DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01     Page 53

10.27 Report Programming: Program Addresses (3207-3419)

•  To send the User number along with open, close, or partial close reports:  place an ‘F’ (*5) in the extended digit.
•  To disable a report (meaning that nothing will be sent), place a ‘0’ in the reporting digit.
•  When using SIA or Contact ID format, place a ‘1’ in the reporting digit of each report you wish to enable. It is not necessary to program

the extended digit.

• For suggested values for 4/2, BFSK and Pager format, see section 12.1-12.3. For SIA and Contact ID, the values sent are listed in

sections 13.1 and 13.2. For other formats, consult your central station.

•  HEX values:  Some Data Digit values are higher than 9. These values are programmed by pressing the [*] key followed by another

number. These values will display as HEX characters when entered. The HEX character values are as follows:

*0 = A

*1 = B

*2 = C

*3 = D

*4 = E

*5 = F

See Glossary (section 6.13) for further details.

Содержание DS7400Xi

Страница 1: ...alk Test PIN 8 1 Read Event History PIN 8 9 Battery Test PIN System Reset Communicator Test PIN 8 2 Fire Reset PIN System Reset Remote Program Dial out PIN 8 3 Remote Program Answer PIN 8 6 Battery Sounder Test PIN 8 5 Error Display PIN 8 7 Error Display Reset PIN System Reset Fire Walk Test PIN 9 1 To Silence a Fire Trouble Alarm PIN Off To Clear a Fire Trouble Display PIN System Reset Access Con...

Страница 2: ...ncy Keypad Alarms 26 7 4 Fire Safety 27 7 4 1 If Installed in Family Residences 27 7 4 2 Having and Practicing an Escape Plan 27 7 4 3 Installation Considerations 27 7 5 Personal Identification Numbers 28 7 5 1 General Information 28 7 5 2 ProgrammingPINs 28 7 6 The Master Keypad 29 7 6 1 General Information 29 7 6 2 Master Keypad Displays 29 7 6 3 SinglePartitionMode 29 7 6 4 Arming from the Mast...

Страница 3: ... 36 5 Octal Relay Module Output Partition Assignment Program Addresses 2844 2851 65 10 37 Output Function Programming Program Addresses 2772 2843 66 10 37 1 Output Function Partition Assignment Program Addresses 2852 2863 67 10 38 Dual Phone Line Bell Supervision Module Output Programming Program Address 4021 67 10 39 Call Out Timer Programming Program Addresses 4022 4025 68 10 40 Test Report and ...

Страница 4: ...0 mm quad wiring can be home run or daisy chained NOTE No more than 2 keypads 22 AWG or 3 keypads 18 AWG are recommended on any 1000 foot 305 m run NOTE Shared cable is not recommended for keypad multiplex options bus telephone or siren wiring 1 7 Communicator Will report to two phone numbers with full single double and back up reporting Communicates in SIA 110 or 300 baud 3 1 3 1 Ext 3 1 with Par...

Страница 5: ...1 175 mA 175 mA 250 mA 250 mA DS7416i Advanced Radio Communications Module 127 mA 127 mA DS7412 RS232 Serial Interface Module 35 mA max 35 mA max DS7420i Dual Phone Line Bell Supervision Module 20 mA 140 mA DS7430 Multiplex Expansion Module 65 mA 65 mA DS7432 8 Input Remote Module 10 mA 10 mA DS7433 8 Input Direct Module 65 mA 80 mA DS7436 Dual Multiplex Expansion Module 130 mA 130 mA DS7445 DS744...

Страница 6: ...ious control panel functions A built in sounder is used as an interior warning device and to annunciate keystroke entries Current Draw 75 mA Standby 75 mA Alarm DS7447 DS7447E Control Station 15 Keypads max per system The DS7447 DS7447E is an Alpha Numeric LCD keypad It displays information on various control panel functions A built in sounder is used as an interior warning device and to annunciat...

Страница 7: ...ent draw for all 8 outputs combined cannot exceed 750 mA DS9484 The DS9484 is a Remote Notification Appliance Circuit NAC Power Supply designed to add four additional NACs NFPA 72 Class B Style Y to a Fire Alarm Control Panel FACP When connected to the Options Bus of the DS7400Xi it can provide intelligent control of its individual outputs It supplies 6 A of NAC power through four circuits to driv...

Страница 8: ...o connect its ground wire to the top hinge of the enclosure the unpainted tab MX794 The MX794 is a Long Range Multiplex PIR intrusion DS7474 Detector with Self test The standard ranges are 80 ft by 50 ft 24 0 m by 15 0 m and 200 ft by 10 ft 61 0 m by 3 1 m Requires a DS7430 and occupies one multiplex zone Current Draw 800 μA Standby 2 mA Alarm MX934 Multiplex Passive Infrared PIR intrusion detecto...

Страница 9: ...aintained between the battery terminals battery wiring and all other wiring Battery wiring may not share the same conduit conduit fittings or conduit knock outs with other wiring in 6 4 mm Minimum Option or Keypad Wires Output or Zone Wires Battery Wires Only required if external batteries are used To ensure proper spacing secure wires using Tie Wraps or similar devices Wiring ...

Страница 10: ...re intended for connection of Normally Open or Normally Closed alarm contacts They may also be used for compatible 2 wire smoke detectors These zones require a 2 21kΩ resistor P N 25899 at the end of the loop Power is momentarily removed from L after a PIN System Reset or during a fire verification Zone 1 8 assignments are programmed in address 0031 0038 17 18 19 20 21 22 23 24 25 26 27 28 29 30 P...

Страница 11: ... keypad must be designated as keypad 1 and connected to the Keypad Bus See the DS7447 DS7447E DS7445 DS7445i and DS7448 Installation Instructions for further details A DS7420i Dual Phone Line Bell Supervision Module may be connected to the Control Panel and placed within the enclosure Connect to the Options Bus of the control panel See the DS7420i Installation Instructions for further details A DS...

Страница 12: ...________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ____________________________________________________________________________________ ___________________________________________________...

Страница 13: ...015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 PIN Information User Pin Auth Parti Name Level tions PIN Information User Pin Auth Parti Name Level tions PIN Information User Pin Auth Parti Name Level tions 031 032 033 071 072 073 074 075 076 077 078 079 080 081 082 083 084 085 086 087 088 089 090 091 092 093 094 095 096 097 098 099 067 068 069 070 036 037 038 039 040 041 042 043 0...

Страница 14: ... 127 128 129 PIN Information User Pin Auth Parti Name Level tions PIN Information User Pin Auth Parti Name Level tions PIN Information User Pin Auth Parti Name Level tions 130 131 132 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 168 169 170 171 136 137 138 139 140 156 157 158 159 160 161 162 163 164 165 166 134 135 133 167 110 ...

Страница 15: ...tput Partition Location Function Zone 31 Zone 32 Zone 33 Zone 34 Zone 35 Zone 36 Zone 37 Zone 38 Zone 39 Zone 40 2 Kitchen SZ SZ Single Zone Input MZ Multiple Zone Input IO DS7465 see section 10 3 Zone 41 Zone 42 Zone 43 Zone 44 Zone 45 Zone 46 Zone 47 Zone 48 Zone 49 Zone 50 Zone 51 Zone 52 Zone 53 Zone 54 Zone 55 Zone 56 Zone 57 Zone 58 Zone 59 Zone 60 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zon...

Страница 16: ...Page 16 P N F01U035325 01 Copyright 2007 Bosch Security Systems Inc DS7400Xi 4 Reference Guide 5 0 System Worksheet continued ...

Страница 17: ...DS7400Xi 4 Reference Guide Copyright 2007 Bosch Security Systems Inc P N F01U035325 01 Page 17 5 0 System Worksheet continued ...

Страница 18: ...Page 18 P N F01U035325 01 Copyright 2007 Bosch Security Systems Inc DS7400Xi 4 Reference Guide 5 0 System Worksheet continued Zone Location and Notes Worksheet ...

Страница 19: ...tallations 6 2 Zone Function Programming Zone Function A Zone Function is the description of how a particular zone will behave e g steady alarm output bypassing allowed alarm on short trouble on open perimeter instant There are many possible zone functions Up to 30 different zone functions are allowed per control Zone functions may be custom made as needed Each zone must be programmed as a specifi...

Страница 20: ...one on all keypads in every partition A fire reset command must be entered after silencing the alarm to re enable this zone If this zone is programmed for trouble and the loop opens the DS7447 DS7447E keypad will display Fire Trouble for this zone and the keypad sounders will beep once every ten seconds If the system is a combination fire and burglar alarm the fire alarm has priority over the burg...

Страница 21: ...s an output programmed to wait 20 seconds after a zone enters an alarm condition to activate It will remain activated until the system is disarmed or the bell cut off time expires This output is intended to activate alarm bells and sirens but provides a delay to allow the user to silence the system before it activates Output Functions Output Functions can be programmed to follow system events or t...

Страница 22: ...he Fire Key will generate the fire alarm sounders in the partition that activated the Fire Key Any other partitions in use will only have their keypad sounders activated All keypad displays will be the same Special Emergency Key The emergency key key B at the bottom center of the keypad entry area is the Special Emergency Key If programmed the key will activate a supplementary or an auxiliary type...

Страница 23: ...eypad Panic This report is sent when an emergency alarm has been activated using the C emergency key Keypad Tamper For keypads fitted with a wall tamper switch this report is sent when the keypad is removed from the wall Keypad Tamper Restoral For keypads fitted with a wall tamper switch this report is sent when the keypad is properly replaced on the wall after experiencing a tamper condition Zone...

Страница 24: ...t disarmed before the entry delay expires an alarm report for the effected zone will be sent and the Exit Error report will be sent If this report is not programmed the control will not sound the exit error warning Recent Closing This report is sent along with any alarm reports when there is an alarm within the first five minutes after the system has been armed System Walk Test This report is sent...

Страница 25: ...e network until the problem has been corrected or until you are sure that the equipment is not malfunctioning The repairs to this equipment must be made by the manufacturer and not the user To guard against accidental disconnection there is ample room to mount the Telco jack to the inside of the Control cabinet The operation of this Control may also be affected if events such as accidents or acts ...

Страница 26: ...ed so the monitoring company may verify its operation NOTE To use the System Reset command sequence your PIN must have disarm privileges The System Reset com mand will perform a fire reset a battery test and will clear all system troubles NOTE If the System Reset command has not been performed after 24 hours of the Fire Alarm the keypad will sound and it will display Fire Alarm Not Reset If the so...

Страница 27: ...mediately go to the pre selected location to be accounted for Provide a barricade between family members and fire smoke and toxic gases e g close all bedroom doors before retiring Children should be instructed on opening their bedroom windows and exiting safely from the building If exiting is not possible they should be taught to stay at the open window and shout for help until it arrives In the e...

Страница 28: ...ed to more than one partition you must enter a Temporary PIN expiration date for all assigned partitions see Changing the Expiration Date for Temporary PINs 5 Duress When the system is disarmed using the duress code a silent report is sent to your monitoring service The Duress code is intended to be used when the user is forced to disarm the system 6 Access Code When a PIN with an Access Code is e...

Страница 29: ...followed by the key twice 1 2 3 4 The first partition you have access to will be displayed Ready to Arm Cafeteria Complete the command sequence in this case arming you wish for this partition On Move to the next partition you have access to by pressing the key twice The next partition you have access to will be displayed Ready to Arm Office Complete the command sequence you wish for this partition...

Страница 30: ... other Error Displays are limited to the partition the standard keypad is in If you are on a Master keypad you may read Error Displays one partition at a time 7 7 2 System Faults System faults are designated as follows 8 7 will display 8 9 will display RAM Fault System Fault 01 ROM Fault System Fault 02 EEPROM Fault System Fault 03 Ground Fault System Fault 04 2Ph Bell Fault loss of communication ...

Страница 31: ...r Test This test is available only if the system transmits alarms and system information to a monitoring service and has been programmed by the security installing company to permit communicator tests This test can be performed from a Master Keypad The account code for partition 1 will be used System Tests are not available from RF wireless keypads To initiate a Communicator Test Press PIN 8 2 A l...

Страница 32: ... different address press the key two times and enter the program address you wish to program If you make a mistake at any time press the key two times before pressing the key This will clear the display allowing you to enter the program address you wish to work with 8 4 HEX values Some Data Digit values will be higher than 9 These values must be programmed by pressing the key followed by some othe...

Страница 33: ...he dots represent which options features are included with each selection Example To select Feature 2 only enter the data digit as a 1 To select Feature 2 and Feature 4 enter the data digit as a 5 If the chart looks like this only a single feature is available to be programmed for that particular address Disabled Perimeter Instant 24 Hour Entry Exit Delay 1 Entry Exit Delay 2 1 2 3 4 0 Enter one o...

Страница 34: ...hunts Send Bypass Reports Select Options 5 Enter DD as a 6 7 8 Allow Swinger Shunts No Bypass Reports Normal Arming PIN On If programmed Normal Arming arms the entire system while allowing entry delays for entry exit zones Perimeter Instant Arming PIN No Entry Perimeter Only If programmed Perimeter Instant Arming arms only the perimeter of the system and does not allow entry delays for entry exit ...

Страница 35: ...ut alarm on short and open 6 Interior home away 2 Steady alarm output alarm on short and open 7 Interior Instant 2 Steady alarm output alarm on short and open 2 24 hour 7 Pulsing alarm output alarm on short trouble on open 0 Fire zone with verification 0001 0002 0003 0004 0005 0006 0007 0008 0009 0010 0011 0012 0013 0014 0015 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 Steady alarm output alarm on short...

Страница 36: ...vice that will follow the output functions its input loop will follow a zone function All single and multiple zone inputs will follow a zone function See section 6 3 for further details Data Digit 1 2 1 2 3 4 5 6 7 8 0031 0032 0033 0034 0035 0036 0037 0038 0039 0278 01 02 03 04 05 06 07 08 00 Zone Number Address Zone Function Default Hint Address Zone Number 30 Options Disable a zone Enter a Zone ...

Страница 37: ...37 38 Zones 39 40 Zones 41 42 Zones 43 44 Zones 45 46 Zones 47 48 Zones 49 50 Zones 51 52 Zones 53 54 Zones 55 56 Zones 57 58 Zones 59 60 Zones 61 62 Zones 63 64 0415 0416 0417 0418 0419 0420 0421 0422 0423 0424 0425 0426 0427 0428 0429 0430 0431 0432 0433 0434 0435 0436 0437 0438 0439 0440 0441 0442 0443 0444 0445 0446 Zones 65 66 Zones 67 68 Zones 69 70 Zones 71 72 Zones 73 74 Zones 75 76 Zones ...

Страница 38: ...8 Zones 119 120 Zones 121 122 Zones 123 124 Zones 125 126 Zones 127 128 0319 0320 0321 0322 0323 0324 0325 0326 0327 0328 0329 0330 0331 0332 0333 0334 0335 0336 0337 0338 0339 0340 0341 0342 0343 0344 0345 0346 0347 0348 0349 0350 Zones 129 130 Zones 131 132 Zones 133 134 Zones 135 136 Zones 137 138 Zones 139 140 Zones 141 142 Zones 143 144 Zones 145 146 Zones 147 148 Zones 149 150 Zones 151 152 ...

Страница 39: ... Zone Function 5 Can Be Bypassed Select Options Enter the Data Digit as a 0 5 are Hex values They will display as A F at the keypads Zone Function 8 Can Be Bypassed Zone Function 7 Can Be Bypassed Zone Function 6 Can Be Bypassed 8 0 5 are Hex values They will display as A F at the keypads 1 2 Data Digit PA 2722 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 Zone Function 9 Can Be Bypassed Select Options Enter the ...

Страница 40: ...2 3 4 5 Zone Function 29 Can Be Bypassed Select Options Enter the Data Digit as a Zone Function 30 Can Be Bypassed 0 1 2 Data Digit PA 2723 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 Zone Function 17 Can Be Bypassed Select Options Enter the Data Digit as a 0 5 are Hex values They will display as A F at the keypads Zone Function 20 Can Be Bypassed Zone Function 19 Can Be Bypassed Zone Function 18 Can Be Bypasse...

Страница 41: ... Alarm delayed by 20 sec Keypad Sounder Output Access Output 10 sec pulse 1 2 3 4 5 6 7 8 9 1 2 DD Data Digit This includes invisible zones See glossary for further details See section 6 4 for description of this option Select Option Keyfob 1 Alarm Programmable Output 1 Programmable Output 2 2734 2736 6 3 2 3 Output Address Default 3 3 2735 On during battery test 3 0 Panic Duress Output Programmab...

Страница 42: ...mber of partitions in use and the common area common area can only be partition 1 See Glossary section 6 5 for further details Data Digit 1 2 1 2 3 4 5 6 7 0 Belongs to Partition 1 Belongs to Partition 2 Belongs to Partition 3 Belongs to Partition 4 Belongs to Partition 5 Belongs to Partition 6 Belongs to Partition 7 Belongs to Partition 8 Select Option DD 8 Follows all Partitions 1 2 Data Digit A...

Страница 43: ...ht 2007 Bosch Security Systems Inc P N F01U035325 01 Page 43 10 10 Quick Arm Control Programming Program Address 3477 Quick Arm Control programming defines which partitions can be quick armed armed without requiring a PIN to be entered ...

Страница 44: ...ion Bus at keypad address 11 15 the corresponding keypad s is are unavailable If only using one partition do not program keypads as Master Keypads Only program for a Master Keypad if you need to view multiple partitions from a single keypad 10 12 Keypad Partition Assignment Program Addresses 3139 3146 Data Digit 1 Data Digit 2 Keypad 1 default 1 Program Address 3131 Data Digit 1 Data Digit 2 Progr...

Страница 45: ... Pulsed Alarm 3 Select Option DD Fire Key A May be forced to a different value when in Commercial Fire Mode See section 10 16 3 1 2 0 Special Emergency Key Disabled Special Emergency Key Silent Alarm Special Emergency Key Steady Alarm 1 2 Special Emergency Key Pulsed Alarm 3 Select Option DD Emergency Key B 0 Panic Key Disabled Panic Key Silent Alarm Panic Key Steady Alarm 1 2 Panic Key Pulsed Ala...

Страница 46: ...Continued 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 Bypass Zone Function 25 Bypass Zone Function 26 Bypass Zone Function 27 Bypass Zone Function 28 Select Options Enter the Data Digit as a 0 5 are Hex values They will display as A F at the keypads 1 2 Data Digit PA 2728 Enter the Data Digit as a 0 1 2 3 Bypass Zone Function 29 Bypass Zone Function 30 Select Options ...

Страница 47: ... Force Armed using an Arming sequence followed by the Bypass key With this entry all violated zones up the programmed limit will automatically be Force Armed bypassed Ground Fault Detect programming determines whether or not the control will detect a ground fault condition See Glossary sections 6 9 and 6 10 for further details Note This limit does not apply when arming with a keyswitch programmed ...

Страница 48: ...ort Trouble on Open Pulsing Fire with verification Zone Function 13 address 0013 will be a 7 1 Alarm on Short Trouble on Open Pulsing Fire without verification Zone Function 14 address 0014 will be a 7 2 Alarm on Short Trouble on Open Pulsing Water Flow Zone Function 15 address 0015 will be a 7 3 Alarm on Short Trouble on Open Pulsing Supervisory Zone Bypass address 2722 will not allow zone functi...

Страница 49: ...tition 6 Report opens and closes in Partition 7 Report opens and closes in Partition 8 exit delay Data Digit 1 2 When using this option all partitions should have the same account code Data Digit 1 2 0 10 18 Open Close Zone Report Control Programming Program Address 3151 This section allows you to decide which phone number will send open and close reports zone alarm zone restoral and zone trouble ...

Страница 50: ...Default 04 minutes 1 minute intervals 99 30 second cutoff 0 to 51 0 to 255 sec Default 09 45 sec Data Digit 1 2 Address 4028 Entry Delay Time 1 Data Digit 1 2 Address 4029 Entry Delay Time 2 Data Digit 1 2 Address 4030 Exit Delay Time Data Digit 1 2 Address 4032 Fire Bell Cutoff Data Digit 1 2 Address 4033 Burglary Bell Cutoff May be forced to a different value when in Commercial Fire Mode See sec...

Страница 51: ...exit delay At 10 seconds and 5 seconds remaining the keypad sounder will activate 3 times During auto arming a pre arming period will begin 15 minutes before the system arms automatically The keypad sounders will pulse five times every minute During the last five minutes before arming these sounders will be on steady 0 1 General Code can Arm Disarm and Bypass Select Option DD General Code can Arm ...

Страница 52: ...iguration Programming allows you to configure the DS7412 for your printer Most printers will operate using the default values for the DS7412 Some printers may operate more efficiently using optional program values DS7412 RS232 Interface Control Programming allows you to enable or disable the DS7412 and to select which history events are sent to the printer as they occur Selecting No Events will ca...

Страница 53: ...he reporting digit of each report you wish to enable It is not necessary to program the extended digit For suggested values for 4 2 BFSK and Pager format see section 12 1 12 3 For SIA and Contact ID the values sent are listed in sections 13 1 and 13 2 For other formats consult your central station HEX values Some Data Digit values are higher than 9 These values are programmed by pressing the key f...

Страница 54: ...Page 54 P N F01U035325 01 Copyright 2007 Bosch Security Systems Inc DS7400Xi 4 Reference Guide Report Programming Continued ...

Страница 55: ...Phone Use DS7416i and Try Phone First options are all selected If the value is less than or equal to 2 or more than 5 two attempts will be made on the phone before trying the DS7416i if the Phone First option is selected Use Phone Use Either Try Phone First Use Both 1 2 7 1 5 Select Options Enter the DD as a 3 Data Digit 1 2 DD 0 Attempts 1 Attempt 2 Attempts 3 Attempts 1 2 3 4 Attempts 5 Attempts...

Страница 56: ... reporting from this panel 1 Account Codes are programmed from left to right If programming a 3 digit Account Code the fourth digit of the address must be 0 For example If the Account Code is 121 program 1210 in the programming address 2 If you wish to send a zero 0 enter it as 0 this does not apply to the added zero in a three digit Account Code For example If the Account Code is 101 program 1 01...

Страница 57: ...rogram address 3156 as data digit 1 9 data digit 2 1 Program address 3157 as data digit 1 9 data digit 2 1 4 Dial tone on all phone numbers Enter the Data Digit as a Select Options 2 1 0 3 5 6 7 8 Enable remote programmer call back Dial pulse on all phone numbers Dial tone switch to pulse if required Try DS7416i first 9 0 1 0 1 are Hex values They will display as A B at the keypads ΔΔ If this opti...

Страница 58: ...m Communicator Receivers and Formats that are compatible with the DS7400Xi NOTE Contact your central station regarding which format to use and if a special line card is required l The Format type the DS7400Xi supports and the Digital Alarm Communicator Receiver accepts 10 32 Phone Answering Programming Program Address 3158 See Glossary section 6 15 for further details ...

Страница 59: ...r Code authority level Master Code for User Number 001 has its authority fixed at level 0 It will always have access to all partitions 10 35 PIN Length Programming Program Address 3478 PIN Length Programming defines the length of the PINs that are assigned to each user PINS can be programmed to be 4 or 6 digits in length Programmer s Code Enter as 6 digits It can not be the same as any PIN number ...

Страница 60: ...s are used one replaces Octal Relay Module 1 and the other replaces Octal Relay Module 2 For Octal Relay Partition Assignment see section 10 36 5 0 1 2 SELECT OPTION DD 2 3 Follows Disabled Burglar Alarm Fire Alarm Octal Relay DS7488 1 Address A DS7488 1 Address B 1 2 3 4 5 6 7 8 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 2750 2751 2752 2753 2754 2755 2756 2757 9 10 11 12 13 14 2758 2759 27...

Страница 61: ...Relay DS7488 1 Address A DS7488 1 Address B 1 2 3 4 5 6 7 8 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 2750 2751 2752 2753 2754 2755 2756 2757 9 10 11 12 13 14 2758 2759 2760 2761 2762 2763 2764 2765 2766 2767 2768 2769 2770 2771 15 16 1 2 Data Digit Program Address B 1 2 Data Digit 2 Program Address A DD 0 0 Disabled AC Power Fail Low Battery Communicator Failure System Fault Keypad Superv...

Страница 62: ...ollow Output Function follow the steps below 1 Select Octal Relay to program 2 Program Data Digit 1 of Program Address A as 3 for Follow Function 3 Program Data Digit 2 of Program Address A for the desired function 4 Program Data Digit 1 and 2 of Program Address B for the desired function Once both Address A and Address B have been programmed proceed to program the next Octal Relay For Octal Relay...

Страница 63: ...ss A and Address B have been programmed proceed to program the next Octal Relay Octal Relay DS7488 1 Address A DS7488 1 Address B 1 2 3 4 5 6 7 8 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 2750 2751 2752 2753 2754 2755 2756 2757 9 10 11 12 13 14 2758 2759 2760 2761 2762 2763 2764 2765 2766 2767 2768 2769 2770 2771 15 16 1 2 Data Digit Program Address B 1 2 Data Digit 4 Program Address A 1 0...

Страница 64: ...Page 64 P N F01U035325 01 Copyright 2007 Bosch Security Systems Inc DS7400Xi 4 Reference Guide ...

