en | System Overview
Battery Charger
180110011Aa | V1.1 | 2011.05
Installation and Operation manual
Bosch Security Systems B.V.
3.4.2
Connections on the rear panel
Figure 3.2
Rear view of battery charger
A
Mains power socket
Socket for connecting the battery charger to the
mains power. The socket has a built-in strain relief.
B
Auxiliary output terminals
Three terminals for connecting auxiliary outputs (5
A max.) to power modules of the Voice Alarm
System that do not have mains power inputs. The
outputs are protected by a fuse (Faux1 to Faux3).
C
Temperature sensor socket
Socket to connect the temperature sensor (see
section
6.6
).
D
Main output terminals
Six output terminals to connect to the back-up
power terminals of VAS equipment (40 A max.).
The outputs are protected by a fuse (F1 to F6).
E
Output contacts
Fail-safe, dry contact, three-pole SPDT switch (C-
NC-NO), allowing 1A at 24 Vdc or 0,5 A at 120 Vac:
- Mains status (5 sec. of delay after mains fault)
- Battery status
- Output voltage status
F
Battery terminal
Terminal for connecting the battery leads (150 A
max.).
1
7
8
9
2
3
4
5
6
A
B
E
D
C
F