Product Information
5
Uni Condens 8000 F – 6720867056 (2016/10)
H
Combustion/room air
▶ Keep the combustion/ambient air free of corrosive
substances (e.g. halogenated hydrocarbons that
contain chlorine or fluorine compounds). This will
help to prevent corrosion.
▶ Keep the combustion air supply free of dust.
H
Danger posed by explosive and easily
flammable materials
▶ Never use or store easily flammable materials
(e.g. paper, thinners, paints, etc.) near the
appliance.
H
Risk of damage to the system from frost
When the heating system is not in operation
(e.g. controller switched off, fault shutdown),
there is a risk of it freezing when there is frost.
In order to protect the heating system from freezing
when shutting down or switching off for extended
periods:
▶ Drain the heating system and DHW pipework at the
lowest point.
H
Inspection and servicing
▶
Recommendation for customers:
Arrange a
maintenance and inspection contract with an
approved contractor, covering an annual inspection
and responsive maintenance.
▶ The user is responsible for ensuring the heating
system is safe and environmentally compatible.
▶ Immediately correct all faults to prevent system
damage!
▶ Use only genuine spare parts from the
manufacturer. Losses caused by the use of spare
parts and accessories not supplied by the
manufacturer are excluded from the manufacturer's
warranty.
H
Handover to the user
When handing over, instruct the user how to operate
the heating system and inform the user about its
operating conditions.
▶ Explain how to operate the heating system and draw
the user's attention to any safety relevant action
▶ Explain that conversions and repairs must only be
carried out by a competent person.
▶ Point out the need for inspections and maintenance
for safe and environmentally-compatible operation.
▶ Leave the installation instructions and the
operating instructions with the user for
safekeeping.
2
Product Information
2.1
Declaration of Conformity
The design and operation of this product comply with European
Directives and the supplementary national requirements. Conformity
has been demonstrated by the CE marking.
You can ask for a copy of the declaration of conformity for this product.
For this see the contact address on the back cover of these instructions.
2.2
Determined use
The product may only be used for the heating of central heating water
and for DHW heating in closed-loop DHW and heating systems.
The product is only approved for open-flue mode.
Any other use is considered inappropriate. We take no responsibility for
damage caused through incorrect use.
When installing and operating the heating system observe the following:
• Standards, regulations and directives of the relevant country
• Data plate of boiler
• Requirements for the control unit (
chapter 7.1, page 25).
• Requirements for the burner (
chapter 4.2, page 13)
• Requirements for the safety equipment (
chapter 2.10, page 10)
• Requirements for the water quality of the heating water
(
chapter 4.6, page 14)
2.3
Symbols at the boiler
2.4
Scope of delivery
▶ After delivery, check that all packaging is undamaged.
▶ Check the scope of delivery for completeness:
– Boiler body with casing
– Front cover
– Control unit retainer and cable conduit
(in the combustion chamber)
– Sound insulation strips
– Siphon in the combustion chamber
– Insulating rings for blast tube in the combustion chamber
– Technical documents
2.5
Required accessories
The following accessories are not part of the standard delivery, but are
required to operate the boiler:
• Burner
• Burner plate, drilled or undrilled
• Fitting assembly/boiler safety assembly
• Safety equipment
• Condensate neutraliser (if required by regulations)
• Cleaning brushes
• Control unit
Further optional accessories are listed on the Bosch Commercial and
Industrial website.
This symbol is used to point out that the installation and
operating instructions must be read prior to installation
operation or maintenance in order to prevent damage to the
system.
This symbol is used to point out that the
accessories package must be taken out
of the combustion chamber before work
starts.
Содержание Uni Condens 8000 F
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ...Bosch Thermotechnik GmbH Junkersstrasse 20 24 D 73249 Wernau www bosch thermotechnology com ...