background image

gns shown in Fig. 8.

(See Figs. 9, 10 and 11). 

8.1 

Plastic or steel tanks should be installed to BS5410. 

A steel tank should also conform to BS799: part 5 and be arranged
with a slope of 1 in 24 away from the outlet valve with a sludge
cock at its lower end.

8.2 

Do not use galvanised steel tanks or pipework for the oil

supply system.

8.3 

Do not use soldered joints in the oil supply pipework as this

could cause a hazard in the case of a fire.

8.4 

The burners on all appliances are supplied so as to be

connected to a single pipe gravity feed system. Details of how to
convert the burners to a double pipe sub-gravity feed system are
shown in Fig. 9

8.5 Oil Supply System
(a)

Single Pipe System 

If a single pipe system is employed, then the tank must be
positioned such that the oil level does not exceed 4 metres
above the level of the burner oil pump and in addition the oil
level must be at least 0.3 metres above the level of the oil pump.
Should it prove impossible to site the tank below the 4 metres
maximum oil level head breaking device must be installed
between the tank and the burner.

(b)

Double Pipe System

If a double pipe system is used then the maximum suction
height allowable is 3.5 metres.

(c)

Single Pipe Suction Lift with De-aerator

If a single pipe suction lift with a de-aerator is used, the oil tank must
be positioned below the burner. An inlet and return loop should be
created between the de-aerator and oil pump. The oil pump should be
connected as for a double pipe system. Details of how to convert to a
double pipe system are shown in Fig. 9.
Oil inlet and return flexible hoses should be connected to the oil
pump inlet and return ports.
Table 14 is a general guide to determine the maximum allowable
pipe run when using a de-aerator.
Table 14 does not override the de-aerators manufacturers
instructions and should only be used in conjunction with the
manufacturers instructions.
If a non-return valve is not incorporated within the de-aerator
unit, a non-return valve should be fitted in the oil line between
the oil tank and the de-aerator.

NOTE:

If a de-aerator is used it should be fitted externally to the building.

8.6 Oil Supply Pipework
a) 

The oil supply pipe diameter can be determined using Tables 12,

13 and 14 depending on whether a single or double pipe system or
single pipe suction lift system is being installed. Selection of the
correct pipe diameter will depend on the position of the oil storage
tank relative to the burner and the length of pipe run.

b)

The oil supply pipe should be laid as level as possible to avoid

air pockets and unnecessary friction losses.

c) 

The following components should be fitted in the fuel line

between the storage tank and burner:

1. 

A Manual isolating valve installed as close to the tank as possible.

2. 

A fire valve in accordance with BS5410, as shown in Fig 10. The

fire valve should be fitted externally with a fire detection element
located within the appliance case. Use of a capillary type valve will
allow a neat and simple installation. A suitable valve is the KBB
manufactured by Teddington Controls Limited. A spring clip has
been provided behind the electrical panel on CF/LLD models, shown
in Fig 2 and on the burner box on RS models, shown in Fig 3 to
allow a fire valve element to be mounted. Alternatively a fusible link
or electrical system may be used. Under no circumstances should a
combination isolating/fire valve be used as the sole fire protection
device.

3. 

An oil filter should be fitted close to the oil storage tank. If

there is doubt about the internal oil line condition, a further filter
should be fitted near the boiler.

8. Oil Supply

12

Fig. 9. Oil Pump.

B. Danfoss BFP 11 Oil Pump.

A. Danfoss BFP 41.

C. Suntec AS47C Oil Pump.

Cartridge filter

1

2

3

4

4a

5

6

1

2

3

4

5

6

A

1 INLET

2 RETURN

3 BLEED AND PRESSURE

GAUGE PORT

4 VACUUM GAUGE PORT

5 PRESSURE ADJUSTMENT

6 NOZZLE OUTLET

To convert to a double pipe sys-
tem, remove plug 4a and insert
the grub screw provided into the
threaded hole. Connect flow and
return pipes to (1) and (2).

To convert to a double pipe sys-
tem: Remove the pump front
cover, remove the changeover
screw (A) nearest to ports 1 and
2, and the horseshoe washer
underneath. Replace the
changeover screw back into the
threaded hole. Connect the flow
and return pipes to 1 and 2.

Note: 

When removing the pump

front cover ensure that a suitable
receptacle is placed below the
pump to catch the oil residue.

To convert to a double pipe sys-
tem, remove the return port plug
(2) and insert the grub screw (A)
provided into the threaded hole
(B). Connect flow and return pipes
to (1) and (2).

1

2

3

3

4

5

B

A

TABLE 12 Single Pipe Gravity Feed System

MAXIMUM ALLOWABLE PIPE RUN

HEAD (metres)

(metres)

8 mm inside dia. pipe 10 mm inside dia. pipe

(10 mm O.D. copper)

(12 mm O.D. copper)

0.5

12

30

1.0

25

69

1.5

37

91

2.0

49

100

2.5

62

100

3.0

74

100

3.4

87

100

4.0

99

100

TABLE 13 Double Pipe Sub-Gravity Feed System

MAXIMUM ALLOWABLE PIPE RUN

HEAD (metres)

(metres)

8 mm inside dia. pipe 10 mm inside dia. pipe

(10 mm O.D. copper)

(12 mm O.D. copper)

0

50

100

0.5

44

100

1.0

38

95

1.5

32

80

2.0

26

66

2.5

20

51

3.0

14

37

3.5

8

22

Содержание WORCESTER DANESMOOR UTILITY 12/14

Страница 1: ...D ROOM SEALED BF FLOOR STANDING OIL FIRED PRESSURE JET APPLIANCES INSTALLATION AND SERVICING INSTRUCTIONS THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE This appliance must be installed and serviced by a competent person Worcester supports the Benchmark code of practice ...

Страница 2: ...ccording to the manufacturers instructions Without the completion of the Log book manufacturers may refuse to respond to a call out from a householder who will be advised that he or she must call back the installer who has not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is...

Страница 3: ... mbar 66mbar 195mbar 3 mbar 6 mbar 12 mbar 19 mbar 7mbar 10mbar 24 g hr 35 kg hr 43 kg hr 57 kg hr 85 kg hr 115 kg hr 55 C minimum cut in o 82 C maximum cut out 5 C 100 0 6 C 110 0 6 C CF RS Model POWER SUPPLY HEATING FLOW HEATING RETURN MINIMUM FLUE REQUIREMENT Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Section 7 3 Section 7 3 Section 7 3 Section 7 3 N A N A 12 14 15 ...

Страница 4: ...0 25 85 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 20 25 Table 4 Electro Oil Inter B11C Burner See Fig 20 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate Flue Gas Temp C CO2 Approx Air Setting Appliance Input kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 85 80 EH 110 2 36 2 99 225 11 0 11 5 11 28 5 97 000 26 89 000 28 Sec Kerosene 0 85 80 EH 130 2 66 3 37 240 11 0 11 5 12 32 ...

Страница 5: ...2 0 12 5 2 75 45 3 154 500 41 140 000 28 Sec Kerosene 1 35 60 S 150 4 6 5 81 220 12 0 12 5 4 75 55 25 188 500 50 171 000 35 Sec Gas Oil 0 85 60 S 210 3 82 4 6 190 12 0 12 5 2 75 45 3 154 500 41 140 000 35 Sec Gas Oil 1 0 60 S 260 4 66 5 61 210 12 5 13 0 6 5 55 25 188 500 50 171 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 32 50 Table 7 Electro Oil Inter B20C Burner See Fig 22 Conventi...

Страница 6: ...e combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are shown in Table 9 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the appliance is to be installed in a confined space or compartment two air...

Страница 7: ...onal pump location Manual reset overheat thermostat Strain relief bush Burner plug in connector High limit thermostat Fire valve clip Side panel Top panel Front panel Thermostat knob Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly ...

Страница 8: ...8 Fig 3 Room Sealed Balanced Flue Appliance RS ...

Страница 9: ...and adjusted to achieve a flue draught within the specified range 7 2 Low Level Discharge LLD See Fig 5 The low level flue kit is not designed for use with this appliance as there is no provision for installation of the flue gas purge timer However where fume odour will not present a problem eg boilerhouse outhouse the flue kit may be used without the purge unit Alternatively a standard Danesmoor ...

Страница 10: ...tension kit a Rear Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall...

Страница 11: ...ance of combustion products An alternative flue terminal position should be sought when there is any possibility of a nuisance being caused by inadequate dispersal of flue products Terminals should be positioned so as to avoid products of combustion entering into buildings Fig 7 Flue terminating positions for oil fired appliances Window Flue Terminal Fig 8 Terminal guard Minimum dimensions 265 280...

Страница 12: ... the burner and the length of pipe run b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A Manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should b...

Страница 13: ...level H 4 m 13 ft maximum Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De...

Страница 14: ...14 Fig 11 Oil Pipe Installation Fig 12 Typical Open Vent Fully Pumped System Honeywell Y plan ...

Страница 15: ...Domestic hot water cylinder Pressure gauge Safety valve To system filling device see Fig 14 Fig 14 System filling and make up Temporary hose Heating return Non return valve Stop cock Auto air vent Fill point Heating return 30mm 12in min above highest point of the system Make up vessel METHOD 1 METHOD 2 Boiler Automatic bypass valve to be fitted where thermostatic radiator valves are fitted on all ...

Страница 16: ...em Pipework Copper pipework must be used when installing the appliance on a sealed system 2 General The system should be installed in compliance with the requirements of BS5449 Part 1 The boiler must be fitted with a spring loaded safety valve set to operate at 3 bar 45 psi and the pipe connections made throughout the system must be capable of sustaining a pressure of up to 3 bar The following is ...

Страница 17: ... junction box remotely from the boiler it can be easily connected into the Worcester Utility Oil Boiler 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER Live Neutral Earth Control Box Connecto...

Страница 18: ... Never use soldered joints on oil supply pipes as this could cause a hazard in the case of a fire 2 Fit an isolating valve at the end of the oil line close to the burner and ensure that the valve is closed Continue from step 11 5 b 5 Room sealed balanced flue appliance a Single pipe suction lift with de aerator For connection of single pipe suction lift with de aerator follow the proceedure as for...

Страница 19: ...sulation is positioned correctly in the bottom of the boiler 3 Check that all baffles are correctly located and the heat shield is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24 4 Check that the baffle retainer is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24c 24d and 24e 5 On the 50 70 remove and discard the transit baffle retainer as s...

Страница 20: ...Check that the flue temperature does not exceed the value specified in Tables 2 to 8 If this is the case then check that the baffles are correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balance...

Страница 21: ...djustment Screw Adjusting disc To adjust the nozzle position undo the locking screw located at the rear of the nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 20 Electro Oil Inter B11 Burner 20 25 model Combustion Head Draught tube Nozzle Nozzle block S...

Страница 22: ...zzle block Spark gap 2 5 3 0mm 0mm 7 5mm A Air guide Remove at 50kW 28sec only Nozzle block 0mm Nozzle 7 5mm Blast tube Spark gap 2 5 to 3mm A Fig 22 Electro Oil Inter B20C Burner 32 50 model Combustion Head PL 10 8 10 6 19 10 E x 78mm Output Fuel Dimension mm kW A 32 28sec Kerosene 3 41 28sec Kerosene 6 50 28sec Kerosene 6 41 35sec Gas Oil 6 50 35sec Gas Oil 6 ...

Страница 23: ... and clean the air intake ducts at the rear and underneath the boiler and the air intake grille at the end of the terminal 5 Check and clean the baffle retainer 20 25 26 32 32 50 and 50 70 models 6 Check and clean the cap retainer 32 50 and 50 70 models 7 Check and clean the baffles 8 Check and clean the heat exchanger surface 9 Check the heat shield 20 25 26 32 32 50 and 50 70 models 10 Check the...

Страница 24: ... the electrical box d Feed the electrical lead back through the grommet seal to give sufficient play to allow withdrawal and inspection of the burner e Slacken the two M6 burner locking screws using a 5mm Allen key and remove the burner b 15 19 c 20 25 and 26 32 ENSURE THAT ALL BAFFLES ARE SEATED IN POSITION a 12 14 Baffle retainer Baffle Baffle Heat shield Fig 24 Location of Boiler Flueway Baffle...

Страница 25: ...ear of any debris and clean if necessary d Check that the 3 holes in the check valve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Replace in the reverse order 5 It is strongly recommended that the oil atomising nozzle is replaced at each service If this is not possible then remove and clean the integral filt...

Страница 26: ...o compress the gasket and tighten the two locking screws using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re emission of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround hous...

Страница 27: ...oiler does not respond to a call for heat Boiler thermostat faulty Check by linking out high limit and control thermostats Programmer open circuit Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion setti...

Страница 28: ...ovement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 746a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 753130 Technical Helpline 08705 266241 Worcester Bosch Group is a trading name of BBT Thermotechnology UK Limited www worcester bosch co uk ...

Отзывы: