Maintenance and service
Greentherm T9900 SE/i – 6 720 813 635 (2019/03)
56
▶ Touch the symbol
.
A green check mark is displayed indicating that reset is
complete.
6.9.3 Problem solving to activate Wi-Fi
Exceed Wi-Fi activation time
The Wi-Fi module must be activated within 15 minutes after
plug in the appliance to the power supply.
▶ Unplug the appliance from the power supply.
▶ Repeat Wi-Fi activation process, see section 6.9.1 "Wi-Fi
Wi-Fi module disconnected from HMI
If an error message is displayed or isn’t possible to configure
Wi-Fi menus:
▶ Unplug the appliance from the power supply.
▶ Remove the front cover, see fig. 3, page 12.
▶ Confirm that Wi-Fi module is correctly installed in the HMI.
Wi-Fi module is located on the back side of HMI.
Fig. 52
Wi-Fi module installed in HMI
[1]
Wi-Fi module
7
Maintenance and service
DANGER:
▶ Always shut off the electrical power supply, shut off the
manual gas valve and shut off the water valves whenever
servicing.
DANGER:
▶ Replace all dismantled seals and o-rings with new ones.
NOTICE:
▶ Inspect the complete water heating system once a year.
▶ Follow points 5 and 6 in Table 23 after 400 operation
hours or 25000 cycles (whichever occurs first), see
chapter 6.5.1(Data History).
▶ Inspect the water heater and components for wear or
fatigue. Immediately repair all faults to avoid damage to the
system.
Table 23 Annual maintenance
Annual maintenance table
Every year
1. Inspect venting system
X
2. Inspect heat exchanger
X
3. Inspect burner
X
1)
1) Proceed with burner cleaning if error code CE, CF and C2 is
displayed. Check the flue exhaust for blockage (appliance
is protected against flue blockage).
4. Inspect pressure relief
X
5. Inspect water filter
X
6. Heat Exchanger
Descaling
X
2)
2) Proceed with heat exchanger descaling whenever error
codes AA and E5 are displayed (appliance is protected
against over heating in case of scaling), see table 17 Water
Quality.
7. Inspect condensate trap
X