Security Escort
System menus and dialogs | en
201
Robert Bosch (SEA) Pte Ltd
Training Manual
2017.08 | V2.18.1.0 | DOC
Figure 8.18: Popup Trouble Filter Dialog
Transponder troubles group
Communications failure
To continually assure that communications between the Central
Console and each transponder are functioning properly, each
transponder is required to send a message to the Central Console
periodically. If there is no response from the transponder, the
Central Console displays a communications failure warning and
records the condition in the audit file.
If a transponder determines it lost communications with the
Central Console, it assumes control of the outputs of the devices
connected to it and transmits “I’M OK” messages until it is
acknowledged by the Central Console.
Notice!
If during this loss of communications, an alarm transmission is received by one or more of the
receivers attached to the transponder, the transponder activates any alert units attached to it
as well as the horns and red LED’s on any of its receivers which detected the alarm
transmission. Since the transponder does not have access to the
Subscriber Database
, it
must assume that all transmitters are valid, so even unauthorized (not in the
Subscriber
Database
) transmitters produce audible alarm indications (if the system is set for audible
alarms in the
Set Security Preferences
dialog).