Operation

15

Compress 7001i/7400i AW AWE – 6721835320 (2021/09)

Setting the DHW alternating operation

If DHW alternating operation is not activated, DHW heating has priority 
and interrupts the heat requirement of the heating system, if necessary.

Menu: 

DHW alternating operation

Table 11 Settings for the DHW alternating operation

Settings for the DHW circulation

Menu: 

Circulation

Table 12 Settings for the circulation

3.3.3

Settings for the venting function

Menu: 

Ventilation

Table 13 Ventilation settings

3.3.4

Setting up a holiday program

Menu: 

Holiday

CAUTION

Risk of system damage!

▶ Before a prolonged period of absence, only change the settings 

under 

Holiday

.

▶ After a long absence, check the operating pressure of the heating 

system and check the pressure gauge of the solar system if 
applicable.

▶ Do not switch off the solar system during long absences.

Cooling mode will not be activated during a holiday program.

Menu: 

Holiday 1

Holiday 2

Holiday 3

Holiday 4

 and 

Holiday 5

Menu item

Description

DHW alt. 
operation on

In the event of simultaneous DHW and heating 
demand, the system will alternate between DHW 
heating and heating mode based on the times set in 
[Prioritise DHW for] and [Heating priority for].

Prioritise DHW 
for

Duration of DHW heating.

Heating priority 
for

Duration of heating mode.

Menu item

Description

Op. mode

[Off]: Circulation is switched off permanently.

[On]: The pump will run according to the settings under 
[Start frequency]. The time program for the DHW 
circulation pump is not active.

The circulation can be linked to the time program for 
DHW heating.

[My circulation time prog.]: Set a time program for the 
DHW circulation pump that works independently of the 
time program for DHW.

Start frequency

The start frequency determines how often the DHW 
circulation pump goes into operation for three minutes at a 
time every hour (1 x 3 minutes/h ... 6 x 3 minutes/h) or if it 
is constantly in operation. Whatever the case, circulation is 
only active during the times set in the time program.

My circulation time 
prog.

6 switching times can be set for each day or group of days. 
The DHW circulation pump can be switched on or off at 
each switching time. The minimum duration of a time slot 
between two switching times is 15 minutes.

Resetting prog.

The time program is reset to factory default.

Menu item

Description

Op. mode

[Select vent. operating mode.]

• [Sleep]
• [High vent. rate] (high ventilation rate)
• [Auto (time program)]
• [Demand-ctrlled] (demand controlled)
• [Ex.air bypass] (exhaust air bypass)
• [Party vent.] (party ventilation)
• [Firepl.] (fireplace)
• [Fan speed 1 ... 4]
• [Ventil. switched off] (ventilation off)

Time program

[Enter vent. time program.]

Reset time prog.

[Reset ventilation time  program.]

Humidity

[Setting the desired humidity level]:
• [Dry]
• [Normal]
• [Moist]

Air quality

[Setting the desired air quality level:
• [Adequate]
• [Normal]
• [High]

Bypass

[Bypass] for more opening hours:

• [Open]
• [Close.]

Supply air temp. 
control

Set the [Supply air temp.]:
• [Heating]
• [HtgCool] (heating and cooling)
• [Cooling]
• [Off]

Supply air temp. 
control (Electric)

Set the [Supply air temp.]:
• [Heating]
• [Off]

Reheat supp.air 
temp.

[Set the desired supply  air temp. of reh. bank.]

10 ... 

22 

... 30 °C

Filter timer

[Set the time in months until the next filter change.]

1 ... 

... 12 Months

Confirm filter 
change

The filters in the ventilation unit must be changed. 
Please confirm the filter change.

Rename ventil. 
zone

The names of the ventilation zones can be changed 
in the same way as the names of the heating 
circuits. This helps in choosing the right ventilation 
zone.

Menu item

Description

Holiday period

Set the start and end date of the absence during 
holiday: the holiday program starts at the set start 
time at 00:00 o'clock. The holiday program ends at 
the set end time at 24:00 o'clock.

Selection of htg 
circ./DHW

The holiday program is applied to the sections of the 
system highlighted here. Only the heating circuits 
and DHW systems actually installed in the system 
are available for selection.

Heating

Control of the room temperature for the selected 
heating circuits during the holiday period:
• Any [Constant temperature] can be set for the 

selected heating circuits throughout the entire 
holiday period.

• The [Off ]setting deactivates the heating system 

completely for the selected heating circuits.

Menu item

Description

Содержание Compress 7001i AW

Страница 1: ...6721835320 2021 09 GB User Guide Air Water Heat Pump Compress 7001i 7400i AW AWE Heat pump with indoor unit ...

Страница 2: ...the time program automatic mode 9 3 2 8 Selecting active time program for the heating system 10 3 2 9 Renaming a time program or heating circuit 10 3 2 10 DHW settings 11 3 2 11 Setting up a holiday program 11 3 2 12 More settings 12 3 3 Main menu 13 3 3 1 Heating settings 13 3 3 2 DHW settings 14 3 3 3 Settings for the venting function 15 3 3 4 Setting up a holiday program 15 3 3 5 Settings for o...

Страница 3: ...t be performed by children without supervision If the power cable is damaged it must be replaced by the manufacturer its customer service department or a similarly qualified person so that risks are avoided H Inspection and maintenance Regularinspectionandmaintenanceareprerequisites for safe and energy efficient operation of the heating system We recommend you enter into a contract for the annual ...

Страница 4: ...ity is available on the Internet worcester bosch co uk 2 3 Heat pump outdoor unit The heat pump is inverter operated which means that it will automatically change the compressor speed to deliver the exact amount ofenergyrequiredatthemoment ThefanisalsoRPMcontrolledandwill change its speed as needed This provides the lowest possible energy consumption The speed changes have an effect on the sound e...

Страница 5: ...is connected to the unit AWE an external DHW cylinder must be connected if the heat pump is to produce hot water The change between heat and hot water is then controlled via an external 3 way valve The integrated booster heater in the indoor unit is started if necessary Fig 3 Heat pump Compress 7001i 7400i AW indoor unit AWE with electric booster heater and external hot water cylinder 2 5 Hints on...

Страница 6: ...thermal disinfection Dependingonthesoftwareversionoftheuserinterface thetextsshown in the display may differ from the texts in these instructions The adjustment ranges default settings and functional scope may differ from the information in these instructions depending on the system installed at the site If 2 or more heating circuits are installed settings for different heating circuits are availa...

Страница 7: ...circuit Heat source temperature if there are no remote control installed 2 Info line display of time of day day of the week and date 3 Additional temperature display outside temperature temperature of the solar collector or a DHW system For ventilation display of the ventilation level For ventilation frost protection reduced ventilation 4 Text information e g the designation of the temperature cur...

Страница 8: ...ndow is displayed and thetimeprogramisactivated The currently valid temperature flashes Activating optimised operation without time program If automatic mode is active Press the menu key Press the selector to open the Heating or Heating Cooling menu Press the selector to open the Op mode menu Highlight the desired heating circuit and press the selector Choose Optimise and press the selector Press ...

Страница 9: ...program for the heating system Turn and press the selector to activate the input field for a switching time Set and confirm the switching time Adjusting the temperature operating mode for a time slot Open the menu for adapting a time program for the heating system Turnandpresstheselectortoactivatetheinputfieldfortheoperating mode of a time slot Set and confirm operating mode Deleting switching tim...

Страница 10: ... available if 2 or more heating circuits are installed Open the main menu Open Heating or Heating Cooling Time program Heating circuit 1 Rename heating circuit menu or other heating circuit The cursor flashes to indicate the start position for data input Entering adding characters Open menu for renaming a time program or heating circuit Turn the selector to position the cursor in the required loca...

Страница 11: ...HW Extra hot water Set the maximum DHW temperature and duration as desired Select and confirm Start now Select Yes in the pop up window and confirm The water heating becomes active immediately Once the set duration time has expired the extra DHW cylinder charging switches off again automatically Open the menu for adapting the time program for DHW heating Open the main menu Open the DHW Time progra...

Страница 12: ...Select Yes in the pop up window and confirm The holiday program is deleted 3 2 12 More settings Setting the time and date If the user interface has been disconnected from the power supply for a prolonged period the date and time must be set Restore the power supply The user interface displays the setting for the date Set the day month and year respectively and confirm Confirm Next The user interfa...

Страница 13: ...e My time program 1 Resetting prog The default setting for My time program 2 can be restored here Rename time prog The names of the time programs can be changed in the same way as the names of the heating circuits This helps to select the correct time program e g family or night shift Menu item Description Heating Cooling In summer heating cooling mode can be switched off Continuous summer The hea...

Страница 14: ...y heat up outside normal hours of use Make sure that a thermal mixer is installed If in doubt ask your installer Menu Autom therm disinfect Table 10 Settings for thermal disinfection Menu item Description Op mode Off Deactivated no DHW production Always on DHW Eco 1 Lowest DHW temperature mode that results in lowest energy consumption Always on DHW Eco Medium DHW temperaturemodethatresultsinmedium...

Страница 15: ... time prog 6 switching times can be set for each day or group of days The DHW circulation pump can be switched on or off at each switching time The minimum duration of a time slot between two switching times is 15 minutes Resetting prog The time program is reset to factory default Menu item Description Op mode Select vent operating mode Sleep High vent rate high ventilation rate Auto time program ...

