3.5.
BACnet setting
The BACnet network code represents only one of the BACnet
centralised controllers in the range between 0 to 65535. Once the
address has been set, the device will need to be reset for the changes
to be effective.
Each BACnet has a unique network number. This BACnet network
number is required when multiple BACnet or centralised controllers
are connected.
The calculation formula for the indoor and outdoor air conditioning
units are:
Device ID=BTXX;
B is the bus Number 0-3;
T means type 0-indoor unit,1-outdoor unit;
XX is the indoor unit Number 0-63 or outdoor unit 0-31;
3.6.
Factory Reset
To delete settings and return to factory setting, connect 1 and 2 of
485. This will restore factory settings of the BACnet.
4.
OBJECT TABEL
This device provides with different objects tables for the different
types of outdoor units which are in using for the VRF system. System
will automatically identify using outdoor unit and generate the BACnet
object.
4.1.
Indoor objects
This equipment provides with fourteen types of BACnet object, show
as the following table, for connecting with indoor unit using in the
Building Management System (BMS) or other system which suitable
for BACnet Protocol.
Number
Content
1
Device Information
2
Operation mode
3
Fan state
4
Preset Temperature
5
Indoor temperature
6
Set on time
7
Set off time
8
Swing function
9
Electric heater function
10
Malfunction state
11
Protection state
12
Mode query
13
Speed query
14
Temp set query
4 | OBJECT TABEL
6720862469 (16/04)
CLIMATE 5000 VRF