Select Option 1 in Location 493 to program the codepad Panic Alarm as silent (refer to System
Options 2, page 139). A codepad Panic Alarm transmits Contact ID Event Code 120 if the
system reports to a base station receiver.
Codepad fire alarm
An audible codepad Fire Alarm activates when a user presses [4] and [6] on the remote
codepad simultaneously. A distinct fire sound emits through the horn speaker to indicate this
type of alarm. The fire sound is different than the burglary sound.
Select Option 2 in Location 493 to program the codepad Fire Alarm as silent (refer to System
Options 2, page 139). A codepad Fire Alarm transmits a Contact ID Event Code 110 to a base
station receiver.
Codepad medical alarm
An audible codepad Medical Alarm activates when a user presses [7] and [9] simultaneously.
Select Option 4 in Location 493 to program codepad Medical Alarm as silent (refer to System
Options 2, page 139). A codepad Medical Alarm transmits a Contact ID Event Code 100 to a
base station receiver.
Isolating zones
Isolating zones allows you to manually disable one or more zones before arming the system in
AWAY Mode, STAY Mode 1, or STAY Mode 2. When a zone is isolated, access is allowed into
that zone when the system is armed without activating an alarm.
For example, you might want to isolate a zone before arming the system because a zone
passive infrared (PIR) detector is activating false alarms or because you need to leave a pet
inside a particular zone while you are away.
You can isolate zones using one of two methods. By default, the standard isolation method is
used. Standard isolation does not require a User Code. The other method requires a valid User
Code. The ability to isolate zones is determined by the priority level assigned to each User
Code holder. Some User Code holders cannot isolate zones. Refer to User Code Priority, page
89 for more information.
Zones that are manually isolated using this method transmit a Zone Bypass Report (Contact ID
Event Code 573) for each isolated zone when the system is armed. A Zone Bypass Restore
Report is transmitted when the system is disarmed.
When you select a 24-Hour Fire Zone to be isolated, a Contact ID Event Code 571 is sent. If
you select another 24-Hour Zone to be isolated, a Contact ID Event Code 572 is sent. A Zone
Bypass Report is transmitted once the 24-Hour Zone is isolated. A Zone Bypass Restore
Report is transmitted when the system is disarmed or the isolated zone is restored.
You can isolate zones manually using these two methods, and you can also isolate zones
automatically as programmed by the installer.
How to isolate zones automatically in STAY Mode 1, refer to Zone Options 2, page 101.
How to isolate zones automatically in STAY Mode 2, refer to STAY Mode 2 Automatically Bypass
Zones, page 106.
Standard isolating
Standard isolating allows any operator to isolate zones because no code is required.
1.
Press [STAY] twice. Three beeps sound and the STAY indicator flashes.
2.
Enter the number of the zone to be isolated and press [STAY]. The indicator for the zone
flashes. 24-Hour zones are automatically isolated as soon as you press [STAY]. All other
Burglary Zones are automatically isolated only after the system is armed.
6.9
6.10
6.11
6.11.1
Control Panel
System Operations | en
35
Bosch Security Systems, Inc.
Installation Guide
2017.10 | 03 | F.01U.298.026