en | Troubleshooting
Battery Charger
180110011Aa | V1.1 | 2011.05
Installation and Operation manual
Bosch Security Systems B.V.
9
Troubleshooting
Problem
Cause
Solution
Battery charger does not
start-up when the mains
is connected (LEDs on
battery charger are off).
Mains fuse is broken.
Check / replace fuse F1 (refer to
table
6.1
).
Load on battery charger outputs
is to high (>12 A).
Disconnect load on the main and
auxiliary outputs until load is
<12 A.
When the battery charger
is switched on it doesn’t
start charging. The
battery relay is not
switched on. Battery
status LED is yellow.
Voltage of the battery is not
between 14 V and 30 V for PLN-
24CH12 or 40 V and 60 V for
PRS-48CH12.
Check voltage on the battery
terminal. When the battery
voltage is not between the
specified values solve the
problem.
No back-up power when
battery charger mains is
connected (Battery status
and Output status LED is
yellow).
Probably fuse F8 is broken
because of a reversed battery
connection when battery relay
was already switched on.
Disconnect the battery and the
mains power from battery
charger. Check / replace fuse
F8, Main and Auxiliary fuses.
No backup power on one
or more outputs (main or
auxiliary status LED is
yellow).
On or more main or auxiliary
output fuses are broken.
Check the voltage of the main
and auxiliary outputs. The
measured voltage should be
equal to the battery terminal
voltage. Replace the regarding
fuse (refer to table
6.1
).
Mains status LED remains
yellow.
Refer to section
3.4.1
.
Battery status LED
remains yellow.
Refer to section
3.4.1
.
Battery is connected in reverse. Check battery polarity on
battery terminals. When
connected in reverse solve the
problem.
Output voltage status
LED remains yellow.
Refer to section
3.4.1
.
Indicator lights are not
illuminated while battery
charger is working
correctly.
Problem with flat cable inside
the battery charger.
Have qualified personnel check
the flat cable between the front
panel and the controller board.
Ensure that the battery charger
was handled with care and
without heavy bumps during
transport.