System components
Systemlösung – 6 720 885 509 (2018/03)
8
2.2.3
Operation conditions CHP
The following operating conditions are required to
maintain the warranty:
• Ensure dust and halogen-free cooling and
combustion air
• Ensure that the exhaust air and exhaust gas lines are
correctly dimensioned, and run them separately
• Maximum setup height without a drop in
performance: depending on model used 100 ... 500
meters above zero
• Ratio of starting/operating hours: 1 start to 6
operating hours averaged over the year
• Methane count: 80
• Natural gas Hi = 10 kWh/m
3
• Maximum exhaust gas counterpressure depending on
GenSet motor manufacturer 40 ... 60 mbar
• Module only suitable for setup within a building
• The condensate and flue gas line are pressurized and
must be appropriately designed, and the operating
pressure must be demonstrated in a pressure test.
Unit
CHP CE 1287 NE
CHP CE 1560 NE
CHP CE 1718 NE
CHP CE 1999 NE CHP CE 2000 NE
GenSet
Gas category
–
Natural gas
Natural gas
Natural gas
Natural gas
Natural gas
Power consumption
kW
2974
3629
3991
4666
4588
Electrical output
kW
1287
1560
1718
1999
2000
Thermal output
kW
664
819
974
1076
1053
Electrical efficiency
%
43.3
43
43
42.8
43.6
Type
–
Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Engine manufacturer
–
MTU
MWM
MTU
MTU
MWM
Engine model
–
12V4000 L33
TCG 2020 V16
16V4000 L33
20V4000 L33
TCG 2020 V20
Dimensions
Length
mm
4800
6300
5500
5900
7820
Width
mm
2000
1800
2000
2000
1800
Height
mm
2300
2500
2300
2400
2680
Weight (empty)
kg
12000
13400
15000
19000
18100
Generation of electricity
Generator
manufacturer
–
Stamford
Marelli
Leroy-Somer
Stamford
Marelli
Generator type
–
PE734F
MJB 500 LA4
LSA 51.2
VL95 C6S/4P
LV804T
MJB 560 LB4
Voltage/Frequency
V/Hz
400/50
400/50
400/50
400/50
400/50
Speed
1/min
1500
1500
1500
1500
1500
Efficiency
generator
%
96.5
97.1
96.5
96.3
97.4
Temperature levels
LT mixture circuit
°C
43/40
44/40
43/40
43/40
45/38
Heating water
without flue gas heat
exchanger
°C
85/75
85/75
85/75
85/75
85/75
Flue gas temperature
without flue gas heat
exchanger
°C
440
426
426
449
410
Maximum flue gas
temperature
°C
550
550
550
550
550
Flue gas tube
dimension (KAT)
–
DN 350/PN 10
DN 400/PN 10
DN 400/PN 10
DN 450/PN 10
DN 450/PN 10
Flue gas mass flow
rate (wet)
kg/h
6700
8665
8940
10458
10983
Available flue gas
back pressure
mbar
25
25
25
25
25
Flue gas back
pressure boiler
mbar
15
15
15
15
15
Flue gas limit values
CO
mg/m
3
i.N.
d
300
d
300
d
300
d
300
d
300
NOx
mg/m
3
i.N.
d
250
d
250
d
250
d
250
d
250
NMHC
mg/m
3
i.N.
d
150
d
150
d
150
d
150
d
150
Table 2 Specifications CHP CE 1287 NE ... CHP CE 2000 NE