DS938Z  Installation  Guide

4.0 Mounting

Select a location likely to intercept an intruder moving 

across

 the

coverage pattern (review patterns on page 2). 

The recommended

ounting height is 8 to 18 ft. (2.4 to 5.5 m).

0

10

10

20

20

30  Feet

30

0

10

15

AR13-18 SIDE VIEW

(Cross Section of 2 Opposite Zones)

0

3

3

6

6

9  Meters

9

0

3

4.6

0

10

10

20

20

30  Feet

30

0

10

AR8-13 SIDE VIEW

(Cross Section of 2 Opposite Zones)

0

3

3

6

6

9 Meters

9

0

3

0

3

6

9 Meters

3

6

9

0

10

20

30

10

20

30

TOP VIEW

NOTE:

The mounting surface should be solid and vibration free (e.g.,
drop tiles should be secured if the area above the tiles is used
as an air return for HVAC systems).

• Do not mount near air handling system outlets, or in areas of

extreme drafts.

• Remove the cover by turning it counterclockwise.

• Remove the base from the enclosure by pressing the two

enclosure release tabs inward while lifting the enclosure away
from the base.

HINT:

Slightly rock the enclosure side-to-side during removal to
overcome the friction caused by the base-to-enclosure terminal
pins.

• Route wiring as necessary to the rear of the base and through

the center hole.

NOTE:

Be sure all wiring is unpowered (de-energized) before routing.

• Firmly mount the base. Depending on local regulations, the

base may be directly surface mounted using anchors, mollies,
or wing-nuts, or may be mounted to standard four inch
octagonal or square electrical boxes.

NOTE:

The DS938Z base will not completely cover a four inch

square box. Where aesthetics are important, a four inch
octagonal box is recommended.

HINT:

Mounting to removable ceiling tiles is not recommended unless a
sandwich is made of the base, ceiling tile, and a back plate behind
the tile. Covers used for four inch octagonal and square boxes
make a suitable back plate (when used with bolts and wing nuts,
as an example).

5.0 Selecting the Optical Module (AR8-13 or AR13-18)

• Replace the enclosure onto the base.

• For ceilings between 8 and 13 ft. (2.4 and 4.0 m) from the floor,

use the optical module marked AR8-13. This marking can be
found next to the two optical module tabs.

For ceilings between 13 and 18 ft. (4.0 and 5.5 m) high, use the
optical module marked AR13-18.

To replace an optical module, push the optical module tabs
towards the center until the module snaps free of the circuit
board. Holding the new module by the tabs, snap the new
module into place.

    Avoid fingerprints on the mirrored surfaces. Should the mirrored

surfaces become soiled or otherwise marked, they can be
cleaned using a soft, clean cloth and any commonly available,
mild window cleaner.

6.0 Wiring

CAUTION:

ONLY APPLY POWER AFTER ALL CONNECTIONS
HAVE BEEN MADE AND INSPECTED.

NOTE:

Do not coil excess wiring inside unit.

+

RELAY

1

2

3

4

5

6

7

8

6 to 15

VDC

Alarm

INTERFACE

PINS

KEY GUIDE

TAMPER

Terminals 1 (-) & 2 (+):

  Power limits are 6 to 15 VDC. Use no

smaller than #22 AWG (0.8 mm) wire pair between the unit and
the power source.

Terminals 3, 4, & 5:

  Alarm relay contacts rated 125 mA, 28 VDC

maximum for DC resistive loads. Use terminals 4 & 5 for
Normally Closed circuits. 

Do not use with capacitive or inductive

loads.

Terminals 6 & 7:

  Normally Closed tamper contacts rated at

28 VDC, 125 mA.

Terminal 8:

  Trouble Output.

7.0 Configuration Switch Settings

The DS938Z has several features that are controlled using the
configuration switches.

1 ON   

=  LED ON

1 OFF

 =  LED OFF

2 ON

 

and 3 OFF 

=  High

2 OFF and 3 ON

 =  Intermediate

2 ON and 3 ON

   =  Standard

4 ON and 5 OFF

   =  4 Day Motion Monitor

4 OFF and 5 ON

   =  30 Day Motion Monitor

4 OFF and 5 OFF

 =  Motion Monitor Disabled

ON

OFF

O
N

1

2

3

4

5

7.1 LED Operation (S1)

ON:

Allows the Alarm/Test LED to operate when activated by
motion.

OFF:

The LED will not operate on alarm activation, but will
indicate a supervision trouble condition.

INTERFACE

PINS

ANTI-VANDAL

TIE-DOWN SCREW

HOLE (2)

ENCLOSURE RELEASE

OPENINGS (2)

Base

COVER TWIST

TABS (4)

Cover

INTERFACE

CONNECTOR

ENCLOSURE

RELEASE TABS

OPTICAL
MODULE

TEST LEAD CUTOUT

Enclosure

Содержание DS938Z

Страница 1: ... looking straight down from the unit sabotage Each barrier is 30 ft 9 2 m long and 4 4 ft 1 3 m wide at 30 ft 9 2 m Choice of two optical modules depending on ceiling height NOTE For UL Certificated installations the coverage is 360 by 54 ft 16 5 m when mounted from 10 to 13 ft 3 1 to 4 0 m using the AR8 13 Array and when mounted from 15 to 18 ft 4 6 to 5 5 m using the AR13 18 Array Input Power 6 ...

Страница 2: ... the Optical Module AR8 13 or AR13 18 Replace the enclosure onto the base For ceilings between 8 and 13 ft 2 4 and 4 0 m from the floor use the optical module marked AR8 13 This marking can be found next to the two optical module tabs For ceilings between 13 and 18 ft 4 0 and 5 5 m high use the optical module marked AR13 18 To replace an optical module push the optical module tabs towards the cent...

Страница 3: ...espect to either outside pin outside pins are common Place the cover on the unit and twist lock it clockwise into place NOTE Be sure the TC6000 and Sonalert leads are dressed through the cutout Apply power to the unit Wait at least two minutes after applying power to start walk tests NOTE Walk testing should be done across the coverage pattern as shown The edge of the coverage pattern is determine...

Страница 4: ...ovided with the unit for each segment of the optical module to allow for customized coverage or to block out areas of objects that may cause thermal disturbances The mask is self adhesive and pre cut in the shape of the optical module To block out a particular zone or group of zones peel off a section of the mask that corresponds to the appropriate zone and stick it on the mirror segment Use Secti...

Отзывы: