en | Tones
PRAESENSA
2020-09 | V1.20 | PRAESENSA 1.20
Configuration manual
Bosch Security Systems B.V.
–
Alarm_MS_800-970Hz_100%_10x1s.wav
–
Sweep 800 Hz - 970 Hz, up in 1 s, 10 repetitions
–
Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
UK, BS 5839-1 “Fire”
–
Alarm_MS_800-970Hz_100%_70x0.14s.wav
–
Sweep 800 Hz - 970 Hz, up in 0.14 s, 70 repetitions
–
Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
UK, BS 5839-1 “Fire”
–
Alarm_MS_800-970Hz_25%_3x(0.5+0.5)s+1s.wav
–
Sweep 800 Hz - 970 Hz, up in 0.5 s, 0.5 s off, up in 0.5 s, 0.5 s off, up in 0.5 s, 1.5 s
off
–
Duty cycle 25%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
ISO 8201
–
Alarm_MS_970Hz_25%_3x(0.5+0.5)s+1s.wav
–
Intermittent 970 Hz, 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off
–
Duty cycle 25%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
ISO 8201 “Low tone”
–
Alarm_MS_970Hz_20%_8x(0.25+1.00)s.wav
–
Intermittent 970 Hz, 0.25 s on, 1 s off, 8 repetitions
–
Duty cycle 20%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
“General purpose”
–
Alarm_MS_970Hz_50%_5x(1+1)s.wav
–
Intermittent 970 Hz, 1 s on, 1 s off, 5 repetitions
–
Duty cycle 50%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
UK, BS 5839-1 “Alert”, PFEER “Alert”
–
Alarm_MS_970Hz_100%_10s.wav
–
Continuous 970 Hz, 10 s
–
Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
UK, BS 5839-1 “Evacuate”, PFEER “Toxic gas”
–
Alarm630Hz_100%_10x(0.5+0.5)s.wav
–
Alternating 970 Hz, 0.5 s and 630 Hz, 0.5 s, 10 repetitions
–
Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
UK, BS 5839-1
–
Alarm_2000Hz_100%_10x(0.5+0.5)s.wav
–
Alternating 1000 Hz, 0.5 s and 2000 Hz, 0.5 s, 10 repetitions
–
Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
Singapore
–
Alarm_MS_1200-500Hz_100%_10x1s.wav
–
Sweep 1200 Hz - 500 Hz, down in 1 s, 10 repetitions
–
Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
Germany, DIN 33404 Part 3, PFEER “Prepare for evacuation”
–
Alarm_MS_1400-1600-1400Hz_100%_8x(1.0+0.5)s.wav
–
Sweep 1400 Hz - 1600 Hz, up in 1.0 s, down in 0.5 s, 8 repetitions
–
Duty cycle 100%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
France, NFC 48-265
–
Alarm_MS_2850Hz_25%_3x(0.5+0.5)s+1s.wav
–
Intermittent 2850 Hz, 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off
–
Duty cycle 25%, Peak level -1.3 dBFS, RMS level <-9 dBFS
–
USA, ISO 8201 “High tone”