6     Control Logic

6.1     Connector

Connector

Purpose

Y

Cooling

W

Heating

G

Fan- Auto speed

AUX/DRY

Aux-Heat/Dry

Table 6

6.2     Mode Setting

Y

W

G

Aux/Dry

Setting mode

X

*

*

Cooling

X

*

X

Heating (without aux-heater)

X

*

Heating (with aux-heater)

X

X

X

Fan only

*

*

OFF

X

X

X

X

OFF

X

X

*

Dry

Table 7

     

√   = ON
X     = OFF

= ON or OFF

6.3     Fan Speed Setting

Unit ON/OFF

G

Setting fan speed

X

Auto fan speed

Auto fan speed

X

X

Fan OFF

Table 8

√   = ON
X     = OFF

7     Dip Switch Con

fi

 guration

The 24V INTERFACE must be confi gured to operate properly with the system 
components with which it is installed. To successfully confi gure the system, move 
the Dip Switches to match the components and functions used.

7.1     Dip Switch De

fi

 nitions

Figure 8

SW2

SW3

SW4

SW1

Dip Switch 1-1

Used to turn ON or OFF the diagnostic code display LED on the control board of the 
24V Interface. 

SW1-1

Result

Note

ON

Display on

OFF

Display off 

Default

Table 9

Dip Switch 1-2

Used for selection of the indoor unit type.

SW1-2

Result

Note

ON

Enables 24V INTERFACE to work with IDU & ODU

OFF

N/A

Default

Table 10

 

   Must be switched to ON before using the system.

Dip Switch 2-1

Used for selection of the system: Cooling Only or Heat Pump.

SW2-1

Result

Note

ON

Cooling only

OFF

Heat pump

Default

Table 11

Содержание BMS500-AAS012-0AHWXB

Страница 1: ...24 Volt Interface For use with Bosch Split Type Ductless Air Conditioner Heat Pump 208 230V 60Hz 1Ph 115V 60Hz 1Ph Installation Manual ...

Страница 2: ...2 Bosch Climate 5000 Series 24 Volt Interface Installation Manual 06 2019 Bosch Thermotechnology Corp Data subject to change ...

Страница 3: ...ty Instructions 4 1 1 Key to Symbols 4 1 2 Safety Instructions 4 2 Dimensions 5 3 Clearances 5 4 Installation 6 4 1 Preparation 6 4 2 Installation Process 6 5 Applications 7 5 1 Application 1 7 5 2 Application 2 9 6 Control Logic 10 6 1 Connector 10 6 2 Mode Setting 10 6 3 Fan Speed Setting 10 7 Dip Switch Configuration 10 7 1 Dip Switch Definitions 10 8 Error Codes 12 ...

Страница 4: ...formation where there is no risk to people or property 1 2 Safety Instructions Read this manual carefully before installing or operating your new 24 Volt Interface Adapter Make sure to save this manual for future reference WARNING Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only WARNING All wiring to be rated for the control box amperage...

Страница 5: ...ermotechnology Corp 06 2019 Data subject to change 2 Dimensions Figure 1 220mm 8 7 32mm 1 3 176mm 6 9 15mm 0 6 200mm 7 8 283mm 11 1 63mm 2 5 3 Clearances This interface must be installed indoors in an area free from drips and moisture Figure 2 Right Wrong 150mm 5 9 150mm 5 9 ...

Страница 6: ...3 Figure 3 Minimum free space required around the product is 7 180 mm 2 Mount the back plate of the 24V INTERFACE on the wall Mount the 24V INTERFACE vertically and fasten the back plate to the wall with 3 screws M4 x20 and anchors see Fig 4 Figure 4 Back plate Screws M4 20 Place the unit on a flat surface Be careful not to distort the back plate of the 24V INTERFACE by over tightening the screws W...

Страница 7: ... AAS030 1AHWXB 8733953098 Minisplit 30kBTU Single Zone Wall Mounted 230V BMS500 AAS036 1AHWXB 8733953100 Minisplit 36kBTU Single Zone Wall Mounted 230V Cassette BMS500 AAU009 1AHCXB 8733953109 Minisplit 9kBTU Universal Cassette 230V BMS500 AAU012 1AHCXB 8733953110 Minisplit 12kBTU Universal Cassette 230V BMS500 AAU018 1AHCXB 8733953111 Minisplit 18kBTU Universal Cassette 230V BMS500 AAU024 1AHCXB ...

Страница 8: ...technology Corp Data subject to change Wiring Figure 6 Thermostat 70 Please connect thermostat G to 24V interface G as default Make sure the power supply is correct For Wall Mounted unit the up down swing louver and the display on off function is available with the wireless remote control ...

Страница 9: ...tte 230V BMS500 AAU048 1AHCXB 8733953114 Minisplit 48kBTU Universal Cassette 230V Ducted BMS500 AAU036 1AHDXB 8733953106 Minisplit 36kBTU Universal Ducted 230V BMS500 AAU048 1AHDXB 8733953107 Minisplit 48kBTU Universal Ducted 230V BMS500 AAU060 1AHDXB 8733953108 Minisplit 60kBTU Universal Ducted 230V Table 5 Cassette Sizes 36K 48K Ducted 36K 60K Wiring Figure 7 Thermostat Please connect thermostat...

Страница 10: ...4V INTERFACE must be configured to operate properly with the system components with which it is installed To successfully configure the system move the Dip Switches to match the components and functions used 7 1 Dip Switch Definitions Figure 8 SW2 SW3 SW4 SW1 Dip Switch 1 1 Used to turn ON or OFF the diagnostic code display LED on the control board of the 24V Interface SW1 1 Result Note ON Display o...

Страница 11: ...ating mode Dip Switch 3 1 Dry is used for thermostats with a Dry Function output An auxiliary heater is used on the Ducted Indoor Units to control a secondary Heat Source SW3 1 Result Note ON Dry OFF Aux heater Default Table 13 Dip Switch 3 2 Used to increase the compressor frequency in case the set point has not been reached after 1 hour or 3 hours of operation SW3 2 Result Note ON 1h OFF 3h Defa...

Страница 12: ...ent temperature sensor T4 malfunction F2 Condenser coil temperature sensor T3 malfunction F3 Condenser coil temperature sensor T5 malfunction F4 Outdoor unit EEPROM parameter error F5 Outdoor fan speed error F6 T2b sensor error P0 Inverter module IPM malfunction P1 Over voltage or under voltage protection P2 Compressor top high temperature protection OLP P3 Low ambient temperature cut off in heatin...

Страница 13: ...Installation Manual Bosch Climate 5000 Series 24 Volt Interface 13 Bosch Thermotechnology Corp 06 2019 Data subject to change ...

Страница 14: ...14 Bosch Climate 5000 Series 24 Volt Interface Installation Manual 06 2019 Bosch Thermotechnology Corp Data subject to change ...

Страница 15: ...Installation Manual Bosch Climate 5000 Series 24 Volt Interface 15 Bosch Thermotechnology Corp 06 2019 Data subject to change ...

Страница 16: ...United States and Canada Bosch Thermotechnology Corp 65 Grove Street Watertown MA 02472 Tel 1 866 642 3198 Fax 1 603 965 7581 www boschheatingandcooling com BTC 769003109 A 06 2019 ...

Отзывы: