background image

RADION receiver SD

Table of contents | en

5

Bosch Security Systems B.V.

2020.05 | 13 | F.01U.261.834

17.1

RADION keyfob FB

86

17.2

RADION keyfob TB

87

18

RADION panic FP

89

19

Appendices

91

Содержание B810-CHI

Страница 1: ...RADION receiver SD B810 en Installation manual ...

Страница 2: ......

Страница 3: ...power level for RADION devices 13 3 2 Certifications and approvals 14 3 3 UL product requirements 18 3 4 Installation 22 3 4 1 Configuration 22 3 4 2 Base installation 24 3 4 3 Wiring considerations 25 3 4 4 Programming wireless points in the control panel 26 3 4 5 Enroll point RF ID for wireless points Auto learn mode 29 3 4 6 Walk test for motion detectors 30 3 4 7 Signal level and margin 31 3 4...

Страница 4: ...Walk testing 61 9 RADION smoke RFSM2 63 10 RADION CO 64 11 RADION heat 65 12 RADION smoke 66 12 1 Battery replacement 68 12 2 Smoke test 68 12 3 Sensitivity test 68 12 4 Test Silence button 69 12 5 LED 70 12 6 Clean the detector and replace the optical chamber 70 13 RADION contact SM 72 13 1 Installation considerations 73 14 RADION contact RM 75 14 1 Installation considerations 76 15 RADION specia...

Страница 5: ...RADION receiver SD Table of contents en 5 Bosch Security Systems B V 2020 05 13 F 01U 261 834 17 1 RADION keyfob FB 86 17 2 RADION keyfob TB 87 18 RADION panic FP 89 19 Appendices 91 ...

Страница 6: ... is constructed in a manner that is systematic and sequential for the installer on a point of need basis The following represents a basic outline of that information Chapter 1 this chapter introductory information and how to use this document Chapter 2 basic RADION system wide general installation information and workflow check list Chapter 3 RADION receiver specific installation information Remai...

Страница 7: ...documentation Copyright This document is the intellectual property of Bosch Security Systems Inc and is protected by copyright All rights reserved Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly 1 2 Bosch Security Systems Inc product manufacturing dates Use the serial number located on the product label...

Страница 8: ...pecifications and the radio frequency signal strength RFSS between devices receivers and control panels Installation considerations RADION devices are intended only for indoor dry applications Mount RADION devices on flat rigid surfaces Some devices can be optionally corner mounted as indicated in the installation instructions Avoid mounting RADION devices in areas with large metallic objects elec...

Страница 9: ...ging the transformer and disconnecting the battery Plan the installation of the RADION system Install the RADION components refer to the graphical installation guides and this system reference guide for details Program wireless points in the control panel Enroll point RF ID for wireless points Verify LED responses on devices Perform a local walk test for installed detectors Review signal strength ...

Страница 10: ...contain a feature that activates the wall tamper switch located on the base of the device In order to properly install the device you must consider the following To properly install a device with active wall tamper functionality insert a screw in the designated screw slot location Failure to insert a screw into the wall tamper slot prevents the wall tamper feature from generating a tamper signal w...

Страница 11: ...rforming an overall service walk test Refer to your control panel documentation for system walk or other system wide testing procedures To ensure proper operation of the RADION devices test the basic functionality of the device locally Depending on the RADION device to be tested perform the following procedures for functionality When testing the receiver power up the compatible control panel in wh...

Страница 12: ... This will ensure proper operation and functionality of the devices Battery Life Extension feature PIR and TriTech In the normal operating mode an alarm can be transmitted only after three 3 minutes have passed since the previous alarm restoral This 3 minute lockout time reduces unnecessary RF transmissions in high traffic areas thereby extending battery life ...

Страница 13: ...ces come in three varieties and are compatible with three RADION receivers The three varieties are A versions ex RFRP A Non A versions ex RFRP or CHI versions ex RFRP CHI Each variety of detector was originally designed for a certain geographical region and catered to that specific region s regulatory requirements The B810 receiver supports all device versions The slight differences are described ...