Страница 16: ...ure may be increased Forced peak 2 5 C Set how much the room temperature is forced to increase DHW The energy available in the smart grid is used for DHW Selectable peak Yes No If enabled the DHW is heated to the temperature set for DHW operating mode Always on DHW comfort No heating is done if the holiday program is active Menu item Description Menu item Control range Function description Heating...

Страница 17: ...valid in the selected heating circuit Inautomaticmode thiscanchangeseveraltimes a day if necessary In normal operation it is always constant Measured room temp Currently measured room temperature in the selected heating circuit Measured flow temp Currently measured flow temperature in the selected heating circuit Menu item Description Menu item Description Set temp Desired DHW temperature Measured...

Страница 18: ... consumed by the electric booster heater Heating Cumulatedenergyconsumedbytheelectricbooster heater in heating mode DHW Cumulatedenergyconsumedbytheelectricbooster heater in DHW mode Pool Cumulatedenergyconsumedbytheelectricbooster heater in pool heating mode Menu item Description Total Cumulated total energy consumed by the heat pump Heating Cumulated energy consumed by the heat pump in heating m...

Страница 19: ...more frequent intervals If a lot of magnetic dirt is clinging to the magnetic bar in the particulate filter and that dirt frequently causes an alarm related to the poor flow e g low or poor flow high flow supply or HPalarm anapprovedmagnetitefilter mustbeinstalledtoavoidregular drainingoftheindicator Themagneticfiltermustbeinstalledinaddition to the mesh filter and be placed in the secondary circu...

Страница 20: ...acks and damage on the casing with anti corrosive paint Standard car wax can be applied to protect the paint 4 2 2 Evaporator Any layers of dust or dirt for example deposited on the surface of the evaporator must be removed CAUTION The aluminium fins are thin and sensitive They can be damaged easily due to careless handling Never use hard objects Never rub the fins directly with a cloth Wear prote...

Страница 21: ...upport TheIPmodulecanbeusedtocontrolandmonitorthesystemviaamobile device It is used as an interface between the heating system and a network LAN and also enables the SmartGrid function The IP module is installed as standard in a number of products and can be retrofitted to others as an accessory To take advantage of all the functions an Internet connection and router with a free RJ45 output are ne...

Страница 22: ...ce Login data for the IP module Manuf no _________________________________________________________________ Login name _______________________________________________________ Password _______________________________________________________________ Mac _____________________________________________________________________ 4 4 Information on refrigerant This device contains fluorinated greenhouse gase...

Страница 23: ...ther information are provided on request You can contact our Data Protection Officer under Data Protection Officer Information Security and Privacy C ISP Robert Bosch GmbH Postfach 30 02 20 70442 Stuttgart GERMANY You have the right to object on grounds relating to your particular situation or where personal data are processed for direct marketing purposes atanytimetoprocessingofyourpersonaldatawh...

Страница 24: ...is heated in accordance with the time program and switching between the operating modes occurs automatically Operating phase The heating operating phases are heating and setback They are depicted by the symbols and The operating phases for DHW heating are DHW DHW reduced and Off A temperature can be set for each operating phase except for Off Frost protection Depending on the type of frost protect...

Страница 25: ...ng priority for Circulation Op mode Start frequency My circulation time prog circulation time program Resetting prog reset circulation time program Ventilation Op mode Time program Reset time prog Humidity Air quality Bypass Supply air temp control Reheat supp air temp After heater supply air temperature Filter timer Confirm filter change Rename ventil zone Pool Switch on pool heating Pool tempera...

Страница 26: ... cool Op hours for comp DHW Op hours for comp pool Number of heating starts Number of cooling starts Number of DHW starts Number of pool starts Energy consump Total Electric auxiliary heater Total Heating DHW Pool Compressor Total Heating DHW Cooling Pool 24h ventil current 30d ventil current Energy supplied Total energy suppl Heating energy suppl DHW energy suppl Emitted cooling energy Pool energ...

Страница 27: ...Overview Info 27 Compress 7001i 7400i AW AWE 6721835320 2021 09 ESC block PV system Smart grid Current operation COP heat source ...

Страница 28: ... Cotswold Way Warndon Worcester WR4 9SW United Kingdom Tel 0330 123 9559 worcester bosch co uk 0330 123 3366 TECHNICAL SUPPORT RENEWABLE SUPPORT 0330 123 9229 CONTROLS AND CONNECTIVITY TEAM 0330 123 3641 0330 123 9339 0330 123 9779 0330 123 9119 0330 123 0166 0330 123 9669 ...

Отзывы: