes to the device and natural wear 8 0 RATING PLATE DATA Th...

Страница 10: ...10 EN fig 1 Threaded connections in line DN 15 DN 20 DN 25...

Страница 11: ...11 EN fig 2 Threaded connections in line DN 32 DN 40 DN 50...

Страница 12: ...12 EN fig 3 Flanged connections DN 65 DN 80 DN 100 19mm...

Страница 13: ...21 Filter element 22 Top disk for membrane 23 Top cover clamping screws 24 Bottom disk for membrane 25 Membrane disc fixing nut 26 Spring washer Table 2 Screw M5 M6 Max torque N m Galvanised 6 10 Sta...

Страница 14: ...3 23 MO 0850 2 2x29x140x18 20 36 MO 0970 2 5x29x155x16 33 58 MO 1000 3 2x29x123x15 5 55 100 MO 1370 3 5x29x125x14 90 190 MO 1070 4x66 5x155x16 DN 65 DN 80 7 18 MO 1100 4 5x70x200x15 5 13 27 MO 1200 5x...

Страница 15: ...15 EN Capacity diagram Diagram calculated with P1 50 mbar and regulator set out of service dv density relative to the air 1 methane 2 air 3 town gas 4 lpg...

Страница 16: ...he right to any technical and construction changes Registered Office Travis Perkins PLC Lodge Way House Lodge Way Harlestone Road Northampton NN5 7UG Telephone Number 0116 245 5500 www bssindustrial c...

Отзывы: