D8125 | Installation and Operation Guide | 4.0 Installation
.
Bosch Security Systems B.V. | 2020.04 | F01U036298-15
27
4.3.7. Central Station Reports
4.3.7.1 Pulse and BFSK Reporting
When a POPIT initiates an alarm or trouble report, the D8112G/G2 transmits the reports indicating the D8112
master zone tripped. Two POPIT reports to the central station (in addition to alarm, trouble, and restoral
reports for each master zone) are supported.
TROUBLE ZONE D indicates a “missing” POPIT condition.
RESTORAL ZONE D indicates that a “missing” POPIT condition has been resolved.
These reports may be followed by a TROUBLE ZONE # or RESTORAL ZONE # report, which indicates the master
zone assignment of the missing POPIT.
4.3.7.2
Modem II Reporting
Only D8112G2 supports expanded POPIT reports (such as POPIT alarm reports) using Modem II format
reporting.
Trouble Reports
When ZONEX is used on a 24 hour master zone or a controlled point in the disarmed state, and a missing
condition occurs, the following report is printed out on the D6500 Receiver tape:
ACCT 1234 TROUBLE ZN D
ACCT 1234 TROUBLE* ZN 101
* Indicates that this point is “Missing”
Restoral Reports
When the point is restored from the missing condition, the following report will be printed out on the D6500
Receiver tape:
ACCT 1234 RESTORAL ZN D
ACCT 1234 RESTORAL ZN 101
When multiple points on the same master zone go into any trouble condition, all of the points on the master
zone must be returned to normal before individual restoral reports are sent to the D6500 receiver. A
RESTORAL ZONE D will, however, be sent when the backbone itself has restored.
Missing Reports (Multiple)
If multiple points assigned to the same master zone go into a missing condition while in the disarmed state,
the following reports are printed out on the D6500 Receiver tape:
ACCT 1234 TROUBLE* ZN D
ACCT 1234 TROUBLE* ZN 103
ACCT 1234 TROUBLE* ZN 102
ACCT 1234 TROUBLE* ZN 101
* Indicates that this point is “Missing”
Armed Controlled Zone Points
If the D8112G2 is armed, a missing report would be printed out on the D6500 Receiver tape as follows:
ACCT 1234 TROUBLE ZN D
ACCT 1234 ALARM* ZN 101
* Indicates that this point is “Missing”
When multiple points on the same master zone go into any alarm condition, all of the points on the master
zone must be returned to normal before individual restoral reports are sent to the D6500 receiver. A
RESTORAL ZONE D will, however, be sent when the expansion loop itself has restored.
A complete list of reports received by the D6500 Receiver can be found in the D6500 Report Directory (P/N:
4998132019).