6 720 643 259 (2010/05)
Menu settings INSTALLER SETTINGS (for installers only)
|
35
US/CA
8.2 Configuring the heating system
Installer settings: System configuration
For menu structure and adjustment ranges
Æ
page 32.
Use this menu if you want to configure the system
automatically or manually. E.g. on commissioning
the system for the first time or making changes to
it.
B
Set ID of all BUS devices according to their
function (e.g. IPM2 for heating circuit 1 and
heating circuit 2, etc.).
B
Start automatic configuration.
B
Check the other menu options under
System
configuration
and, if necessary, adjust
manually to suit the present system.
8.3 Parameters for heating
Installer settings: Heating parameters
For menu structure and adjustment ranges
Æ
page 33.
Use this menu if you want to set the parameters
for the assigned heating circuit. For example, the
heating curves can be calculated with these
parameters.
Menu: Heating parameters > Heating circuit
type
B
Set the heating type of the assigned heating
circuit:
–
Baseline/Design temp
: Default settings for
a level heating curve are used according to
the classic base point/end point method.
–
Radiant Floor
: Default settings are used
for a sloped heating curve as in a radiant
floor heating circuit.
–
Radiators
: Default settings are used for a
sloped heating curve as in a radiator
heating circuit.
–
Baseboard
: Default settings are used for a
sloped heating curve as in a convector
heating circuit.
For system examples, see the
instructions for the IPM. Other
examples can be found in the
planning documents.
Set the supply temperature control
on the boiler to the maximum
required supply temperature.
Parameters not used in a particular
type of heating are not shown.