background image

25

2. 

Clean the fan impeller using the following procedure:

Electro-oil Inter B9 Burner

(a) Remove the two screws holding the combustion head in

position and withdraw the combustion head and air guide
collar (where fitted).

(b) Remove the three remaining screws holding the front

cover plate in position and withdraw the cover to expose
the fan impeller.

(c) Clean both sides of the fan impeller and remove any debris

from the burner housing.

(d) Check that the impeller rotates freely.

(e) Clean the air inlet passage and check that the adjustment

mechanism operates freely.

(f) Re-assemble the components.

Electro Oil Inter B11

(a) Remove the acoustic fan inlet cover.

(b) Remove the three screws holding the fan cowl in position and

remove the cowl noting how the fan control flap is positioned.

(c) Check that the air control flap pivots freely and ensure the

air path to the burner head is clear.

(d) Clean both sides of the fan impeller and remove any debris

from the burner housing.

(e) Check that the impeller rotates freely.

(f) Re-assemble the components.

Electro Oil Sterling

(a)

Remove the air adjustment cover.

(b)

Separate the main body of the burner from the burner
front by removing the M6 allen screw (located beneath the
air adjustment screw), using a 4mm allen key.
Check the condition of the Gasket between these two parts
and replace if necessary.

(c)

Note the position of the air damper adjustment and check
the air damper moves freely.

(d)

Check the air path to the burner head is clear.

(e)

Clean both sides of the fan impeller and remove any debris
from the burner housing.

(f)

Check the impeller rotates freely.

(g)

Re-assemble the components.

Electro Oil Inter B20

(a) Remove the four screws holding the fan cover and remove.

(b) Clean both sides of the fan impeller and remove any debris

from the burner housing.

(c) Check that the impeller rotates freely.

(d) Clean the air damper which is attached to the fan cover

and check that the adjustment mechanism operates
freely.

(e) Re-assemble the components.

3. 

Remove the combustion head and thoroughly clean all deposits.

4. Inspection of Mechanical Shut-off Valve.

a) Remove the nozzle.
b) Fasten an M5 screw, with a minimum length of 30mm, into the
threaded hole (A) and pull the screw to withdraw the check valve.
c) Check that the nozzle holder is clear of any debris and clean if
necessary.
d) Check that the 3 holes in the check valve are clear of any
debris. Discard the check valve if the holes cannot be cleared or
if the unit is defective and replace with a new one.
e) Replace in the reverse order. 

5. 

It is strongly recommended that the oil atomising nozzle is

replaced at each service. If this is not possible then remove and
clean the integral filter, but under no circumstances should the
nozzle be stripped into its component parts and never attempt
to clean the nozzle tip.

6. 

Check and reset the electrodes, where necessary, as shown in

Figs. 18, 19, 20, 21, 22 and 23.

7. 

Replace the combustion head and check that the nozzle lies

central to the combustion head and the head settings are as
shown in Figs. 18, 19, 20, 21, 22 and 23.

8. 

Withdraw the photocell from its housing and clean.

9. 

Remove and clean the oil pump internal filter using kerosene

or white spirit. The internal filter is accessed by removing the oil
pump cover on the Danfoss BFP 11 and Suntec AS47C and by
unscrewing and withdrawing the cartridge on the Danfoss BFP
41 as indicated in Fig. 9. 

10. 

It is recommended that the standard flexible oil line is

replaced at each yearly service to prevent the possibility of a
leak due to ageing.

11. 

Re-assemble the burner components.

12. 

Check the sponge O-ring seal located around the combustion

head and replace if necessary. It is imperative that this seal is in
good condition since failure will cause the flue gases to be re-
circulated into the burner inlet, or the room in the case of a
CF/LLD appliance.

14.4 

Remove the paper element from the external oil filter and

replace. If the filter contains a washable element then
thoroughly clean in Kerosene or white spirit and re-assemble
into the filter.

14.5 Clean the air ducts. 

(RS balanced flue model only).

1. 

Remove the rear duct top cover.

2. 

Shine a light down the rear duct and inspect both the rear and

under duct for any sign of debris and clean where necessary
using a flexible hose connected to a vacuum cleaner. A short
length of garden hose would be suitable for this purpose.