Страница 65: ... Digit 1 Data Digit 2 Program Address 2847 Data Digit 1 Data Digit 2 Program Address 2850 Data Digit 1 Data Digit 2 Program Address 2851 1 2 3 4 5 6 7 0 Belongs to Partition 1 Belongs to Partition 2 Belongs to Partition 3 Belongs to Partition 4 Belongs to Partition 5 Belongs to Partition 6 Belongs to Partition 7 Belongs to Partition 8 Select Option DD Follows all Partitions Relay 1 default 8 Relay...

Страница 66: ...1 2 Program Address 1 Enter the Zone Number of Second Zone to Follow see Zone HEX Values chart Program Address 1 Program Address 2 Program Address 3 2 Data Digit Data Digit 1 2 Data Digit 1 2 Data Digit 1 2 1 Not Required if following a single zone Enter the Zone Number of First Zone to Follow see Zone HEX Values chart Zone Trouble Supervisory Select Option DD DD Select Option 1 Communication Fail...

Страница 67: ...rogram Addresses 2852 2863 10 38 Dual Phone Line Bell Supervision Module Output Programming Program Address 4021 The Dual Phone Line Bell Supervision Module is the DS7420i See section 1 18 for further details When in Central Station or Local Commercial Fire Mode this address will be forced to specific values see sections 10 16 1 and 10 16 2 ...

Страница 68: ...ll Out The default time for the Communicator Test Report to be sent and for the control to call the Remote Programmer is Midnight 10 40 Test Report and Remote Programmer Call Out Programming Program Address 4026 This section allows you to define the Day and Frequency for the Communicator Test Report and the Remote Programmer Call Out If this address is not programmed the Communicator Test Report w...

Страница 69: ...s es blank Once programmed the descriptions will be displayed on the alpha keypads The following chart lists the Program Addresses used to program Alpha Numeric characters for each partition or zone See Section 10 41 1 for an Alpha Description Programming worksheet for Partitions 1 through 8 and Zones 1 through 8 See the Programming Addresses Worksheet P N 43850 for a complete Alpha Programming Wo...

Страница 70: ...Page 70 P N F01U035325 01 Copyright 2007 Bosch Security Systems Inc DS7400Xi 4 Reference Guide 10 41 1 Alpha Description Programming A Worksheet ...

Страница 71: ...DS7400Xi 4 Reference Guide Copyright 2007 Bosch Security Systems Inc P N F01U035325 01 Page 71 10 41 1 Alpha Description Programming A Worksheet Continued ...

Страница 72: ...Page 72 P N F01U035325 01 Copyright 2007 Bosch Security Systems Inc DS7400Xi 4 Reference Guide 10 41 1 Alpha Description Programming A Worksheet Continued ...

Страница 73: ...DS7400Xi 4 Reference Guide Copyright 2007 Bosch Security Systems Inc P N F01U035325 01 Page 73 10 41 1 Alpha Description Programming A Worksheet Continued ...

Страница 74: ...a Phone Number enter 5 in the first digit 1 5 are Hex values They will display as B F at the keypads Recommendation The phone line that the control panel is connected to should not have a Call Waiting feature If it must have call waiting program the code to disable call waiting and add a three second delay before the phone number This will prevent incoming calls from interrupting a communication F...

Страница 75: ... Enclosure Attack Enclosure AE TR16 Enclosure DS7416i AB12 Bell w Housing R 1 1 R n a R 0 0 0 2 0 n a 0 n a n a R 1 1 n a n a n a 0 0 0 3 0 n a 0 n a R R n a R n a R 4 0 0 0 3 0 4 0 R n a R n a R n a n a n a 0 0 0 3 0 n a 0 R n a R n a R n a n a n a 0 0 0 3 0 n a 0 R n a R n a R n a n a n a 0 0 0 3 0 n a 0 R n a R n a R n a R 4 0 0 0 3 0 4 0 R n a R 1 1 R R 4 0 0 0 2 0 4 0 n a n a R n a R n a n a ...

Страница 76: ... devices A compatible Listed 4 wire detector is the Detection Systems Inc DS250 in an MB4W base A compatible Listed EOL relay is the Detection Systems Inc EOL200 All zones must be used with the EOL resistor P N 25899 provided 1 Report Programming Fire Zone Report must be programmed Low Battery Report Program Address 3336 must be programmed AC Failure Report Program Address 3338 must be programmed ...

Страница 77: ...11 4 Required Accessories The control must be in the Detection System s model AE3CC enclosure with a cover actuated tamper switch installed The Ademco Model AB 12 bell housing see section 11 6 1 Timer Programming Bell Cutoff Times Program Addresses 4032 and 4033 must be programmed for not less than 15 minutes Entry Exit Delay Times Program Addresses 4028 4030 must be programmed for not longer than...

Страница 78: ...ance with NFPA 72 Required Accessories DS7420i Dual Phone Line Bell Supervision Module For Local Commercial Fire Alarm A Listed notification appliance such as a Wheelock 46T G10 12 bell or 34T 12 horn If not using the phone line supervision it must be disabled AE TR16 Transformer Housing At least one DS7447 DS7447E must be used and assigned as keypad 1 If only one is used it may be connected to th...

