BE 300 LSN 

4.998.099.747 A2 

User‘s Guide 

Message display/Editing 

External alarm, internal alarm, malfunctions........................... 17 
Display message .................................................................... 18 
Display faulted points.............................................................. 19 
Reset message....................................................................... 20 

Use of menus 

Notes on menu use................................................................. 21 
View all detectors.................................................................... 22 
View alarm counter ................................................................. 23 
View event log ........................................................................ 24 
Change own user code........................................................... 25 
Change user code for new user.............................................. 26 
Display/change date and time ................................................ 27 
SW version BE 300 and NZ 300, programming date .............. 28 
Display test ............................................................................. 29 

Bypass

..................................................................................... 30 

Enable/Disable detector

.......................................................... 31 

Walktest

................................................................................... 32 

Introduction, security and safety

............................................. 2

Display/Keys 

Explanation of displays ............................................................. 3
Explanation of keys................................................................... 4

User code/User authorization

 

Notes on user code................................................................... 6
Notes on coded mode............................................................... 7
User authorization..................................................................... 8

Arming/Disarming with BE 300 LSN (user code) 

Perimeter arm with door contact ............................................... 9
Perimeter arm ......................................................................... 10
Arming with door contact ........................................................ 11
Arming .................................................................................... 12
Disarming with door contact.................................................... 13
Disarming................................................................................ 14

Arming/Disarming with block-type lock 

Arming .................................................................................... 15
Disarming................................................................................ 15

Arming/Disarming with key switch 

Arming .................................................................................... 16
Disarming................................................................................ 16

Содержание BE 300 LSN

Страница 1: ...E 300 and NZ 300 programming date 28 Display test 29 Bypass 30 Enable Disable detector 31 Walktest 32 Introduction security and safety 2 Display Keys Explanation of displays 3 Explanation of keys 4 User code User authorization Notes on user code 6 Notes on coded mode 7 User authorization 8 Arming Disarming with BE 300 LSN user code Perimeter arm with door contact 9 Perimeter arm 10 Arming with doo...

Страница 2: ...the contents fast and reliably What do these operating instructions not tell you about They do not contain any basic or specific know how about secu rity techniques The only information contained on this subject is what you need for operating purposes Therefore make sure you are familiar with all security proce dures and regulations in your sector eg if there is an alarm The equipment should only ...

Страница 3: ...uzzer Keys These keys are explained on the next page Display panel LCD The display consists of two lines with 16 alphanumeric characters illuminated in dialog The display shows all pending messages plus indicators The sign on the display indicates that several messages are pre sent If the keypad unit is on standby ie no messages have arrived and no operation is initiated the display shows the stan...

Страница 4: ...of the alarm system Use this key to reset faulted points of all areas to which a user has access Use this key and the user code to call up the walk test Use this key to show faulted points armed parti tions and malfunctions Use this key to enter coded mode Use this key to terminate coded mode and to clear the walk test Explanation of keys Display Keys Reset 6 Clear Disable 5 Arm 2 Bypass 4 Perimet...

Страница 5: ...ing keys can be used to move the cursor to the left or right The keys can also be used to scroll up and down through messages on the display and through menus to show them on the display Use this key to confirm an entry eg after entry of the user code Use the keys 0 through 9 to enter digits eg a user code Press any key to turn off the buzzer Explanation of keys Display Keys Menu 0 Escape Menu 0 9...

Страница 6: ...t be changed The user number is entered before the user password and appears on the display User password The user password consists of between two and six digits the minimum number of digits is defined in programming and is the same for all users The user password can be changed and the entry does not appear on the display Initially each user defines his own password Initial definition of user co...

Страница 7: ...g on the operation the display automatically prompts Enter code In further operations the user code no longer has to be entered To perform an operation for which the user code is necessary the user code is entered first for an example refer to chapter Notes on menu use 1 2 3 Entering user code Press the Code key Enter your user code user number user password eg 02 Confirm your entry with the OK ke...

