Vent specifications
Establish vent clearances that comply with the vent
manufacturer's specifications and all applicable
national/local codes.
Venting specifications
Condensate drain requirements
An external condensate drain (not supplied with the
heater) must be installed under the following
conditions:
• All vertical terminating vent installations.
• Horizontal terminating vent installations where the
total linear vent length is greater than 6 feet (1.8 m).
• Vent installations where any section of the exhaust
vent pipe passes through an unconditioned space.
Minimum combustion air and exhaust pipe
length
The minimum exhaust pipe length is 3 feet (1m) of
straight vent pipe. The minimum combustion air pipe
length is one 90° elbow.
Maximum combustion air and exhaust pipe
length
The following tables (Tables 5 & 6) display the
maximum allowable straight pipe lengths for
combustion air and exhaust piping with consideration to
the number of elbows used.
Step 1: If using the twin pipe penetration system, refer
to table 5. If using the concentric vent kit
system, refer to table 6.
Step 2: Total the number of 90° elbows and 45°
elbows used on the exhaust piping.
Step 3: Use this value in the appropriate table to
determine the maximum straight exhaust pipe
length allowed.
Step 4: Total the number of 90° elbows and 45°
elbows used on the combustion air piping.
Step 5: Use this value in the appropriate table to
determine the maximum straight combustion
air pipe length allowed.
*
Not allowed. At least one 90º elbow required.
**
Not allowed. Minimum of 3 feet (1m) of straight pipe required.
*
Not allowed. At least one 90º elbow required.
**
Not allowed. Minimum of 3 feet (1m) of straight pipe required.
Note:
Include pipe length that is part of the concentric terminal.
Diam.
Aproved terminals
E
x
h
a
u
s
t
3 or 4 inches
“T” terminal
90° elbow
Concentric
(196016)
I
n
t
a
k
e
3 or 4 inches
“T” terminal
90° elbow
Concentric
(196016)
Table 4 Venting specifications for intake and exhaust
i
Note:
90°
elbows
used
for
terminations should not be counted
in the exhaust and combustion air
piping.
Twin Pipe
System
# of 90° elbows
0
1
2
3
4
# of 45°
elbows
0
N/A*
26
21
16
11
1
N/A*
23
18
13
8
2
23
20
15
10
5
3
20
17
12
7
N/A**
4
17
14
9
4
N/A**
5
14
11
6
N/A**
N/A**
6
11
8
3
N/A**
N/A**
Maximum allowable straight pipe length (ft)
Table 5 Maximum allowable straight pipe length (twin
pipe)
Concentric
pipe System
# of 90° elbows
0
1
2
3
4
# of 45°
elbows
0
N/A*
18
13
8
3
1
N/A*
15
10
5
N/A**
2
15
12
7
N/A**
N/A**
3
12
9
4
N/A**
N/A**
4
9
6
N/A**
N/A**
N/A**
5
6
3
N/A**
N/A**
N/A**
6
3
N/A**
N/A**
N/A**
N/A**
Maximum allowable straight pipe length (ft)
Table 6 Maximum straight pipe length (concentric ter-
minal)