Operation instruction
The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 1 ELECTRIC CURRENT (it’s unsettable).
The MINIMAL VALUE stands for the MINIMUM ELECTRIC CURRENT, while the MAXMUN VALUE stands for the MAXIMUM
ELECTRIC CURRENT.
7) Compressor 2 current
Attribute Identifier
Data mode
Attribute value
Read/write
Object Identifier
BACnetObjectIdentifier
Analog-iutput 4
R
Object Name
CharacterString
AC_ ICom2Current
R
Object Type
BACnetObjectType
Analog-iutput
R
Current value
REAL
R
Description
CharacterString
Compressor 2 current
O
Status Flags
BACnetStatusFlags
F F F F
R
Event states
BACnet EventStates
Normal
R
Take off service
BOOLEAN
F
R
Unit
BACnetEngineering Units
Amperes
R
Minimum
REAL
0
O
Maximum
REAL
200
O
Time delay
Unsigned
1
O
Publicly type
Unsigned
1701
O
Low valve value
REAL
0
O
High valve value
REAL
200
O
Width valve value
REAL
1
O
Enable valve value
BACnetLimitEnable
T T
O
Event enable
BACnetEventTransitionBits
T T T
O
Notify Type
BACnetNotifyType
alarm
O
Operation instruction
The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 2 ELECTRIC CURRENT (it’s unsettable).
The MINIMAL VALUE stands for the minimum electric current, while the MAXMUN VALUE stands for the maximum electric
current.
8) Compressor 3 current
Attribute Identifier
Data mode
Attribute value
Read/write
Object Identifier
BACnetObjectIdentifier
Analog-iutput 5
R
Object Name
CharacterString
AC_ ICom3Current
R
Object Type
BACnetObjectType
Analog-iutput
R
Current value
REAL
R
Discription
CharacterString
Compressor 3 current
O
Status Flags
BACnetStatusFlags
F F F F
R
Event states
BACnet EventStates
Normal
R
Take off service
BOOLEAN
F
R
Unit
BACnetEngineering Units
Amperes
R
Minimum
REAL
0
O
Maximum
REAL
200
O
Time delay
Unsigned
1
O
Publicly type
Unsigned
1701
O
Low valve value
REAL
0
O
High valve value
REAL
200
O
Width valve value
REAL
1
O
Enable valve value
BACnetLimitEnable
F T
O
Event enable
BACnetEventTransitionBits
T T T
O
Notify Type
BACnetNotifyType
alarm
O
Operation instruction
The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 1 ELECTRIC CURRENT (it’s unsettable).
The MINIMAL VALUE stands for the minimum electric current, while the MAXMUN VALUE stands for the maximum electric
current.
9) Error states
CLIMATE 5000 VRF
6720862469 (16/04)
OBJECT TABEL
|
15
Содержание BMS-BAC
Страница 18: ...18 NOTES 6720862469 16 04 CLIMATE 5000 VRF 5 NOTES ...