PI - 32.15a
Product Documentation of the LSN Radio Fire Detection System
Seite 16 von 32
601-F.01U.002.708
A3.en / 28.12.2004
ST-FIR/ PRM1 / deh
6.
Initial Set - Up with Fire Panel and WinPara
D
Connect the LSN and supply voltage to RF expan-
sion module FK 100 LSN.
⇒
The red LED on FK 100 LSN lights up for a few sec-
onds, after which the yellow LED flashes slowly to
indicate that FK 100 LSN is in standby mode.
D
Programm the entire system including
FK 100 LSN on the programming PC using Win-
Para and load all RF detectors to be set in the fire
panel.
D
Activate the menu item “Reset FK100” in WinPara
under FK 100 LSN.
⇒
The red LED on FK 100 LSN lights up briefly, then
the green and yellow LEDs start to flash rapidly to
indicate a frequency search (max. 10 min.).
⇒
Following a successful frequency search, the yel-
low LED goes out to indicate that it is now possible
to log on to the RF detector.
Log RF detector on to RF expansion module:
D
Insert the batteries and secure the cables,
as shown in the diagram on the right.
⇒
The LED on the detector should flash slowly.
D
If the LED is flashing rapidly, press the new button
and hold it for at least 3 seconds.
⇒
The detector will be reset to its default settings and
the red LED will flash slowly.
D
Insert the detector in the base
within 10 minutes of
inserting the batteries
!
⇒
Following a successful system logon (duration:
15 sec. to a max. of 10 mins), the red LED will go
out and then flashes again for two minutes to indi-
cate the field strength.
Flashes/sec.
Field strength
Effect
4
High
Within field strength range adequate for
3
Moderate
Within field strength range adequate for
detector use!
2
Low
Impermissible field strength range!
1
Very low
Impermissible field strength range!
Improve detector positioning!
LED green
LED yellow
LED red
Button new
LED
red