Страница 14: ... the check in interval is 13 minutes The following table shows check in intervals and power levels for all RADION devices within the B810 wireless receiver security system Check in differences between A and non A RADION devices Item A version Non A CHI version Devices affected Check in interval 65 minutes 13 minutes All RADION devices Power level for check in messages 3 db less than alarm message ...

Страница 15: ...A smoke detector RFHT A heat detector RFCO A CO detector RFKF TB A keyfob RFKF FB A keyfob RFPB TB A panic RFPB SB A panic RFPB FP A fixed position panic RFKF FBS A keyfob RFKF TBS A keyfob Products not evaluated by UL The following products have not been evaluated by UL RFGB A RFGB RFGB CHI glassbreak RFRP RFRP CHI repeater RFBT RFBT CHI specialty billtrap RFDW SM RFDW SM CHI standard door window...

Страница 16: ...refer to your supported control panel documentation Federal Communications Commission FCC Rules This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This equipment has been tested and fo...

Страница 17: ...may cause undesired operation of the device Le présent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux conditions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettr...

Страница 18: ...UL product requirements Notice For all wireless devices receivers and or repeaters do not install on removable surfaces such as ceiling tiles For product specific UL requirements refer to desired product title below for more information RADION Repeater When selecting a suitable 16 5 VAC Class 2 plug in transformer the following transformers are suggested MG Electronics MGT 1640 Codex SEP 1640 The ...

Страница 19: ...follows Power voltage Standby Battery Rated 3 7 VDC 3050mAH EVE ENERGY CO Part No P0046 LF Not user replaceable Notice For standby battery to be operative the tamper switch is required to be engaged Standby battery is capable of providing 72 hours of standby power to the RF repeater for a UL Burglar Alarm Installation Bank Safe and Vault 24 Hours for Household Fire Warning Systems 8 Hours for HOLD...

Страница 20: ...ROL UNIT PLUS SMOKE DETECTORS SHALL NOT EXCEED 60 SECONDS NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION RADION contact SM During the installation of the device UL installations primary securement means shall be screws RADION contact RM During the installation of the device UL installations primary securement means shall be s...

Страница 21: ...sal transmitter During the installation of the device the following items are required by UL For UL installations an UL Listed burglar alarm dry contact device shall be connected if the external terminal is used When external contact is configured for UL hold up installations a hold up device such as potter electric model HUB is to be connected to the external contact For programming refer to the ...

Страница 22: ...urement means shall be screws RADION keyfobs To comply with UL 1023 RADION keyfobs shall be programmed with Forced Arm Bypass Max set to 0 3 4 Installation Use the anchors and screws to install the receiver in locations accessible for future maintenance Install the receiver onto a wall For best performance place the receiver in a central location among the transmitters For optimal communication re...

Страница 23: ...invalid and will cause the receiver to enter into an SDI2 communication error state This causes the receiver to be unrecognized by the control panel The receiver uses Address 9 to reset itself when the keyfob becomes inoperable Refer to the Notice below and procedure regarding the synchronization of the keyfob with the receiver Refer to your control panel documentation for information on the valid...

Страница 24: ...eiver from its base 2 Set the receiver address switch to 9 3 Power on the receiver or re attach the receiver to its base 4 LED indicates the firmware version The LED turns on steady for a short time to reset the receiver and then turns off Replace the receiver if the LED continues to flash 5 Power off the receiver or remove the receiver from its base 6 Set the receiver address switch back to the o...

Страница 25: ...he cover removed Other mounting considerations include Minimum clearance above the location to compensate for the vertical sliding movement to attach or remove the device from the base is 30 mm 1 2 in Minimum clearance below the location where the base is mounted 23 mm 0 9 in 3 4 3 Wiring considerations Notice Do not install long cable runs next to high current power feeds Keep cable lengths as sh...

Страница 26: ...Callout ᅳ Description 1 ᅳ SDI2 compatible control panel 2 ᅳ Terminal wiring 3 ᅳ RADION receiver SD mounting base 4 ᅳ Module terminal block 3 4 4 Programming wireless points in the control panel Configure the RADION points to establish communication between the RADION system and the control panel This can be accomplished by using one of two methods Using Remote Programming Software RPS on a support...

