Climate 5000 8736862495(2015/07)
Unit maintenance | 19
No.
Inspection and
maintenance items
Maintenance measures
1
M
3
M
6
M
1
Y
2
Y
Remarks
Inspection and
maintenance
intervals
9.3
Check the abnormal noise,
heat, etc. of the bearing
△
Refill in
accordance
with manu-
facturer
requirement
9.4
Check the vibration and
wearing condition of the fan
axle
△
9.5
Check the leakage of the soft
connections
△
9.6
Check the damping state of
the shock absorber
△
9.7
Check the tightness of the
fan fastening bolts
△
1
0
Drive components
1
0.
1
Motor
1
0.
1
.
1
Check the scale on the motor
surface
Clean
△
1
0.
1
.2 Measure voltage
Record measured value
△
1
0.
1
.3 Measure consumed power
Record measured value
△
1
0.
1
.4 Check the bearing noise
△
1
0.
1
.5
Check the vibration and
abnormal noise of the motor
bearing
△
1
0.2
Belt drive
Only for
the unit
with belt
driven fan
1
0.2.
1
Check the belt tension and
parallelism
Adjust in accordance with
the inspection
△
1
0.2.2 Check the wearing condition
of the belt
△
1
0.2.3 Adjust or replace belt in
accordance with conditions
★
1
0.2.4 Check the tightness of the
axle key
△
1
0.2.5 Check the wearing condition
of the pulley
△
Tab. 6-3 Inspection and maintenance items 3