Installation
Uni Condens 8000 F – 6720867056 (2016/10)
16
6
Installation
When installing and operating the heating system:
▶ Comply with standards, regulations and directives of the relevant
country.
▶ Observe the information on the data plate of the boiler.
6.1
Positioning the appliance
DANGER:
Risk to life through poisoning!
Insufficient ventilation can lead to dangerous flue gas leaks!
▶ Never close off or reduce the size of ventilation and extract air vents.
▶ Never operate the boiler unless faults are rectified immediately.
▶ Inform the operator in writing of any faults and their associated risks.
DANGER:
Risk of fire through flammable materials or liquids.
▶ Never store flammable materials or liquids in the immediate vicinity
of the heat source.
NOTICE:
Risk of damage to the system from frost!
▶ Install the heating system in a room protected from the risk of frost.
Minimum clearances
Observe the specified minimum wall clearances for the foundations or
installation surface (
fig. 9, page 16 and tab. 11, page 16).
The surface on which the boiler is to be positioned must be of load-
bearing capacity, even and level. The front edge of the boiler should be
flush with the edge of the plinth.
The burner door can be fitted to open from right to left or vice-versa
(
chapter 6.9.1, page 20).
Allow extra space if a flue gas silencer or control unit are to be installed
on the side of the boiler.
Fig. 9
Installation location with boiler (with door opening to the right)
Table 11 Specified wall clearances (dimensions in brackets are
minimum clearances)
Boiler size
800 W
1000 KW
1200 kW
A
H
[mm]
1)
1) If using a flue gas silencer, take its installation dimensions into account.
1000 (800)
1000 (800)
1000 (800)
A
V
[mm]
2)3)
2) Factor in dimension L
BR
(burner length) subject to burner overhang.
3) Dimensions also subject to the burner length LBR
1800 (900)
1800 (900)
1800 (1100)
L
BR
in mm
Burner
800 (200)
Burner
800 (200)
Burner
800 (200)
L
RG
[mm]
906
906
906
Installation
clearance
control unit
Cable conduit
Length (L)
foundations
2300
2300
2300
Width (B)
foundations
1060
1140
1140
B
L
A
H
400
(100)
0010014757-001
L
RG
A
V
L
BR
Содержание Uni Condens 8000 F
Страница 45: ......
Страница 46: ......
Страница 47: ......