Страница 27: ...ocess Refer to the Points Menu Parameters section inside the Keypad Installer Menu chapter of the compatible Bosch control panel Installation and System Reference Guides or Points Point Assignments in RPS Help File for more information Point source RFID programming A point s source gives a description as to the physical location of the point for installation and service personnel 1 Using either RP...

Страница 28: ...xes Point indexes determine how points operate respond to circumstances within a system 1 Using either RPS or a supported keypad access the Program Menu and select the Points menu 2 Select the point source of the device you are programming and select the wireless device type Ensure that it matches that of the physical device you are enrolling 3 Assign the attributes of the point index how the devi...

Страница 29: ...keyfob buttons are pressed then released Motion detectors when the battery is inserted or if coverage pattern is disturbed by someone walking through the coverage pattern field Notice The Auto Learn mode option is not recommended as the preferred method of entering in the RF ID s due to the potential of the RADION system picking up the first available RF ID it detects For optimal results manually ...

Страница 30: ...edure to test the detector range and functionality Notice Also see Control Panels D9412GV4 D7412GV4 SIA CP 01 Quick Reference Guide P N F 01U 265 466 and or B6512 B5512 B4512 SIA CP 01 Quick Reference Guide P N F 01U 265 464 Motion walk test Remove and replace cover to activate a 90 sec Walk Test Mode During this Test Mode any activity in the sensor s coverage pattern will cause a transmitted alar...

Страница 31: ...ed In this test you are verifying the distances of which the magnet engages and disengages the transmitter 3 4 7 Signal level and margin The signal level and margin ambient signal of the RADION system is dependent on the receiver location and transmitters communicating with it Installing the receiver in an environment that has a lot of radio transmitter communication or other exterior disturbances...

Страница 32: ...y transmitter including repeaters should be tested and verified to be reporting good at the time of installation and in the unlikely event of a interference trouble report Signal strength test for Points and Receiver Use the following procedure to test the frequency strength and range of the RADION system 1 From the keypad access the Wireless Menu and select Diagnostics 2 Select RF Points 3 Select...

Страница 33: ...e every year including the B810 receiver by an installer to ensure proper functionality of the RADION system 3 5 External LED states The receiver utilizes the External LED to show various states of the receiver These states fall into the following three categories Normal State Communication Error State Trouble State Maintenance state Off state Normal state The receiver enters a normal state when i...

Страница 34: ... ID while in Learn Mode Communication error state The receiver enters a communication error state when during power up it does not establish a link with the control panel or has been in an idle state for more than 30 sec without communication Another cause for a communication error state is an invalid address switch setting 0 or 9 LED condition State description 3 pulse flash A 3 pulse signal foll...

Страница 35: ...le state experiencing a radio frequency interference failure A communication failure with internal hardware components within the receiver Maintenance state The receiver enters a maintenance state when the address switch settings are set between switch 5 switch 8 LED condition State description Continuous Flash A continuous pattern of short off time followed by long on time Indicates the receiver ...

Страница 36: ...n from a RADION transmitter Continuous Flash A 3 pulse signal followed by a short delay at the end of the 3rd pulse Communication error Indicates the receiver has experienced a communication error and or a self test failure This error could be a result of either A communication failure between the control panel and receiver or An invalid address switch setting Continuous Flash A continuous pulse b...

Страница 37: ...staller Operating environment 0゚C to 49゚C 32゚F to 120゚ F Relative humidity Up to 93 non condensing Frequency 433 42 MHz Wiring distance Maximum distance of 243 m 800 ft from the control panel Wiring gauge 0 65 mm 22 AWG to 2 0 mm 18 AWG maximum Wall and cover tamper switch Transmits a tamper signal when someone removes the device from its base or pulls it away from the wall Tab 3 2 Specifications ...

Страница 38: ...ate Replace battery with battery manufacturer s name or end product manufacturer s name and part number only Use of another battery might present a risk of fire or explosion Battery requirements RADION Device Battery Size Battery Type Cell Voltage Quantity Cells B810 receiver None RADION PIR motion detector CR123A Lithium 3 VDC 1 RADION PIR C motion detector CR123A Lithium 3 VDC 1 RADION repeater ...