3. 

Replace the rear duct top cover.

4. 

Check that the oil bleed holes are clear. These are located in

the base of the burner cover box and the bottom front face of
the burner housing.

Fig. 26. Mechanical Shut-off Valve.

Top Baffle

(32/50 model

only)

Access Door

Cap Retainer

Cap

Fig. 25.  Location of cap retainer (32/50 and
50/70 models) and  location of top baffle. (32/50
model only).

Содержание WORCESTER DANESMOOR UTILITY 12/14

Страница 1: ...D ROOM SEALED BF FLOOR STANDING OIL FIRED PRESSURE JET APPLIANCES INSTALLATION AND SERVICING INSTRUCTIONS THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE This appliance must be installed and serviced by a competent person Worcester supports the Benchmark code of practice ...

Страница 2: ...ccording to the manufacturers instructions Without the completion of the Log book manufacturers may refuse to respond to a call out from a householder who will be advised that he or she must call back the installer who has not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is...

Страница 3: ... mbar 66mbar 195mbar 3 mbar 6 mbar 12 mbar 19 mbar 7mbar 10mbar 24 g hr 35 kg hr 43 kg hr 57 kg hr 85 kg hr 115 kg hr 55 C minimum cut in o 82 C maximum cut out 5 C 100 0 6 C 110 0 6 C CF RS Model POWER SUPPLY HEATING FLOW HEATING RETURN MINIMUM FLUE REQUIREMENT Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Section 7 3 Section 7 3 Section 7 3 Section 7 3 N A N A 12 14 15 ...

Страница 4: ...0 25 85 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 20 25 Table 4 Electro Oil Inter B11C Burner See Fig 20 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate Flue Gas Temp C CO2 Approx Air Setting Appliance Input kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 85 80 EH 110 2 36 2 99 225 11 0 11 5 11 28 5 97 000 26 89 000 28 Sec Kerosene 0 85 80 EH 130 2 66 3 37 240 11 0 11 5 12 32 ...

Страница 5: ...2 0 12 5 2 75 45 3 154 500 41 140 000 28 Sec Kerosene 1 35 60 S 150 4 6 5 81 220 12 0 12 5 4 75 55 25 188 500 50 171 000 35 Sec Gas Oil 0 85 60 S 210 3 82 4 6 190 12 0 12 5 2 75 45 3 154 500 41 140 000 35 Sec Gas Oil 1 0 60 S 260 4 66 5 61 210 12 5 13 0 6 5 55 25 188 500 50 171 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 32 50 Table 7 Electro Oil Inter B20C Burner See Fig 22 Conventi...

Страница 6: ...e combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are shown in Table 9 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the appliance is to be installed in a confined space or compartment two air...

Страница 7: ...onal pump location Manual reset overheat thermostat Strain relief bush Burner plug in connector High limit thermostat Fire valve clip Side panel Top panel Front panel Thermostat knob Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly ...

Страница 8: ...8 Fig 3 Room Sealed Balanced Flue Appliance RS ...

Страница 9: ...and adjusted to achieve a flue draught within the specified range 7 2 Low Level Discharge LLD See Fig 5 The low level flue kit is not designed for use with this appliance as there is no provision for installation of the flue gas purge timer However where fume odour will not present a problem eg boilerhouse outhouse the flue kit may be used without the purge unit Alternatively a standard Danesmoor ...

Страница 10: ...tension kit a Rear Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall...

Страница 11: ...ance of combustion products An alternative flue terminal position should be sought when there is any possibility of a nuisance being caused by inadequate dispersal of flue products Terminals should be positioned so as to avoid products of combustion entering into buildings Fig 7 Flue terminating positions for oil fired appliances Window Flue Terminal Fig 8 Terminal guard Minimum dimensions 265 280...

Страница 12: ... the burner and the length of pipe run b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A Manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should b...

Страница 13: ...level H 4 m 13 ft maximum Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De...

Страница 14: ...14 Fig 11 Oil Pipe Installation Fig 12 Typical Open Vent Fully Pumped System Honeywell Y plan ...

