PI - 32.15a
Product Documentation of the LSN Radio Fire Detection System
Seite 24 von 32
601-F.01U.002.708
A3.en / 28.12.2004
ST-FIR/ PRM1 / deh
7.2. Expanding a radio cell (adding RF detectors)
This function combines additional RF smoke detectors in an
existing configured radio cell, e.g. to expand the detection range.
.
The LSN terminal block must not be connected to FK 100 LSN.
D
Disconnect the power supply to FK100 LSN, e.g. by removing the connection
terminal block.
D
Activate the reed switch in FK 100 LSN and se-
cure the magnet to the expander.
.
The reed switch must remain activated.
D
Connect the power supply for FK 100 LSN!
⇒
The red LED lights up briefly and the yellow LED
then begins to flash rapidly shortly afterwards.
D
Deactivate the reed switch in FK 100 LSN by re-
moving the magnets.
D
Within 10s, activate the reed switch on
FK 100 LSN (by moving the magnets along the
left - hand side of the housing) repeatedly until only
the green LED flashes rapidly.
⇒
After 10s, the red LED lights up briefly, indicating
that the new RF detectors can now be logged on.
Reed switch
LED yellow
LED red
Reed switch
LED yellow
LED red
Reed switch
LED red
LED green