![Bosch LM024 Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/bosch/lm024/lm024_operating-instructions-manual_44205005.webp)
Location
|
5
LM CS Series Heat
8 733 920 847 (2014/01)
Revised 01-14
LOCATION
To maximize system performance, efficiency and
reliability, and to minimize installation costs, it is
always best to keep the refrigerant lines as short
as possible. Every effort should be made to locate
the air handler and the condensing section as
close as possible to each other.
Condensing Section
Locate the condensing section in an area that
provides sufficient room to make water and
electrical connections, and allows easy removal of
the access panels, for service personnel to
perform maintenance or repair.
The condensing section is designed for indoor use;
however, if the condensing section must be
installed in an outdoors location where ambient
temperatures can fall below freezing, some form of
freeze protection should be employed such as a
freeze-stat and/or a pump timer/starter to prevent
possible condenser freeze-up and to optimize
overall system performance.
Air Handler
Locate the air handler unit in an indoor area that
allows easy removal of the filter and access panels,
and has enough room for service personnel to
perform maintenance or repair. Provide sufficient
room to make electrical and duct connections. If
the unit is located in a confined space such as a
closet, provisions must be made for return air to
freely enter that space.
INSTALLATION
Condensing Section
The condensing section should be mounted on a
vibration absorption pad on a cement slab or
similar support to provide a good base and some
degree of levelness. The cement pad should not
come in contact with the foundation or side of the
dwelling, because sound may be transmitted into
the residence. See Figure #2 below.
Figure # 2
Reference the Factory Manual for your AH, or
Air Handler section of this manual for detailed
installation and operation.
Loosen compressor mounting bolts.
NOTE:
The installer should comply with all
local codes and regulations which govern
the installation of this type of equipment.
Local codes and regulations take precedent
over any recommendations contained in
these instructions. In lieu of local codes, the
equipment should be installed in
accordance with the recommendations
made by the National electric code, and in
accordance with the recommendations
made by the National Board of Fire
Underwriters.
DO NOT
remove the protective caps or plugs
from the service valves until the refrigerant
lines are run and ready for final connections.
Vibration Pad is
recommended