Страница 15: ...Domestic hot water cylinder Pressure gauge Safety valve To system filling device see Fig 14 Fig 14 System filling and make up Temporary hose Heating return Non return valve Stop cock Auto air vent Fill point Heating return 30mm 12in min above highest point of the system Make up vessel METHOD 1 METHOD 2 Boiler Automatic bypass valve to be fitted where thermostatic radiator valves are fitted on all ...

Страница 16: ...em Pipework Copper pipework must be used when installing the appliance on a sealed system 2 General The system should be installed in compliance with the requirements of BS5449 Part 1 The boiler must be fitted with a spring loaded safety valve set to operate at 3 bar 45 psi and the pipe connections made throughout the system must be capable of sustaining a pressure of up to 3 bar The following is ...

Страница 17: ... junction box remotely from the boiler it can be easily connected into the Worcester Utility Oil Boiler 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER Live Neutral Earth Control Box Connecto...

Страница 18: ... Never use soldered joints on oil supply pipes as this could cause a hazard in the case of a fire 2 Fit an isolating valve at the end of the oil line close to the burner and ensure that the valve is closed Continue from step 11 5 b 5 Room sealed balanced flue appliance a Single pipe suction lift with de aerator For connection of single pipe suction lift with de aerator follow the proceedure as for...

Страница 19: ...sulation is positioned correctly in the bottom of the boiler 3 Check that all baffles are correctly located and the heat shield is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24 4 Check that the baffle retainer is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24c 24d and 24e 5 On the 50 70 remove and discard the transit baffle retainer as s...

Страница 20: ...Check that the flue temperature does not exceed the value specified in Tables 2 to 8 If this is the case then check that the baffles are correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balance...

Страница 21: ...djustment Screw Adjusting disc To adjust the nozzle position undo the locking screw located at the rear of the nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 20 Electro Oil Inter B11 Burner 20 25 model Combustion Head Draught tube Nozzle Nozzle block S...

Страница 22: ...zzle block Spark gap 2 5 3 0mm 0mm 7 5mm A Air guide Remove at 50kW 28sec only Nozzle block 0mm Nozzle 7 5mm Blast tube Spark gap 2 5 to 3mm A Fig 22 Electro Oil Inter B20C Burner 32 50 model Combustion Head PL 10 8 10 6 19 10 E x 78mm Output Fuel Dimension mm kW A 32 28sec Kerosene 3 41 28sec Kerosene 6 50 28sec Kerosene 6 41 35sec Gas Oil 6 50 35sec Gas Oil 6 ...

Страница 23: ... and clean the air intake ducts at the rear and underneath the boiler and the air intake grille at the end of the terminal 5 Check and clean the baffle retainer 20 25 26 32 32 50 and 50 70 models 6 Check and clean the cap retainer 32 50 and 50 70 models 7 Check and clean the baffles 8 Check and clean the heat exchanger surface 9 Check the heat shield 20 25 26 32 32 50 and 50 70 models 10 Check the...

Страница 24: ... the electrical box d Feed the electrical lead back through the grommet seal to give sufficient play to allow withdrawal and inspection of the burner e Slacken the two M6 burner locking screws using a 5mm Allen key and remove the burner b 15 19 c 20 25 and 26 32 ENSURE THAT ALL BAFFLES ARE SEATED IN POSITION a 12 14 Baffle retainer Baffle Baffle Heat shield Fig 24 Location of Boiler Flueway Baffle...

Страница 25: ...ear of any debris and clean if necessary d Check that the 3 holes in the check valve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Replace in the reverse order 5 It is strongly recommended that the oil atomising nozzle is replaced at each service If this is not possible then remove and clean the integral filt...

Страница 26: ...o compress the gasket and tighten the two locking screws using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re emission of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround hous...

Страница 27: ...oiler does not respond to a call for heat Boiler thermostat faulty Check by linking out high limit and control thermostats Programmer open circuit Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion setti...

Страница 28: ...ovement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 746a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 753130 Technical Helpline 08705 266241 Worcester Bosch Group is a trading name of BBT Thermotechnology UK Limited www worcester bosch co uk ...

Отзывы: