Rexroth IndraDrive C HCS03.1
Electrical Data
6-11
DOK-INDRV*-HCS03.1****-PR02-EN-P
Designation
Symbol
Unit
Value
HCS03.1E-W0100
P
N3
W
approx. 25
HCS03.1E-W0150
P
N3
W
approx. 25
HCS03.1E-W0210
P
N3
W
approx. 30
internally generated control
voltage
U
N3
V
24 ±10%
(not used for supplying the motor holding brake)
*:
data without motor holding brake and control section taken into
account
Fig. 6-13:
Control voltage
Note:
Overvoltage of more than 33V has to be discharged by means
of the appropriate electrical equipment of the machine or
installation.
This includes:
•
24V power supply units that reduce incoming overvoltages
to the allowed value.
•
Overvoltage limiters at the control cabinet input that limit
existing overvoltage to the allowed value. This, too, applies
to long 24V lines that have been run in parallel to power
cables and mains cables and can absorb overvoltages by
inductive or capacitive coupling.
Block Diagram of Control Voltage Generation from the
DC Bus
24 V
BSHC0004DE00.FH9
Br
LT
ST
int.
SMPS
ZK
Br:
brake circuit
LT:
power section
ST:
control section
SMPS:
internal switching-mode power supply
ZK:
DC bus
Fig. 6-14:
Block diagram of internal control voltage generation
Содержание Rexroth IndraDrive C HCS03.1
Страница 6: ...IV Contents Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Страница 12: ...1 6 Indroduction Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Страница 30: ...4 4 Identification Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Страница 38: ...5 8 Mechanical Data Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Страница 72: ...8 6 Replacing Devices Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Страница 74: ...9 2 Disposal and Environmental Protection Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Страница 84: ...11 4 Index Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Страница 85: ......