Combining installation options
The three installation options can be combined as shown in the following figure:
1
2
3
4
4
6
6
6
6
6
6
4
5
5
3
5
7
8
Figure 4.4: Combining installation options
No. Item
Combined Installation
1
Zone output of public
address/voice alarm system
–
100 V constant voltage line (50 Hz – 20 kHz), 500 W
power handling capacity.
2
Master Unit
–
See Connections indicators and controls, page 31.
–
See DIP switch settings, page 41.
3
Loudspeaker loop
–
See Connections indicators and controls, page 31.
4
Isolator Board
–
Isolator Board configured for installation option 1, 2
or 3.
–
Set the jumper settings on the Isolator Boards, as
required.
5
Loudspeaker
–
Each loudspeaker connected to tap-off connection of
an Isolator Board or DC Blocking Board.
6
DC Blocking Board
–
DC Blocking Boards connected to loudspeakers, as
required.
7
Tap-off for loudspeakers
–
According to some standards, a maximum of 25
loudspeakers can be connected to an Isolator Board
tap-off or in a segment.
8
End-of-line resistor
–
47 kohm, > 0.5 watt resistor connected across the
unused loop terminal of the last DC Blocking Board
in the branch.
–
Open-circuit detection is typically used when
multiple loudspeaker are connected to the tap-off or
when one of the loudspeaker is connected to the
Isolator Board at a distance.
–
Whether or not a branch should be monitored for
open circuits depends on local standards.
See also
–
4.3.4
Loudspeakers Line Isolator System
Planning | en
27
Bosch Security Systems B.V.
Installation and Operation Manual
2014.03 | V1.1 |