ECODRIVE DKC02.1 Drive Controller
DC24V power supplies NTM
7-3
DOK-ECODRV-DKC02.1****-PRJ2-EN-P
LED green = output
voltage applied
Potentiometer for fine
adjustments of output
voltage
Input
voltage
S+ sensor input
S- sensor input
Input voltage
setting
via bridge
A/B not connected, input voltage AC (170-265) V
A/B connected with bridge, input voltage AC (85-132) V
V+/S+ or V-/S- are connected with bridges
Remove the bridges for using the sensor inputs.
Zero point V-
2)
2)
1)
Output
voltage
Protective ground
FA0200D4.fh5
V+
V-
FG
L
N
A
B
DC 24 V V+
1)
2)
1)
Fig. 7-4:
Front view and terminal designations of the power supplies NTM01.1-
024-004 and NTM01.1-024-006
7.5 Electrical
connection
Always use the NTM together with the line filter NFE01.1-230-006.
AP0202D4.fh5
NFE01.1
-230-006
L
N
NTM ...
L
N
+DC 24 V
P
N
E
P'
N'
V+
V-
0 V
Mains section
RF interference suppression filter
PE
Fig. 7-5: Connecting the power supply to a line filter
Note: The bridge circuits V+/S+ and V-/S- must be removed if sensor
inputs are used.
AP0227D4.fh5
NTM
Input DC 24 V
V+
V-
S+
S-
Load
Strand sensor line
Mains section
Fig. 7-6:
Connecting the sensor leads NTM01.1-024-004 and
NTM01.1-024-006
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01