Страница 8: ...X X Reset tamper X X Walktest X X X Change own user code X X X X Change user code for new user X X Display change date and time X X View backup memory X X X View alarm counter X X X Display faulted detector X X X X X Display detector X X X X X View SW version X X X X X View programming date X X X X X Notes on table X operations firmly assigned to user user is authorized to operate P operations can...

Страница 9: ...e internal program is started The door contact is not activated until after the activation de lay The buzzer sounds at intervals during the delay faster for the last 10 s The room must be left in this delay Coded mode is no longer active after activation and the standby image appears on the display Perimeter arm with door contact Arming Disarming with BE 300 LSN user code Perimeter arm Code Perime...

Страница 10: ...is necessary if there is only one internal program continue to point 4 4 Press the OK key Activation of the internal program is started After activation the standby image appears on the display Perimeter arm Arming Disarming with BE 300 LSN user code Perimeter arm IP 2 Perimeter arm in preparation NZ 300 LSN BOSCH Perimeter arm All IPs Perimeter arm Code Perimeter 1 OK OK ...

Страница 11: ...essary if there is only one areas continue to point 4 4 5 Press the OK key Activation of the areas is started The door contact is not arm until after the arming delay The buzzer sounds at intervals during the delay faster for the last 10 s The room must be left in this delay Coded mode is no longer active after arming and the standby image appears on the display Arming with door contact Arming Dis...

Страница 12: ...or activation No se lection is necessary if there is only one areas continue to point 4 4 Press the OK key Activation of the areas is started After arming the standby image appears on the display Arming Arming Disarming with BE 300 LSN user code Arm areas 2 Arm in preparation NZ 300 LSN BOSCH Arm All areas Arm Code Arm 2 OK OK ...

Страница 13: ... 10 s Press the Disarm key The buzzer goes off The display shows perimeter disarm or disarm Enter the user code and confirm your entry with the OK key All areas of the user are disarmed The standby image ap pears on the display Disarming with door contact Arming Disarming with BE 300 LSN user code Disarm in 15 s Disarm Code NZ 300 LSN BOSCH Disarm 3 OK ...

Страница 14: ...ump to point 4 if there is only one area in ternal program Use the paging keys to call up the areas internal programs for disarming 4 Press the OK key Disarming is activated and the standby image appears on the display Disarming Arming Disarming with BE 300 LSN user code NZ 300 LSN BOSCH OK Disarm areas 3 Disarm Code Disarm 3 Disarm All areas IPs OK ...

Страница 15: ...ck type lock Notes If arming is not possible a triggered detector can be exempted from surveillance refer to chapter By pass The areas must not be on a walktest when armed 1 2 Open the block type lock After disarming of the areas this will be signaled by a buzzer or LEDs on the block type lock Open the door NZ 300 LSN is on disarmed standby Disarming Arming Arming Disarming with block type lock NZ...

Страница 16: ...rted during the delay by operating the key switch again After arming the standby image appears on the display 1 2 Triggering a door detector produces a display of the time left until disarming The buzzer sounds at intervals faster for the last 10 s Operate the key switch The areas is disarmed The standby image appears on the display NZ 300 LSN BOSCH Disarming Arming Arming Disarming with key switc...

Страница 17: ...sages eg fire Priority 3 malfunctions Priority 4 disable bypass Number of messages The sign on the display indicates that several messages are present Turn off buzzer Use any key to turn off the buzzer of BE 300 LSN Turn off external sounder External sounders are turned off by disarming or automatically after max 180 s Alarm On ALARM 15 35 Office Mills R 106 Malfunction Reset 6 Menu 0 Clear Disabl...

Страница 18: ...elong to the user areas and the areas of BE 300 LSN Duress alarms messages are displayed 1 2 Use the paging keys to scroll up and down through messages on the display Every 2 s the display changes between time and date Further operations Refer to chapter Bypass Refer to chapter Enable Disable detector Display message Message display editing Intrusion 14 55 Detector 12 Intrusion 19 09 Detector 12 ...

Страница 19: ...eas and to the areas of BE 300 LSN 1 2 3 Press the Status key The detector number and type of mes sage are displayed Use the paging keys to scroll up and down through the faulted points Detectors are displayed in the order of their program ming Further operations Refer to chapter Bypass Refer to chapter Enable Disable detector Display faulted points Message display editing Malfun Detector 1 Intrus...

