Technical data
Master Unit
Electrical
Mains power supply
Voltage
115 / 230 VAC, ±10%, 50/60 Hz
Fuse rating
T6.3 A, 250 V
Inrush current
Time: < 10 ms; ≤ 30 A
Max. power consumption
150 W
Battery power supply
Voltage
18 – 56 VDC nominal 24 or 48 VDC
Backup fault detection level
21 ± 1 VDC
Max. backup power current
4.5 A
Hardware Interfaces
100 V audio I/O (loop 1‑6)
Pluggable screw connector
Fault output (loop 1‑6)
Floating contacts 24 V, 1 A
Fault relays except general fault relay
–
OK state is normally de-energized
–
NO is open
General fault relay
–
OK state is Failsafe, normally energized
–
NC is open (failsafe)
Performance
Max. number of Isolator Boards in loop
50
Power handling capacity per loop
500 W
Frequency range
50 Hz – 20 kHz
Max. sum blocking capacitance
Max. sum blocking capacitance per loop
4700 µF
Max sum blocking capacitance per tap-off
220 µF