Troubleshooting
LM CS Series Heat Pump
LM CS Series Heat Pump
8 733 920 847 (2014/01)
Subject to change without prior notice
INSUFFICIENT
COOLING OR
HEATING
Unit undersized
Recalculate heating and or cooling loads. If excessive, possibly adding
insulation and shading will rectify the problem
Loss of
conditioned air by
leakage
Check for leaks in duct work or introduction of ambient air through
doors or windows
Airflow
Lack of adequate air flow or improper distribution of air. Replace dirty
filter
Refrigerant
charge
Low on refrigerant charge causing inefficient operation
Compressor
Check for defective compressor. If discharge is too low and suction
pressure is too high, compressor is not pumping properly. Replace
compressor.
Reversing Valve
Defective reversing valve creating bypass of refrigerant from discharge
of suction side of compressor. Replace reversing valve
Operating
pressures
Compare unit operation pressures to the pressure/temperature chart
for the unit.
TXV
Check TXV for possible restriction or defect. Replace if necessary.
Moisture,
noncondensables
The refrigerant system may be contaminated with moisture or
noncondensables. Reclaim refrigerant, replace filter dryer, evacuate the
refrigerant system, and recharge with factory recommended charge.
Unit Troubleshooting
Problem
Possible Cause
Checks and Correction
Compressor Ohms
Model
Start Winding
Run Winding
LM024
1.64
1.3
LM036
1.52
0.88
LM048
1.86
0.52
LM060
1.63
0.39
LM070
1.85
0.34
Tol/- 7%. All resistance values must be
measured with compressor at room temperature.
UPM Board LED Indications
Indication
Color
Blinks
Description
GREEN
Solid
18-30 VAC Power is present
RED
1
High pressure lockout
RED
2
Low pressure lockout
RED
3
Freeze sensor lockout
RED
4
Condensate overflow
RED
5
Brownout
RED
6
Evaporator Freeze condition