Detailed infromation of corresponding objects refer to under-table  

1) Device infromation

Attribute Identifier

Data mode

Attribute value

Read/write

Object Identifier

BACnetObjectIdentifier

Acnumber

R

Object Name

CharacterString

Indoor * *

R

Object Type

BACnetObjectType

Device

R

Device Status

BACnetDeviceStatus

Operational

R

Producer Name

CharacterString

AC Inc

R

Producer Identifier

Unisgned16

1 1 1 (Unsigned)

R

Model Name

CharacterString

Get one of these from protocolanalysis: Wall Mounted Tpye Floor Tpye Embedded 

Tpye Duct Tpye Floor&ceiling Tpye AC Auxiliary Machine Tpye Digital Mutil-

connection Tpye Frequency Conversion Tpye Digital Rotation Tpye

R

Firmware Edition

CharacterString

1.0

R

Application Software Edition

CharacterString

1.0

R

Protocol Edition

Unsigned

1

R

Protocol Correspondency Type

Unsigned

3

R

Protocol Service Support

BACnetServiceSupport

ReadProperty

R

Protocol Object Types Support

BACnetObjectTypesSupport

AnalogInput

R

Object Array

BACnetArray[n]

Array all object

R

Max length of APDU support

Unsigned

1476

R

Segmentation support

BACnetSegmentation

Segmented both(0)

R

Local Time

Time

R/W

Local Date

Date

R/W

APDU Segmentation Timeover

Unsigned

2000

O

APDU Timeover

Unsigned

3000

R

APDU Resend Times

Unsigned

3

R

Device Address Binding

AddressBinding

ASN.1 ‘’

R

Operation instruction

The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 1 ELECTRIC CURRENT (it’s unsettable). The 

MINIMAL VALUE stands for the MINIMUM ELECTRIC CURRENT, while the MAXMUN VALUE stands for the MAXIMUM ELECTRIC 

CURRENT.

2) Running mode

Attribute Identifier

Data mode

Attribute value

Read/write

Object Identifier

BACnetObjectIdentifier

Multistate-output 1

R

Object Name

CharacterString

AC_OModeSetting

R

Object Type

BACnetObjectType

Multistate-output

R

Description

CharacterString

Operation mode setting

O

Current value

Unsigned

W

Status Flags

BACnetStatusFlags

F F F F

R

Event states

BACnet EventStates

Normal

R

Take off service

BOOLEAN

F

R

States number

Unsigned

6

R

States text

BACnet ARRAY[N] 

CharacterString

Auto 

Cool 

Heat 

Dehumidify 

FanOnly 

Stop

O

Priority Array

BACnetPriorityArra

NULL

R

Release default

Unsigned

0

R

Time delay

Unsigned

2

O

Publicly type

Unsigned

1701

O

Feedback value

Unsigned

6

CLIMATE 5000 VRF

6720862469 (16/04)

OBJECT TABEL

 

|

 

5

Содержание BMS-BAC

Страница 1: ...6720862469 16 04 Before using your bacnet please read this manual carefully and keep it for future reference CLIMATE 5000 VRF Building Management System Gateway Card Bacnet BMS BAC User manual ...

Страница 2: ...CONTENTS 1 CONNECTING DIAGRAM 3 2 FUNCTION DESCRIPTION 3 3 CONFIGURATION ILLUSTRATION 3 4 OBJECT TABEL 4 2 CONTENTS 6720862469 16 04 CLIMATE 5000 VRF ...

Страница 3: ...ACnet into a web browser 3 1 Control setting The local network code range will be between 0 and 63 The name of the network will automatically configure which can be changed to something more memorable After the demand has been set and the equipment has been restarted the equipment will modify the changes The control code has been set randomly before ex factory means of control code in CONTROL UNIT...

Страница 4: ...onnect 1 and 2 of 485 This will restore factory settings of the BACnet 4 OBJECT TABEL This device provides with different objects tables for the different types of outdoor units which are in using for the VRF system System will automatically identify using outdoor unit and generate the BACnet object 4 1 Indoor objects This equipment provides with fourteen types of BACnet object show as the followi...

Страница 5: ...76 R Segmentation support BACnetSegmentation Segmented both 0 R Local Time Time R W Local Date Date R W APDU Segmentation Timeover Unsigned 2000 O APDU Timeover Unsigned 3000 R APDU Resend Times Unsigned 3 R Device Address Binding AddressBinding ASN 1 R Operation instruction The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 1 ELECTRIC CURRENT it s unsettable The MINIMAL VA...

Страница 6: ...lue Unsigned 5 Event enable BACnetEventTransitionBits T T T O Affirm transform BACnetEventTransitionBits T T T O Notify Type BACnetNotifyType alarm O Operation instruction The CURRENT VALUE attribute of the selected object reflects the current FAN SPEED It s writable and settable Thereinto the CURRENT VALUE 1 means HIGH SPEED the CURRENT VALUE 2 means MEDIUM SPEED the CURRENT VALUE 3 means LOW SPE...

