Fig. 5-28:
Example of arrangement for multiple-line structure with components
Arrangement of Cooling Units
CAUTION
Possible damage to the drive controller
Operational safety of the machine endangered!
Note the following instructions!
Due to the operating principle, condensation water is formed when cooling
units are used. For this reason, please observe the following information:
•
Always position cooling units in such a way that condensation water
cannot drip onto electronic equipment in the control cabinet.
•
Position the cooling unit in such a way that the blower of the cooling
unit does not spray accumulated condensation water onto electronic
equipment.
Avoiding Dripping or Sprayed
Water