Страница 39: ... trap AAA Lithium 1 5 VDC 1 RADION TriTech motion detector AA Alkaline 1 5 VDC 4 RADION contact RM recessed door window contact AAA Lithium 1 5 VDC 1 RADION contact SM standard door window contact AAA Lithium 1 5 VDC 1 RADION glassbreak detector CR123A Lithium 3 VDC 1 RADION keyfob FB key fobs CR2032 coin cell Lithium 3 VDC 1 RADION keyfob TB key fobs CR2032 coin cell Lithium 3 VDC 1 ...

Страница 40: ... Size Battery Type Cell Voltage Quantity Cells RADION panic TB RADION panic SB panic buttons CR2032 coin cell Lithium 3 VDC 1 RADION panic FP panic button CR123A Lithium 3 VDC 1 RADION Smoke and Heat CR123A Lithium 3 VDC 2 RADION Heat CR123A Lithium 3 VDC 2 RADION CO AAA Alkaline 1 5 VDC 2 Tab 3 3 Battery requirements ...

Страница 41: ...he specification table for the repeater Do not connect power supply to a receptacle controlled by a switch Notice When used in a life safety application such as in a fire warning system at least two repeaters must be used to provide redundant communication paths Perform the Redundant Verification Process Redundant Communication verification process 1 Build a network of repeaters 2 Remove AC and ba...

Страница 42: ...in a location removed from metal Metal objects duct work wire mesh screens boxes reduce RF range 4 2 Wiring considerations Notice Do not install long cable runs next to high current power feeds Keep cable lengths as short as possible to minimize noise pickup Ensure that the wiring used meets the following specifications Two conductor unshielded wire The minimal requirement for wire length is 1 83 ...

Страница 43: ... Hz secondary rated 18 VAC 1 22 Amps 22 VA For installations other than the U S transformers must meet the country specific requirements Power voltage 16 5 V to 18 V 40 VA Standby battery This component is internal and not user replaceable Typical current draw 60 mA Wire gauge 0 65 mm 22 AWG to 2 0 mm 18 AWG Temperature operating Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F...

Страница 44: ...receiver is not wired correctly Continuous Flash 1 sec rate for 5 sec Indicates the repeater is being powered up and conduction manufacturing test initializations Continuous Flash A 3 pulse signal followed by a short delay after the 3rd pulse Indicates the repeater has experienced a low battery condition Continuous Flash A 2 flash pattern continuous pulse between On and Off states with a short del...

Страница 45: ...RADION receiver SD RADION repeater en 45 Bosch Security Systems B V 2020 05 13 F 01U 261 834 ...

Страница 46: ... 38 in Power Voltage Battery CR123A 3 VDC Power source type C Low battery level 2 15V Battery replacement Duracell DL123A Lithium Panasonic CR123A Lithium or Sanyo CR123A Lithium Check your battery yearly to ensure proper functionality Battery life Up to 5 years Device testing To ensure proper functionality the device must be tested at least once every year Accoustic Capabilities Glass types and t...

Страница 47: ...y 433 42 MHz Tab 5 6 Specifications 5 1 Installation considerations For the best detector performance select a mounting location that is Mounted on the ceiling within a maximum range of 20 ft 6 m For armor coated glass installations mount the sensor no more than 12 ft 3 65 m from the glass Mount the detector in the direct line of sight of the glass to be protected On an opposite or adjoining wall ...

Страница 48: ...throoms and Small acoustically live rooms Notice Glassbreak detectors are intended only as a component of a perimeter protection system Use glassbreak detectors in conjunction with motion detectors 5 2 Testing Test the detector at least once yearly Use the Sentrol 5709C hand held tester to enter the sensor into test mode and to test the alarm Test the sensor alarm To test the sensor functionality ...

Страница 49: ... hand held tester 1 Hold the tester near the surface of the glass to be protected and aim the speaker at the sensor Be sure the tester is at the point on the glass farthest from the detector Notice If blinds or drapes are present test the area by holding the hand held tester behind the closed blinds or drapes 2 Press the test button on the tester The LED on the detector stays on for 4 seconds to i...

