Danger of death by high electrical voltage.
DANGER
●
Connect power supply units, which generate protective extra-low voltage
(PELV) (24 V), only to supply voltages for which the power supply units are
designed. Comply with the overvoltage categories, see
●
Do not apply the supply voltage to the protective extra-low voltage (PELV)
Wiring 400 V
PE PE PE
PE
PE
PE
6 mm² (green/yellow)
16 mm² (green/yellow)
Min. 16 mm² (green/yellow)
PE neutral point
230V
400V
4 mm² (green/yellow)
16 mm² (green/yellow)
4 mm² (green/yellow)
Fuses, better: protective motor switches
e.g. drives
Transformer
acc. to EN 60742
W1 N
V1
U1
L1 L2 L3 N
Leads
L1.1 L2.1 L3.1 N
PE
PE
N
U2
PE N1 U2
4 mm² (green/yellow)
Overvoltage
category II
230 V power supply
operator terminals
service plug receptacle(s)
N conductor:
Use only with
permission of
the operator!
=
+24 V
0 V
DC 24 V
L1.1 L2.1 L3.1 PE
PE
1
To the housing of the control cabinet
To the device
All housing parts (functional earth)
Overvoltage
category III
Power
supply unit
Terminals in
isolated
arrangement
Overvoltage
category I
①
PE bars are to be installed preferably on the mounting plate. In case of isolated PE bars,
connect both ends to the mounting plate by means of copper strips with a maximum
length of 20 cm. The cross-section of the copper strips has to be at least equal to that of
the incoming mains cable.
Fig. 10-16: Wiring 400 V
Bosch Rexroth AG
Mounting, demounting and electric installation
VEP 07.6/15.6 Multi Touch
34/49
DOK-SUPPL*-VEPXX.6MTHU-IT01-EN-P
Содержание Rexroth IndraControl
Страница 6: ...Bosch Rexroth AG VEP 07 6 15 6 Multi Touch IV DOK SUPPL VEPXX 6MTHU IT01 EN P ...
Страница 50: ...Bosch Rexroth AG VEP 07 6 15 6 Multi Touch 44 49 DOK SUPPL VEPXX 6MTHU IT01 EN P ...
Страница 53: ...VEP 07 6 15 6 Multi Touch Bosch Rexroth AG DOK SUPPL VEPXX 6MTHU IT01 EN P 47 49 ...
Страница 54: ...Bosch Rexroth AG VEP 07 6 15 6 Multi Touch 48 49 DOK SUPPL VEPXX 6MTHU IT01 EN P ...
Страница 55: ...Notes VEP 07 6 15 6 Multi Touch Bosch Rexroth AG ...