Страница 7: ...y NO FAULT DETECTED R Take off service BOOLEAN F R Unit BACnetEngineering Units Degree Celsius R Minimum REAL 20 O Maximum REAL 100 O Distinguishability REAL 1 O Time delay Unsigned 1 O Publicly type Unsigned 1701 O Low valve value REAL 20 O High valve value REAL 100 O Width valve value REAL 1 O Enable valve value BACnetLimitEnable T T O Event enable BACnetEventTransitionBits T T T O Notify Type B...

Страница 8: ...String Off Time Setting O Status Flags BACnetStatusFlags F F F F R Event states BACnet EventStates Normal R Take off service BOOLEAN F R Unit BACnetEngineering Units Hours R Minimum REAL 0 O Maximum REAL 24 O Distinguishability REAL 0 25 O Reliability BACnetReliability NO FAULT DETECTED O Priority Array BACnetPriorityArra NULL R Default release REAL 0 R COV INCREMENT REAL 0 25 O Low valve value RE...

Страница 9: ...ame CharacterString AC _OElecHeat R Object Type BACnetObjectType Binary output R Current value BACnetBinaryPV Inactive W Discription CharacterString Elecheat Setting O Status Flags BACnetStatusFlags F F F F R Event states BACnet EventStates Normal R Take off service BOOLEAN F R Polarity BACnetPolarity Normal R Inactive text CharacterString Turn off O Active text CharacterString Turn on O Time dela...

Страница 10: ...e of the selected object reflects the current MALFUNCTION it s read only In case of the CURRENT VALUE shows as No E that means without malfunction while other information displaying means the relevant malfunction For detail please refer to TROUBLESHOOT MAINTENANCE BROCHURE or contact with After sales agent Provided that more the one malfunction occurs simultaneously only the minimal No of the erro...

Страница 11: ...s No P 12 Mode query Attribute identifier Data type Attribute value Read Write Object identifier BACnetObjectIdentifier Multistate input 3 R Object name CharacterString AC_QueryMode R Object type BACnetObjectType Multistate input R Description CharacterString QueryMode O Status text BACnet ARRAY N CharacterString Heat Cool Dehumidify Fanonly Auto Stop O 13 Fan speed query Attribute identifier Data...

Страница 12: ...n Software Edition CharacterString 1 0 R Protocol Edition Unsigned 1 R Protocol Correspondency Type Unsigned 3 R Protocol Service Support BACnetServiceSupport ReadProperty etc R Protocol Object Types Support BACnetObjectTypesSupport AnalogInput etc R Object Array BACnetArray n List all objects R Max length of APDU support Unsigned 1476 R Segmentation support BACnetSegmentation Segmented both 0 R L...

Страница 13: ...serviceBOOLEAN F R States number Unsigned 4 R States text BACnet ARRAY N CharacterString Low Middle High Stop O Time delay Unsigned 1 O Publicly type Unsigned 1701 O Event enable BACnetEventTransitionBits T T T O Affirm transform BACnetEventTransitionBits T T T O Notify Type BACnetNotifyType alarm O Operation instruction The CURRENT VALUE attribute of the selected object reflects the current FAN S...

Страница 14: ...1701 O Low valve value REAL 0 O High valve value REAL 250 O Width valve value REAL 1 O Enable valve value BACnetLimitEnable F T O Event enable BACnetEventTransitionBits T T T O Notify Type BACnetNotifyType alarm O Operation instruction The CURRENT VALUE attribute of the selected object reflects the current INDOOR UNIT QUANTITY it s read only 6 Compressor 1 current Attribute Identifier Data mode At...

Страница 15: ...elected object reflects the COMPRESSOR 2 ELECTRIC CURRENT it s unsettable The MINIMAL VALUE stands for the minimum electric current while the MAXMUN VALUE stands for the maximum electric current 8 Compressor 3 current Attribute Identifier Data mode Attribute value Read write Object Identifier BACnetObjectIdentifier Analog iutput 5 R Object Name CharacterString AC_ ICom3Current R Object Type BACnet...

Страница 16: ... VALUE shows as No E that means the system without protection while other information displaying means the other relevant protection For detail please refer to TROUBLESHOOT MAINTENANCE BROCHURE or contact with After sales agent Provided that more the one protection occurs simultaneously only the minimal No of the protection would be showed Thereinto the CURRENT VALUE displays as 1 means EO the CUR...

Страница 17: ...CURRENT VALUE shows as No P that means the system without protection while other information displaying means the other relevant protection For detail please refer to TROUBLESHOOT MAINTENANCE BROCHURE or contact with After sales agent Provided that more than one protection occurs simultaneously only the minimal No of the protection would be showed Thereinto the CURRENT VALUE displays as 1 means P0...

Страница 18: ...18 NOTES 6720862469 16 04 CLIMATE 5000 VRF 5 NOTES ...

Страница 19: ...CLIMATE 5000 VRF 6720862469 16 04 NOTES 19 ...

Страница 20: ...Bosch Thermotechnology Ltd CotswoldWay Warndon Worcester WR4 9SW All Enquiries 0330 123 3004 www bosch industrial co uk ...

Отзывы: