4.6 NTC
4.7
Regeneration / drainage valve
The utilised temperature safety switch (>85 °C) is combined with the
NTC sensor. If a fault occurs, the heater is switched off at a water
temperature of 85 °C (operates in switching mode).
Temperature in °C
Resistance in kW
Tol/– °C
25
48.4
7.9
30
38.5
7.1
50
16.5
6.2
60
11.0
5.6
65
9.1
5.5
The regeneration valve and the drainage valve are situated in the
water softening system.
If the regeneration valve is actuated, the
water stored in the regeneration chamber is conveyed through the
water softening system. If the drainage valve is actuated, the water
stored in the heat exchanger (HE) is conveyed into the rinsing tank via
the water softening system.
Technical specifications:
Nominal
voltage
230–240
V
Frequency
50
Hz
Resistance
2.45
k
Ω
A = Water softening system
B
= Regeneration
valve
C = HE drainage valve
202_58300000104305_ara_en_b – 02.11.a