For proper function of the motor thermal management connect the motor
thermal sensor as described in the wiring diagram. Otherwise motor
overtemperature sensing is not provided by the drive.
For Rexroth motors with data memory in the motor encoder, such as MSK,
the motor overload protection level is set automatically while connecting the
motor to the drive. There is no adjustment necessary. Otherwise refer to the
Rexroth firmware documentation.
4.2.2
Connection points
Symbols used to describe the connection points
Screw terminal block
Spring terminal
Thread
Max. connection cross
section
Max. tightening torque
Tab. 4-1:
Symbols
Connection point
HMS01
mm
2
(AWG)
Nm
X5
A
1)
4,0 (10)
0,6
B
2)
16,0 (6)
1,7
C
3)
M6
1×16; 1×25; 1×35
2×16; 2×25; 2×35
(1×6; 1×4; 1×2; 1×1
2×6; 2×4; 2×2; 2×1)
6,5
D
4)
M6
1×16; 1×25; 1×35; 1×50
2×16; 2×25; 2×35; 2×50
(1×6; 1×4; 1×2; 1×1
2×6; 2×4; 2×2; 2×1)
6,5
E
5)
M10
1×16; 1×25; 1×35; 1×50; 1×70; 1×120
2×16; 2×25; 2×35; 2×50; 2×70; 2×120
(1×6; 1×4; 1×2; 1×1; 1×1/0; 1×2/0; 1×4/0
2×6; 2×4; 2×2; 2×1; 2×1/0; 2×2/0; 2×4/0)
20
X6
A, B, C, D, E
1,5 (16)
-
24V, 0V
L+, L-
A, B, C, D, E
M6
6,5
IndraDrive Drive Controllers Power Sections HMS01
21/27
Instructions for use
R911319996_Edition 08 Bosch Rexroth AG