5 Unit maintenance

5.1 Maintenance and inspection

Daily maintenance and periodical maintenance is 

essential to ensure that the MAHU and associ-

ated devices perform as designed specifications. 

Please follow the requirement listed below to 

ensure MAHU long-term safety operation (the 

MAHU power supply shall be powered off when 

inspecting).

•    

During the commissioning, check the unit once 

a day. During normal operation, periodical 

maintenance shall be carried out at a fre-

quency of once a week to once a quarter or 

once half a year to once a year in accordance 

with operating environment and conditions.

•    

Bolts on all parts are tightened, or otherwise it 

will become a major cause of vibration.

•    

Belt and pulley 

(only used for belt-driven fan)

-  The belt tension of MAHU has been adjusted 

in factory. However, belt slack may occur 

due to some factors. Therefore, re-adjust 

belt tension if necessary. Apply a load of 

20-30N pressure to the center of belt, and 

the deflection of the belt is approximately 

5-20mm (→ Fig. 16).

-  When the belt cracked, broken or heavily 

worn, it shall be replaced with a new imme-

diately. 

-  Check pulley for angle error. If the installa-

tion accuracy of two pulleys is not enough, it 

will affect the belt service life. For the axle 

parallelism and eccentricity, please maintain 

θ

1/3°(Fig. 17).

-  The bearing will be damaged if the pulley 

side has been suffered strong impact during 

installing and removing pulley. 

Fig. 16 Schematic diagram of belt tensioning

Fig. 17 Schematic diagram of pulley calibration

•    

Bearing

Permanently lubricated bearings are maintenance 

-free, the oil filling time for other bearings could 

follow the recommendation as follows. Under 

normal operation:

-  If The unit runs below the temperature at 

40

 operating environment, filling oil once in 

every 2,000-5,000 hours. When the environ-

ment temperature raise each 10

, the life-

time of grease and lubrication should be cut 

by half. 

-  If unit is running in wet environment with rela-

tive humidity greater than 85%, filling lubricat-

ing oil once every 2000-2,500 hours.

The filling time above is just for reference, if fan 

manufacture has special requirements, please do 

it according to the fan manufacturer’ s require-

ment

.

14 | Unit maintenance

8736862495(2015/07)                                                                                                                     Climate 5000

 

θ

θ

a

a

5~20mm

P20-30N

Notice: 

When Re-lubrication, please clean the 

nozzle, remove the harden grease; 

please don't stop until the new oil is 

squeezed out from the bearing, in order 

to avoid over-adding, please use your 

hands to move the bearing during 

adding. To avoid the lubrication oil 

splashing, use cotton to wipe out the 

extrusion lubricant oil after adding; after 

filling the lubrication oil, please cover 

the plastic lid over filler hole.

Warning: 

Before re-lubrication, please cut off the 

power supply. Otherwise it may cause 

electric shock or other injuries like  

scrambled into running machine, result 

in serious harm or death.

Содержание Climate 5000

Страница 1: ...HUP C 32 40 en Installation Operation and Maintenance Manual 8736862495 2015 07 CN Read the manual carefully prior to installation and operation the unit Observe the warnings in the manual Installation by an authourised person only Climate 5000 ...

Страница 2: ...tact us for obtaining the latest information Table of Contents 1 Key to symbols and safety introductions 3 1 1 Explanation of symbols 3 1 2 Safety information 3 1 3 Delivery handling and storage 4 1 3 1 Delivery inspection 4 1 3 2 Way of transport 4 1 3 3 Storage of the unit 4 2 Unit introduction 6 2 1 Type introduction 6 2 2 Product introduction 6 2 3 Left right Hand pipe connection 6 2 4 Unit sy...

Страница 3: ...d documents a list entry a list entry second level Key to symbols and safety instructions 3 1 Key to symbols and safety introductions Caution Risk of falling Pay attention to the center of gravity and weight when move in and out Notice Carry out electrical work as per relevant electrical standards and rules for electrical works Notice Risk of loosing Tighten the bolt for connection and assembling ...

Страница 4: ...of lifting frame shall be capable of avoiding all lifting loads to prevent severe damage Each lifting appliance shall be capable of bearing the overall weight of the unit and maintaining suffi cient weight allowance Page5 Fig 1 Sche matic diagram of unit lifting Use lifting steel pipe for unit lifting When the delivery weight is within 2000kg use steel pipe with caliber and wall thickness Φ 48 6 w...

Страница 5: ...Key to symbols and safety instructions 5 Climate 5000 8736862495 2015 07 Max 60 Fig 1 Schematic diagram of unit lifting ...

Страница 6: ...n commissioning and maintenance because of failure to comply steps and instructions specified by this manual shall be free of any responsibilities of the manufacture 2 3 Left right Hand pipe connection Page 7 Fig 3 Schematic diagram of distin guishing left and right type For MAHU with Mono structure Left or Right Hand pipe connection is decided by judging the relative position of Air Inlet to the ...

Страница 7: ...ach unit for the possible risks The following symbols are the unit functional section or warning symbols the color of which is coal ash color and shadow of the lines is industrial gray 高温 HIGH TEMPERATURE Left Right Left type unit Air inlet Fig 3 Schematic diagram of distinguishing left and right type Symbols Instruction Symbols Instruction Air damper Muffler Pre filter Fan Medium filter Drip elim...