Страница 50: ...lly extend the range of a glassbreak sensor The specified sensor range is for worst case conditions While the sensor likely functions at a greater range it might not detect a low volume breaking sound or room acoustics might change at a later point in time Do not exceed the rated range of the sensor regardless of what the tester shows Test the sensor operability When the detector is in normal mode...

Страница 51: ...ce 5 3 Low battery When a low battery state is detected the detector measures the battery and sends a report to the receiver control panel 5 4 Wall Tamper Tab Use the wall tamper tab to activate an alarm when the glass break has been removed from the wall 5 5 Maintenance Clean the cover with a damp water cloth as needed to keep it free of dust and dirt Always test the sensor after cleaning it ...

Страница 52: ...nting height Compatible with Bosch RADION wireless systems Draft and Insect immune Cover activated tamper indication Optional wall activated tamper is included Dimension 138 00 mm x 72 00 mm x 64 00 mm 5 43 in x 2 83 in x 2 52 in Relative humidity 0 to 93 non condensing Temperature operating Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F to 120゚ F Internal coverage directiona...

Страница 53: ...ne removes the device from its base or pulls it away from the wall Frequency 433 42 MHz Table 6 7 Specifications 6 1 Mounting height and range adjustment Loosen the vertical adjustment screw Adjust the board to the desired angle Choose mounting height and desired range and set the vertical angle Reference the table below for proper height and adjustment values Mounting height Range 6 1 m 20 ft 10 ...

Страница 54: ...e battery life the LED elements do not activate unless the unit is in the Walk Test mode Perform a walk test to determine the boundaries of the coverage area Perform this test at the time of installation and monthly thereafter To ensure continual daily operation instruct the end user to walk through the far end of the coverage pattern This ensures an alarm output prior to arming the system Start W...

Страница 55: ...e below for LED descriptions LED Condition Cause Steady LED PIR activation Walk Test Steady green Microwave activation Steady blue Alarm signal Flashing blue Warm up period after power up No LED upon initial power up PIR failure Replace unit Tab 6 9 LED description Walking Testing the system 1 Start at the pattern s expected boundary and walk across the pattern moving closer to the detector Set th...

Страница 56: ...D blue green or red 2 ᅳ Microwave Range Adjustment Potentiometer 3 At each pass observe the color on the Alarm LED refer to the Sensitivity settings figure above 4 Walk test from the opposite direction to determine the coverage pattern boundaries from both sides 5 When walk test is completed the detector returns to normal operation after 90 sec of inactivity ...

Страница 57: ...40 in x 2 40 in x 1 70 in Relative humidity 0 to 93 non condensing Temperature operating Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F to 120゚ F Power voltage One CR123A Lithium battery 3 VDC Power source type C Low battery level 2 15V Battery replacement Duracell DL123A Panasonic CR123A or Sanyo CR123A Check your battery yearly to ensure proper functionality Battery life Up...

Страница 58: ...ea causes a transmitted alarm and LED activation Each alarm will also extend the Test Mode Adjust as necessary Notice Excessive use of the Walk Test Mode may reduce battery life Use only for initial setup and maintenance testing Notice In the normal operating mode an alarm can be transmitted only after three 3 minutes have passed since the previous alarm restoral This 3 minute lockout time reduces...

Страница 59: ...ove 2 While the detector is in the Walk Test Mode turn ON all heating and air conditioning sources which would normally be active during the protection period Stay away from the sensor and outside the coverage pattern and watch for alarms 3 The LED flashes at the completion of a 90 sec span of time indicating that the Walk Test mode is ending This occurs when there is no activity in the sensor s c...

Страница 60: ...n coverage Flexible Mounting Height Dimensions 111 00 mm x 60 00 mm x 43 00 mm 4 40 in x 2 40 in x 1 70 in Relative humidity 0 to 93 non condensing Temperature operating Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F to 120゚ F Power voltage One CR123A Lithium batteries 3 VDC Power source type C Low battery level 2 15V Battery replacement Duracell DL123A Panasonic CR123A or Sa...