Страница 20: ...e the procedure is as described in the right column above If you are already in coded mode the procedure is as described in the right column below Use the Clear key to quit coded mode 1 2 1 2 Press the Reset key Enter your user code and press the OK key All faulted points of all disarmed user areas are reset The messages on the display extinguish as soon as all reset detectors are on standby Press...

Страница 21: ...ss the Menu key The first menu View detector is displayed Use the paging keys to scroll up and down through the menus Call up the selected menu with the OK key Notes on menu use Use of menus Menu View detector Menu SW version BE 300 Menu SW version NZ 300 Menu Programming date SW software up dow Menu Test display Menu View detector Menu Alarm counter Menu Event log Menu Change code Menu Date time ...

Страница 22: ...u View detector is displayed Press the OK key The status of the first detector is displayed 4 5 Use the paging keys up and down to call up the detec tors and their status one after the other The detectors are displayed in the order of their programming Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit the menu or coded mode with the C...

Страница 23: ...Press the OK key The alarm counter is displayed The alarm counter cannot be deleted Maximum entry up to 9999 then restarting at 1 5 Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit the menu or coded mode with the Clear key The standby image appears on the display View alarm counter Use of menus NZ 300 LSN BOSCH Menu View detector C M...

Страница 24: ...display changes between time and date every 2 s 5 6 If there are more events max 1024 in event log you can call them up with the paging keys Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit coded mode with the Clear key The standby image ap pears on the display View event log Use of menus NZ 300 LSN BOSCH Intrusion 13 45 Detector 6 M...

Страница 25: ...er point 1 and appear on the display The re maining digits do not appear on the display Confirm your entry with the OK key Enter the new user code once again and confirm your entry with the OK key The new user code is saved Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit coded mode with the Clear key The standby image appears on the...

Страница 26: ...nter a new user password this entry does not appear on the display user code user number user password Confirm your entry with the OK key 4 5 Enter the new user code once again user code user number user password and confirm your entry with the OK key The new user code is saved Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit coded m...

Страница 27: ...t to be changed 6 7 8 Overwrite the digit to be changed Press the OK key The date and time are read into NZ 300 LSN Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit coded mode with the Clear key The standby image ap pears on the display Display change date and time Use of menus Menu Date time NZ 300 LSN BOSCH Menu View detector C C 2...

Страница 28: ...ct the SW version BE 300 or SW version NZ 300 or Programming date menu Press the OK key 4 Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit the menu or coded mode with the Clear key The standby image appears on the display SW version BE 300 and NZ 300 programming date Use of menus Menu SW version NZ 300 SW version NZ 300 V 1 2 15 04 0...

Страница 29: ...Test display menu Press the OK key The buzzer sounds The Operative LED extinguishes the Alarm and Malfun LEDs illuminate Use any key to turn off the buzzer 5 Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit the menu or coded mode with the Clear key The standby image appears on the display Display test Use of menus Menu Test display M...

Страница 30: ... exempted from surveillance By pass Refer to the chapters above for details Press the Code key Enter the user code and confirm your entry with the OK key 3 4 5 6 7 Press the Bypass key Press the OK key Detector 10 is exempted from surveil lance Other faulted detectors can also be exempted with By pass Quit coded mode with the Clear key Arm the system After disarming the detector is automatically i...

Страница 31: ... the Code key Enter the user code and confirm your entry with the OK key 3 4 5 Press the Disable key Press the OK key Detector 10 is disabled Other detectors can also be disabled with the Disable key Quit coded mode with the Clear key Enable When detectors are to be enable again the steps are analo gous to disabling as explained here The Disable key is then used to enable Enable Disable detector N...

Страница 32: ... the areas This is shown on the display and entered in event log 4 5 Press the OK key You see how much time remains for the walktest Press the Escape or Clear key The Escape key takes you back one step Further operations are then possible or Quit coded mode with the Clear key The standby image ap pears on the display Walktest Walk 12 Detector 012 Walktest Code NZ 300 LSN BOSCH Walktest Active 15 m...

Отзывы: