PI - 32.15a
Product Documentation of the LSN Radio Fire Detection System
Seite 20 von 32
601-F.01U.002.708
A3.en / 28.12.2004
ST-FIR/ PRM1 / deh
6.5. Expanding a radio cell (adding RF detectors)
D
Call up the “Enter as” menu in WinPara under
“System”
⇒
“Peripheral control”
⇒
“LSN”
⇒
“FK100”
⇒
“LSN”.
D
Enter the number of new DOW1171s.
D
Load programming in the fire panel.
D
Activate expansion under “FK100” via
“DOW1171 to be added”.
⇒
The green LED on FK 100 LSN flashes rapidly, indicating that detectors can now
be added.
Log RF detector on to RF expansion module:
D
Insert the batteries and secure the cables,
as shown in the diagram on the right.
⇒
The LED must flash slowly.
D
If the LED flashes rapidly, press the new button and
hold it for at least 3 sec.
⇒
The detector will be reset to its default settings and
the red LED will flash slowly.
D
Insert the detector in the base
within 10 minutes of
inserting the batteries
!
⇒
Following a successful system logon (duration:
15 sec. to a max. of 10 mins), the red LED will go
out and then flashes again for two minutes to in-
dicate the field strength.
Flashes/sec.
Field strength
Effect
4
High
Within field strength range adequate for de-
3
Moderate
Within field strength range adequate for de
tector use!
2
Low
Impermissible field strength range!
1
Very low
Impermissible field strength range!
Improve detector positioning!
⇒
The yellow LED lights up briefly to acknowledge
each successful logon.
D
All other RF detectors (maximum of 30) are logged
on in this way one after the other.
⇒
Once the last DOW 1171 has been logged on,
FK 100 LSN starts system configuration and the
green LED flashes slowly.
⇒
Following successful system configuration, the green LED lights up permanently,
indicating that the radio cell is in standard mode.
Button new
LED
red
LED yellow
LED green