Страница 61: ...ea causes a transmitted alarm and LED activation Each alarm will also extend the Test Mode Adjust as necessary Notice Excessive use of the Walk Test Mode may reduce battery life Use only for initial setup and maintenance testing Notice In the normal operating mode an alarm can be transmitted only after three 3 minutes have passed since the previous alarm restoral This 3 minute lockout time reduces...

Страница 62: ...bove 2 While the detector is in the Walk Test Mode turn ON all heating and air conditioning sources which would normally be active during the protection period Stay away from the sensor and outside the coverage pattern and watch for alarms 3 The LED flashes at the completion of a 90 sec span of time indicating that the Walk Test mode is ending This occurs when there is no activity in the sensor s ...

Страница 63: ...detector is sensitive to all domestic fire types but is especially sensitive to smoldering fires and is ideal for bedrooms and children s rooms The RFSM2 A smoke detector also includes a fixed and rate of rise heat sensor for fire detection 3 1 4 2 Callout Description 1 Mounting plate 2 Test Silence button 3 LED 4 Sounder For more information refer to the RADION Life Safety Installation Manual P N...

Страница 64: ... sensor that senses the presence of toxic carbon monoxide gases A red LED flashes when carbon monoxide is detected When higher levels are detected the alarm sounds ALARM FAULT POWER 1 2 B16980 2 3 4 Callout Description 1 LEDs 2 Test Silence button 3 Sounder 4 Mounting plate For more information refer to the RADION Life Safety Installation Manual P N F 01U 361 555 ...

Страница 65: ... locations for this detector include kitchens and other areas where there is normally some level of smoke or fumes and where smoke alarms might be subjected to false alarms due to an excessively dirty environment 3 1 4 2 Callout Description 1 Mounting plate 2 Test Silence button 3 LED 4 Sounder For more information refer to the RADION Life Safety Installation Manual P N F 01U 361 555 ...

Страница 66: ... LED changes from flashing to steady ON and the sounder produces a loud continuous tone Refer to the LED table for more information Replaceable optical chamber For easy maintenance Power voltage Two CR123A Lithium batteries 3 VDC Power source type C Low battery level 2 15V Current draw Standby 45 uA Alarm 70 mA Battery replacement Duracell DL123A Panasonic CR123A or Sanyo CR123A Check your batteri...

Страница 67: ...nsing Cover and wall tamper switch Transmits a tamper switch signal when the detector is removed from its base or the unit is pulled away from the wall Drift compensation adjustment 1 64 m 0 5 ft maximum Sounder 85 dBA at 3 m Self diagnostics feature Monitors detector sensitivity and operational status Frequency 433 42 MHz Tab 12 14 Specifications 1 2 Figure 12 1 Smoke detector 1 ᅳ High intensity ...

Страница 68: ...moke tester to simulate an alarm Follow the instructions on the can The LED should remain ON while the detector provides a continuous tone The detector automatically resets when smoke is no longer present A detector that fails to activate with the smoke test might require cleaning or replacement Notice To avoid a fire department dispatch contact central monitoring station or put the system into Te...

Страница 69: ...mal sensitivity settings 8 to 9 Detector is becoming too sensitive Confirm that the smoke chamber is snapped down securely Clean the sensor and re test Tab 12 15 Smoke detector sensitivity conditions 12 4 Test Silence button Refer to the RADION smoke detector illustration for location of the Test Silence button Testing Press the Test Silence button for 4 sec The detector performs a Sounder test an...

Страница 70: ...ing an alarm OFF Malfunction replace the batteries clean the detector or replace the optical chamber as required Tab 12 16 LED 12 6 Clean the detector and replace the optical chamber Clean the detector cover with a dry or damp cloth as needed to keep it free from dust and dirt Clean the detector interior at least yearly Cleaning the detector 1 Remove the detector from the mounting base 2 Remove th...

Страница 71: ...irt from the smoke chamber base 6 Align the optical chamber with the base and snap down into place 7 To attach the detector cap line the cap up with the detector press the cap onto the detector and turn clockwise to snap it firmly into place 8 Observing the proper polarity install the batteries and the battery cover If the batteries are not installed properly the detector will not fit onto the mou...

Страница 72: ...rgizer L92 Check your battery yearly to ensure proper functionality Battery life Up to 5 years Device testing To ensure proper functionality the device must be tested at least once every year by an installer Dimensions transmitter 19 50 mm x 82 55 mm x 12 80 mm 0 76 in x 3 25 in x 0 50 in Dimensions magnet 24 5 mm x 18 5 mm x 12 5 mm 0 97 in x 0 72 in x 0 49 in Temperature operating Functional ran...

Страница 73: ...vice onto Failure to do so will make it extremely difficult to access and open the device for maintenance purposes In some cases you might need an additional spacer when installing the transmitter and magnet in the corner of a recessed door or window frame to close the gap in height between the magnet and transmitter For additional security you can use an adhesive with the screws to secure the tra...

Страница 74: ...djacent to the transmitter How to read the Graphical Magnet Distances table Contained in the RADION contact SM Installation Guide is a graphical table along with the X ᅳ Y ᅳ Z coordinates graphic Use the table in conjunction with the graphic to determine desired distances between the magnet and the transmitter based on the type of installation wood or metal Notice The content in the Installation G...

Страница 75: ... VDC Power source type C Low battery level 0 9V Battery replacement Energizer L92 Check your battery yearly to ensure proper functionality Battery life Up to 5 years Device testing To ensure proper functionality the device must be tested at least once every year by an installer Dimensions transmitter 19 00 mm x 104 80 mm 0 75 in x 4 12 in Dimensions magnet 22 mm x 28 mm x 15 mm 0 87 in x 1 10 in x...

Страница 76: ...r housing When reinserting the plastic top verify that the top fits into the designed grooves of the transmitter housing When installing the transmitter in an overhead location be mindful that the PCB assembly may fall out of the transmitter housing The removal of the plastic flaps is optional depending on your installation needs For added security you can use an adhesive with the screws to secure...

Страница 77: ...rief illumination of LED to signify armed and operational status Wall tamper alarm when removed from the cash drawer Dimensions 48 80 mm x 154 10 mm x 23 60 mm 1 92 in x 6 06 in x 0 93 in Power voltage 1 5 VDC Lithium Power source type C Low battery level 0 9V Battery replacement Energizer L92 Replace your battery yearly to ensure proper functionality Battery life Up to 5 years Device testing To e...

Страница 78: ...nk vault at the close of each business day In this scenario the bank vault system is always armed and the bill trap remains in a non faulted condition It is recommended to use the 3M double sided tape when inserting into the cash drawer In other occasions the bill trap itself may be removed from the cash drawer at the end of a workers shift In this situation the bill trap unit will generate a tamp...

Страница 79: ...ming the following 1 Separate the Velcro strips from one another 2 Peel off the protective backing of the Velcro strips 3 Press the two bottom sections of the Velcro onto the bottom of the cash drawer in the desired location 4 Line up and press down on the bill trap so that the Velcro on the bottom of the bill trap is aligned with the Velcro strips inside the cash drawer Warning It is important to...

Страница 80: ...nsions magnet 24 50 mm x 18 50 mm x 12 50 mm 0 97 in x 0 72 in x 0 49 in Wire gauge 0 65 mm 22 AWG to 1 5 mm 16 AWG Wiring distance Maximum distance of 7 62 m 25 ft Power voltage Lithium battery 3 VDC Power source type C Low battery level 2 15V Battery replacement One Duracell DL123A or Panasonic CR123A or Sanyo CR123A Check your battery yearly to ensure proper functionality Battery life Up to 5 y...

Страница 81: ...pulls it away from the wall Frequency 433 42 MHz Tab 16 20 Specifications Single EOL Resistor Option Use a 2 2 kᅳΩ EOL resistor Refer to the diagram below 2 1 3 Figure 16 1 Single EOL resistor option 1 ᅳ Normally open NO 2 ᅳ Normally closed NC 3 ᅳ Input disabled no contact 16 1 Installation considerations You have a variety of installation options to consider when installing the device You must ac...