Страница 8: ... 1 Product introduction To prevent vibration and noise transmission anti vibration pads shall be applied between equipment and foundation foundation level ness should be 1 1000 After placement the tolerance of entire unit in height and width shall be controlled within 3mm For the details of foundation installation Fig 6 8 Unit installation 8736862495 2015 07 Climate 5000 Flat face foundation Concr...

Страница 9: ...an 3mm Use hex bolt M12 80 hex nut M12 for the fixation of the corner of each section Fig 9 Use sealing glue for the connection parts of frame work and hex flangeself drilling tapping screws ST5 5 35 for the fixation of sealing compartment 8mm PE heat preservation foam stuck in ad vance Fig 8 2 Connect other parts and fasten the bolt Fig 8 1 Schematic diagram of section connection 1 Fig 8 2 Schema...

Страница 10: ...herein the air inlet and outlet pipe is connected through pipe thread or flange with PTFE tape applied on the thread and the connection type of water pipe is down in and up out Fig 12 Connect heat exchanger in accordance with the counterflow principle water flow direction counter to airflow direction in unit Except for condensate pipe the buyer should provide venting valves and drain valves in the...

Страница 11: ...ion we recommend to use floating ball siphon a self filling siphon for drainage of heat exchangers humidifiers and other wet regions at a pressure lower than ambient pressure it contains a floating ball which prevents the intake of air so that the first accumulating condensate produced can fill the siphon for the alternative U siphon for the problem mentioned below Fig 14 Schematic diagram of floa...

Страница 12: ...thod phase fail ure connection can lead to over burning of motor For wiring methods Fig 15 Motors on supply fan and humidifier must be set with interlock device 3 8 Electrical wiring of motors Configure and correct connect electric appli ances and wiring according to electrical heating wiring diagram and schematic diagram of the units Metal shell for electrical heater coil shall be well grounded E...

Страница 13: ... has humidifying function fan shall be started before water steam when stop the unit water steam shall be stopped prior to fan For the brand new unit when the temperature of fresh air is less than 2 pre heating the coil or applying corresponding protective measures is required to prevent from coil frost cracking inside the unit When power on the unit and motor is started please stop the operation ...

Страница 14: ...ulley side has been suffered strong impact during installing and removing pulley Fig 16 Schematic diagram of belt tensioning Fig 17 Schematic diagram of pulley calibration Bearing Permanently lubricated bearings are maintenance free the oil filling time for other bearings could follow the recommendation as follows Under normal operation If The unit runs below the temperature at 40 operating enviro...

Страница 15: ...en accidents to the motor and also pollute the air Cooling and heating coil Regularly check coil cleanliness clean if nec essary When using high pressure cleaning be careful with aluminum fins to avoid da mages The scale in coil will reduce cooling and heat ing capacity Please use chemical agents to clean the scale after consulting with the pro fessionals Hot and cold water quality needs to be man...

Страница 16: ...roperly designed hydraulic seal to block the water If the hydraulic seal damaged it may cause leakage Heat exchanger When carrying out maintenance and cleaning for full heat recovery please clean dust on full heat exchanger materials by lightly using the vacuum cleaner month Do not use water steam and solution to wash full heat ex changer materials Carry out inspection and maintenance on the belt ...

Страница 17: ...e operating condition 3 2 Check the pressure difference at both sides When the clean filter resistance exceeds the maximum allowable value replace the filter 4 Coil 4 1 Check the scale damage and corrosion Clean and rectify 4 2 Check the ability state 4 3 Check the connection leakage between inlet and outlet pipe Seal if necessary 5 Water baffle drain pan 5 1 check water baffle 5 2 Check the drain...

Страница 18: ... 8 1 5 Check the scale in the high pressure pipe Clean 8 1 6 Check the nozzle Clean the nozzle and replace the organic filter element in it 8 1 7 Check the tightness of the electrical connector Tighten if necessary 8 2 Wet film humidifier 8 2 1 Check the scale and damage on the surface Clean and rectify 8 2 2 Check the water supply 8 2 3 Check the tightness of connections 8 3 Dry steam humidifier ...

Страница 19: ...astening bolts 10 Drive components 10 1 Motor 10 1 1 Check the scale on the motor surface Clean 10 1 2 Measure voltage Record measured value 10 1 3 Measure consumed power Record measured value 10 1 4 Check the bearing noise 10 1 5 Check the vibration and abnormal noise of the motor bearing 10 2 Belt drive Only for the unit with belt driven fan 10 2 1 Check the belt tension and parallelism Adjust i...

Страница 20: ... abnormal Check voltage Bearing abnormal Replace Connecting part Connecting parts loose Tighten Outer plate loose Tighten Gasket peeled off Rectify Vibration Fastening state abnormal loose bolts poor base Tighten bolts Strengthen base Belt loose Adjust the belt tension Ingress of impurities Clean Bad dynamic balance of moving parts Adjust dynamic balance Contact of moving parts Adjust clearance Pu...

Страница 21: ...e Reduce resistance The opening of air valve too small Check and adjust Fan speed low Increase fan speed Dust Clean Filter blocked Clean replace Coil fin blocked Clean Leaking outside the unit Pipe connection loose Tighten Condensate water outlet blocked Clean Unreasonable design of drain seal Adjust hydraulic seal size Water splashing inside the unit Humidifier abnormal Repair in accordance with ...