10.4.2
Connecting the Panel PC to the UPS
Connection scheme
10 mm² (green/yellow)
6 mm² (blue)
PE bar
A
B
A
Overvoltage category I
(4)
6 mm²
a
connect to functional earth ground of the operator display.
6 mm²
a
connect to functional earth ground of the control cabinet PC.
6 mm²
a
connect to functional earth ground of the UPS (VAU 01.1).
X1S2
UPS
(VAU 01.1)
0V OUT
24V OUT
X1S1
0V IN
24V IN
X10
+
-
(2)
0 V
10 mm²
(1)
(4)
(3)
16 A
24 V
Terminal block UK6-FSI/6
with automatic cut-out TCP 10 A
(PHOENIX CONTACT) is recommended
Functional earth ground
Functional earth ground
VSP xx.3
Panel PC
(green/yellow)
A Terminal block 4 mm
2
B Terminal block 10 mm
2
① Easily removable and visible.
② Cable length between UPS and panel
PC max. 2 m at a minimum cross-
section of 2.5 mm
2
.
③ Polarity reversal of the XS1 and X10
connectors might destruct the device
(fire hazard), if there is no additional
external protection. The reason for this
is the grounding of the 0 V in the de‐
vice and simultaneously to that the
grounding of the 0 V (PELV) (1).
④ Cable length between 24 V power
supply unit and UPS max. 2 m at a
minimum cross-section of 5 mm
2
.
Other values apply to hard-wired con‐
nections, see documentation of the
UPS "VAU01.1".
Fig.10-5: Panel PC connected to a UPS
11
Commissioning
The product can be used directly, no configuration is required.
DOK-SUPPL*-VSP*XX.3***-IT01-EN-P
Rexroth IndraControl VSP xx.3 Panel PC
Bosch Rexroth AG
Commissioning
27/43