Страница 82: ...alling the magnet verify that the notches in the magnet base line up with the notches in the transmitter base otherwise the magnet and transmitter do not function effectively When installing the magnet base install the face of the magnet base flush to the surface edge of the installation location This prevents damage to the magnet plastic base whenever a window or door is opened Adhere to the dist...

Страница 83: ...the detector to enable or disable the reed switch Notice Please note insert the jumper onto the pin prior to installing the battery Failure to do so may result in unexpected operation of the device Figure 16 2 Reed switch Callout ᅳ Description 1 ᅳ No jumper disables the internal reed switch 2 ᅳ Jumper on enables the internal reed switch ...

Страница 84: ...ng the latest firmware version Refer to the following tables for compatible receiver firmware versions Encrypted keyfobs Non encrypted keyfobs RFKF FBS A P N F 01U 313 183 RFKF FB A P N F 01U 263 964 RFKF TBS A P N F 01U 313 186 RFKF TB A P N F 01U 263 976 Encrypted keyfobs Non encrypted keyfobs RFKF FBS P N F 01U 313 182 RFKF FB P N F 01U 253 609 RFKF TBS P N F 01U 313 185 RFKF TB P N F 01U 260 8...

Страница 85: ...attery yearly to ensure proper functionality Battery life Up to 5 years Temperature operating Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F to 120゚F Relative humidity 0 to 93 non condensing Frequency 433 42 MHz Tab 17 21 Specifications Notice Please note the battery does not come installed Refer to the specification table for the correct battery type when replacing an old ba...

Страница 86: ... four button keyfobs are designed for arming lock icon and disarming unlock icon the system remotely You can configure the programmable buttons at the control panel for additional control functionality To operate the programmable buttons simply press and hold either button for at least one sec in order for the desired feature to work Uniquely coded arm and disarm buttons Panic alarm LED indicator ...

Страница 87: ...Programmable button 5 ᅳ Programmable button 17 2 RADION keyfob TB The RADION keyfob TB two button keyfobs are designed for arming lock icon and disarming unlock icon the system remotely To operate these buttons simply press and hold either button for at least one sec in order for the desired feature to work Uniquely coded arm and disarm buttons Panic alarm LED indicator ...

Страница 88: ... F 01U 261 834 Bosch Security Systems B V The RFKF TBS CHI keyfob includes synchronized encryption and is compatible only with RADION receivers having firmware v1 3 or higher Figure 17 2 Keyfob buttons and LED 1 ᅳ Arm button 2 ᅳ LED 3 ᅳ Disarm button ...

Страница 89: ...nter or desk Mount in a location that allows easy access for maintenance Specification Dimensions 93 mm x 73 mm x 23 mm 3 66 in x 2 87 in x 90 in Power voltage 1 Lithium battery 3 VDC Power source type C Low battery level 2 5V Battery replacement 1 Duracell DL123A or Panasonic CR123A Detector testing Yearly by an installer Temperature operating Functional range 10 C to 55 C 14 F to 130 F UL only 0...

Страница 90: ...90 en RADION panic FP RADION receiver SD 2020 05 13 F 01U 261 834 Bosch Security Systems B V Frequency 433 42 MHz ...

Страница 91: ... icons and symbols used in the reference guide Description Icon symbol Not pet friendly Signifies that the item is the correct choice selection or location Pet friendly appropriate height and weights below graphic Point away from rotating machines Point away from objects that rapidly change temperature Do not mount the device that has direct exposure to sunlight ...

Страница 92: ...020 05 13 F 01U 261 834 Bosch Security Systems B V Do not point toward window Intended for indoor use only Electrostatic discharge symbol Symbol against disposing batteries into the garbage Humidity range Temperature range Frequency range ...

Страница 93: ...ch Security Systems B V 2020 05 13 F 01U 261 834 Duration of time Questions are answered in the reference guide Universal sign for connecting or disconnecting power Universal sign for connecting to a power source Battery related information ...

Страница 94: ...94 en Appendices RADION receiver SD 2020 05 13 F 01U 261 834 Bosch Security Systems B V Perform a walk test Walk test has concluded Device has wall tamper detection ...

Страница 95: ......

Страница 96: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2020 Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany ...