7-12
Connections
IPC 40.2
DOK-SUPPL*-IPC*40.2***-PR02-EN-P
This connection is used for device variants for 230/115 VAC.
All internally required voltages are generated by the 230/115 VAC power
supply unit.
CAUTION
The supply voltage must comply with
overvoltage category II! Otherwise the
integrated power supply unit might be
destructed.
⇒
Use an isolating transformer to generate the
230/115 VAC (see following page).
The 230/115 VAC connection occurs via a 3-pin inlet connector for non-
heating apparatus on the connector panel. The maximum cable cross
section for the connected cables is 1.5 mm
2
.
X20
Assignment
PE
N1
U2
PE
230V_Buchse.cdr
Fig. 7-15:
Pin assignment of the 230/115 VAC connection X20
Parameters
Value
Rated voltage
85 VAC ... 264 VAC auto range
Power consumption for U
N
= 230 VAC
0.7 A
Power consumption for U
N
= 115 VAC
1.4 A
Inrush current for U
N
= 230 VAC
30 A cold start 25
°
C
Inrush current for U
N
= 115 VAC
15 A cold start 25
°
C
Line-side fuse
1.6 A (5x20)
Fig. 7-16: Technical data 230/115 VAC connection
X20 – 230/115 VAC Power
Supply