5
6
7
Monitor Range
ON
OFF
OFF
257 to 320
ON
OFF
ON
321 to 384
ON
ON
OFF
385 to 448
ON
ON
ON
449 to 512
Table 6.1: LTC 8916/01 Data Receiver Module Switch Positions (used in LTC 8902 Service Bays)
LTC 8918/01 Data Receiver Modules
The LTC 8918/01 Data Receiver modules (installed in LTC 8903 Series bays) contain three (3)
8-position dip switches.
For system configurations of up to 2048 cameras and 512 monitors, , page 66 can be used as
a guide for setting the Data Receiver DIP switches. Otherwise, follow the procedure described
below.
Verify that switches 1 to 3 and 5 to 8 on dipswitch S1 are OFF.
Switch 4 on S1 should be placed in the OFF position if the LTC 8903 Series bay will be used
as a primary camera bay (one that will have cameras directly connected to it). If the LTC 8903
Series bay will be used as a secondary camera bay (one that will have other LTC 8903 Series
bays connected to its inputs), place switch 4 on S1 in the ON position.
If switch 4 on S1 has been set to the OFF position (for use as a primary camera bay as
described above) set switches 1 to 4 on S2 according to the Primary Camera Bay Range in the
table below:
1
2
3
4
Camera Number Range
OFF
OFF
OFF
OFF
1 to 256
OFF
OFF
OFF
ON
257 to 512
OFF
OFF
ON
OFF
513 to 768
OFF
OFF
ON
ON
769 to 1024
OFF
ON
OFF
OFF
1025 to 1280
OFF
ON
OFF
ON
1281 to 1536
OFF
ON
ON
OFF
1537 to 1792
OFF
ON
ON
ON
1793 to 2048
ON
OFF
OFF
OFF
2049 to 2304
ON
OFF
OFF
ON
2305 to 2560
ON
OFF
ON
OFF
2561 to 2816
ON
OFF
ON
ON
2817 to 3072
ON
ON
OFF
OFF
3073 to 3328
ON
ON
OFF
ON
3329 to 3584
6.9
42
en | Hardware Installation Procedure for Redundant System Configuration Utilizing LTC
8901 Series CPU
LTC 8900 Series
2015.01 | 10.6 |
Installation Manual
Bosch Security Systems, Inc.