Страница 79: ...3279 3280 3281 3282 3283 3284 3285 3286 3287 3288 3289 3290 3291 3292 3293 3294 3295 3296 3297 3298 3299 3300 1 2 3 4 5 6 7 8 9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 A B C D E F 3301 3302 4 1 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 F 4 4 4 4 4 4 4 4 2 3 4 5 6 7 8 9 B C D E F A 4 4 4 4 4 4 3303 3304 3305 3306 3307 3308 3309 3310 3311 3312 3313 3314 3315 3316 3317 3318 3319 3320 3321 3322 ...

Страница 80: ...281 3282 3283 3284 3285 3286 3287 3288 3289 3290 3291 3292 3293 3294 3295 3296 3297 3298 3299 3300 1 2 3 4 5 6 7 8 0 F F F F F F F F F F F F F F F 0 0 0 0 0 0 3301 3302 E 1 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E 8 E E E E E E E E 2 3 4 5 6 7 8 8 8 8 8 8 8 8 E E E E E E 3303 3304 3305 3306 3307 3308 3309 3310 3311 3312 3313 3314 3315 3316 3317 3318 3319 3320 3321 3322 3323 3324 3...

Страница 81: ... dialing a time delay equal to 10 seconds occurs This delay allows time to connect with the pager service while skipping over any voice announcement When the delay has ended the numeric message is sent This message includes the account number followed by up to 5 reports If a delay time greater than 10 seconds is required see Programming Address 4038 to adjust the delay time In addition increments ...

Страница 82: ...0 3281 3282 3283 3284 3285 3286 3287 3288 3289 3290 3291 3292 3293 3294 3295 3296 3297 3298 3299 3300 1 2 3 4 5 6 7 8 9 3 3 3 3 3 3 3 3 4 3 4 4 4 4 4 0 1 2 3 4 5 3301 3302 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 6 6 6 6 6 6 6 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 3303 3304 3305 3306 3307 3308 3309 3310 3311 3312 3313 3314 3315 3316 3317 3318 3319 3320 3321 3322 3323 332...

Страница 83: ...Number S R S J Zone Number Zone Number 000 None None B T Zone Number B J Zone Number Burglary trouble restoral Zone Fire trouble for a zone F T Number Zone Fire trouble restoral F J Number Supervisory trouble for a zone Waterflow trouble for a zone F T F T Zone Number Zone Number First open after alarm cancel report Tamper RF zone T T Zone Number Open report Close report Duress report Partial clos...

Страница 84: ...nication failure report Communication restoral None None None None Number Receiver Number Receiver Number Receiver Number Receiver Number Receiver EEPROM checksum failure or keypad supervision failure report EEPROM checksum restoral or keypad supervision restoral Multiplex bus fault Multiplex bus restoral Number Receiver Number Receiver None None None None Radio receiver tamper Radio receiver tamp...

Страница 85: ...er Number Radio receiver tamper restoral 341 Receiver Number Radio receiver tamper Keypad Tamper restoral 341 Restoral None 341 Keypad Tamper None The 2 digit 89 display System Fault numbers will be sent in the CID data field for DS7416i fault reports 159 Zone Number Mux Smoke low temperature report 159 Restoral Zone Number Mux Smoke low temperature restoral 306 None Local programming successful r...

Страница 86: ...m the DS7430 Program the multiplex devices through the control panel Per form the following Enter the programmer s mode Enter the multiplex programming mode Do this by entering 9 9 9 5 followed by the button The display will then call up the first zone you have pre programmed to be a multiplex zone To access a different zone press the Reset key then enter the three digit value of the zone you want...

Страница 87: ...IN with test authority Formats display information regarding the B and C keys differently In Contact ID A Fire B Silent Panic C Audible Panic In SIA A Fire B Emergency C Panic a Entering from a Master keypad b Not using a PIN with test authority a Install the keypad jumper properly in the back of the keypad b Check keypad programming addresses 3131 3138 c Check keypad addresses 11 15 System will o...

Страница 88: ...ts Panel never transmits history to WDSRP The communicator test report is not being sent The account codes for 2 8 are not pro grammed or are not programmed correctly a AC power fail messages are sent only with other reports such as low battery b Check AC report offset 3338 If 00 AC report will work like above if another number AC report will be delayed a Not programmed to send history b Time and ...

Страница 89: ... Two modules are programmed with the same address The problem will only occur when both modulees are off normal Isolate the duplicate module by disconnecting sections of the bus and performing a PIN System Reset Reprogram modules OR The system is in the programming mode Exit the programming mode OR Zones have been added to a system protected by Busloc Clear Busloc i There is a short on the multipl...

Страница 90: ...he error clears re program the panel e If error still persists replace the panel 87 display Communicator Err 89 display Report Failure X 87 display 2Ph Bell Fault 89 display System Fault 10 87 display Line 1 Fault 89 display System Fault 11 87 display Line 2 Fault 89 display System Fault 12 87 display Bell Fault 89 display System Fault 13 87 display Aux Output Fault 89 display System Fault 14 a Th...

Страница 91: ...isplay System Fault 52 87 display AR Unreg Modem 89 display System Fault 53 87 display AR Power Fail 89 display System Fault 54 87 display AR Network Lost 89 display System Fault 55 87 display AR Modem HW Err 89 display System Fault 56 87 display AR Modem SW Err 89 display System Fault 57 87 display AR Opt Bus Err 89 display System Fault 58 87 display AR Corrupt MSG 89 display System Fault 59 The ...

Страница 92: ...transformer is defective e In some cases the transformer may be connected to a circuit controlled by a switch or a circuit breaker that is periodically turned off The Fire Alarm was caused by the A key When in Commercial Fire Mode a ground fault causes this display Fire zone wiring problems A multiplex smoke detector has failed its internal sensitivity test a Check wiring to the zone or If the zon...

Страница 93: ...umber 57 0088 Zone Number 58 0089 Zone Number 59 0090 Zone Number 60 0091 Zone Number 61 0092 Zone Number 62 0093 Zone Number 63 0094 Zone Number 64 0095 Zone Number 65 0096 Zone Number 66 0097 Zone Number 67 0098 Zone Number 68 0099 Zone Number 69 0100 Zone Number 70 0101 Zone Number 71 0102 Zone Number 72 0103 Zone Number 73 0104 Zone Number 74 0105 Zone Number 75 0106 Zone Number 76 0107 Zone N...

Страница 94: ...ign 0308 Zone 43 44 Partition Assign 0309 Zone 45 46 Partition Assign 0310 Zone 47 48 Partition Assign 0311 Zone 49 50 Partition Assign 0312 Zone 51 52 Partition Assign 0313 Zone 53 54 Partition Assign 0314 Zone 55 56 Partition Assign 0315 Zone 57 58 PartitionAssign 0316 Zone 59 60 Partition Assign 0317 Zone 61 62 Partition Assign 0318 Zone 63 64 Partition Assign 0319 Zone 65 66 Partition Assign 0...

Страница 95: ...Zone Type 0489 Zone 149 150 Zone Type 0490 Zone 151 152 Zone Type 0491 Zone 153 154 Zone Type 0492 Zone 155 156 Zone Type 0493 Zone 157 158 Zone Type 0494 Zone 159 160 Zone Type 0495 Zone 161 162 Zone Type 0496 Zone 163 164 Zone Type 0497 Zone 165 166 Zone Type 0498 Zone 167 168 Zone Type 0499 Zone 169 170 Zone Type 0500 Zone 171 172 Zone Type 0501 Zone 173 174 Zone Type 0502 Zone 175 176 Zone Typ...

Страница 96: ...tition Assign 2860 Output Function Partition Assign 2861 Output Function Partition Assign 2862 Output Function Partition Assign 2863 Output Function Partition Assign 3131 Keypad Assignment 3132 Keypad Assignment 3133 Keypad Assignment 3134 Keypad Assignment 3135 Keypad Assignment 3136 Keypad Assignment 3137 Keypad Assignment 3138 Keypad Assignment Backlight Control 3139 Keypad Partition Assignment...

Страница 97: ...unction 26 Trouble Report 3297 Zone Function 27 Trouble Report 3298 Zone Function 28 Trouble Report 3299 Zone Function 29 Trouble Report 3300 Zone Function 30 Trouble Report 3301 Zone Function 1 Trouble Restoral 3302 Zone Function 2 Trouble Restoral 3303 Zone Function 3 Trouble Restoral 3304 Zone Function 4 Trouble Restoral 3305 Zone Function 5 Trouble Restoral 3306 Zone Function 6 Trouble Restora...

Страница 98: ... Zone Number 153 5401 Alpha for Zone Number 154 5417 Alpha for Zone Number 155 5433 Alpha for Zone Number 156 5449 Alpha for Zone Number 157 5465 Alpha for Zone Number 158 5481 Alpha for Zone Number 159 5497 Alpha for Zone Number 160 5513 Alpha for Zone Number 161 5529 Alpha for Zone Number 162 5545 Alpha for Zone Number 163 5561 Alpha for Zone Number 164 5577 Alpha for Zone Number 165 5593 Alpha ...

Страница 99: ...able Remote Programmer Callback 24 Entry Pre Alert 21 Entry Exit Delays 19 20 50 Error Display 1 Event History 1 Extend Automatic Arming 1 F Factory Defaults 32 Fire Key 22 Fire Reset 1 26 Fire Safety 27 Fire Trouble 1 26 Alarm how to silence 1 Clear Display 1 Fire Walk Test 1 24 31 Fire Zone 20 First Open After Alarm 23 Flow Zone Water 20 Force Arming 1 22 47 Formats 4 2 79 BFSK 80 CID 85 SIA 83 ...

Страница 100: ...Emergency Key 22 Supervisory Zone 20 Swinger Shunts 19 34 System Problems 89 Status ready to arm 21 Trouble Reports 24 Walk Test 1 24 Worksheet 12 18 System Reset 30 T Temperature Alarm 21 Temporal 22 Temporary PIN 28 Test Battery 1 31 Battery Sounder 1 31 Communicator 1 31 Fire Walk 1 31 System Walk 1 31 Test Report 68 Timer Programming 50 68 Trouble Fire 1 26 On Open 19 On Shor t 19 Zone Functio...

Отзывы: