Commissioning

 

 

Natural Gas Inlet Pressure Adjustment 

With the gas supply turned off, remove sealing screw from inlet pressure test point located on 

the right hand side of the gas section refer Fig. 4 pos.A, attach manometer. Turn on gas and 

light heater. Open hot water tap fully and adjust gas pressure regulator to 0.95 - 1.05 kPa . 

Turn off gas and water, remove manometer, replace sealing screw and test for escape. 

 

Natural Gas Burner Pressure Adjustment 

Turn off gas supply, loosen captive screw in burner pressure test point, left hand side of 

burner manifold refer Fig.5 Pos A, attach manometer turn on hot water tap fully and check 

pressure. 

Adjust pressure by turning the knurled wheel clockwise to increase gas pressure, anti 

clockwise to decrease. refer Fig 4 Pos.E 

 

LP Gas Pressure Adjustment 

No adjustment is provided at the appliance for inlet pressure, check cylinder regulator and 

pipe sizing. 

Adjust burner pressure same as for Natural Gas. 

For LP Gas we recommend the installation of two or more supply 

cylinders and an auto change over pressure regulator 

Fig. 4 

Fig 5 

 

Maintenance 

We recommend that the appliance be inspected and cleaned by an authorised person 

periodically, depending upon the frequency and duration of its operation, but never less than 

once a year. 

 

Содержание Water Wizard 600

Страница 1: ...d only by an authorised person This appliance is not suitable for use as a pool heater The authorised installing person is responsible for 1 Correct commissioning of this appliance 2 Ensure unit performs to the specifications stated on the rating label 3 Demonstrate operation of unit to customer before leaving 4 Hand these instructions to customer Failure to install this appliance in accordance wi...

Страница 2: ...m type in cold water supply A non return valve must not be fitted Example duo valve We recommend that all hot water pipes be lagged if the runs are long or exposed and water proof lagging should be used on all external hot water pipes If the water supply pressure exceeds 80 of the specified maximum install a pressure limiting valve If installing a pressure limiting valve fit a cold expansion valve...

Страница 3: ...ight hand corner of the back panel for additional data Freezing Weather In areas where the atmospheric temperature may drop below 0 C the heater must be drained to prevent damage by expansion of freezing water For appliances installed in locations where the temperature falls below 0 C for brief periods the installation of an EXOGEL expansion valve part number H 707 060 151 will minimise the possib...

Страница 4: ...rate as indicated in Fig 3 Refit front cover and tighten screws Fig 3 Warning If the pilot light is extinguished wait 5 minutes before attempting to relight the appliance If the appliance does not operate burns with yellow flame leaks water or a gas smell is evident turn off and contact the local gas authority the manufacturer or an authorised service person When attempting to light the appliance ...

Страница 5: ...nt left hand side of burner manifold refer Fig 5 Pos A attach manometer turn on hot water tap fully and check pressure Adjust pressure by turning the knurled wheel clockwise to increase gas pressure anti clockwise to decrease refer Fig 4 Pos E LP Gas Pressure Adjustment No adjustment is provided at the appliance for inlet pressure check cylinder regulator and pipe sizing Adjust burner pressure sam...

Страница 6: ... and pipe size Check appliance regulator Check thermostat bellows Check thermostat insert Low water temperature Water flow rate set too high Low gas pressure Thermostat faulty out of adjustment Set flow rate Check pressure Replace Adjust thermostat Low water flow Low water pressure Blocked water valve Blocked heat exchanger Blocked shower rose or tap aerator Check and adjust Clean filter Descale C...

Страница 7: ...placement or repair at the option of RBAU of any defective products and of such parts of RBAU s products as have been damaged in consequence of the defect despite proper treatment Parts replaced will not be returned c I Repairs and maintenance shall not extend the warranty period of the appliance ii If the product is located outside of the service agent s area the consumer shall be responsible for...

Отзывы: