1 689 988 238
2012-11-06
|
Robert Bosch GmbH
Maintenance | ACS 651/751 | 117
en
7.3.4
Transferring the R134a record to a USB disk
1.
In the
Service Record
menu, select
“R134a Log”
and press
E
.
2.
Select
“Transfer R134a Movement Report”
and
press
E
.
3.
Enter the password:
71342
.
T
he follo
wing warning message is displayed.
4.
Press
E
.
The following screen is displayed.
!
The USB disk is formatted during data transfer and
any data, if present, will be lost. Ensure that the
existing data in the USB disk is transferred to a PC
or laptop and stored before connecting the USB disk
to the ACS 651/751.
5.
Connect the USB disk to the USB port on the
ACS 651/751.
!
Before transferring the R134a records, ensure that
the USB disk is properly inserted in the USB port.
To reset the R134a Log manually, execute the following
procedure.
i
We recommend that the R134a log be printed before
resetting manually.
1.
Select
"R134a Log"
in the
Service Record
menu.
2.
Select
"Monthly"
.
i
Only monthly R134a logs can be reset.
3.
Select the month for which you wish to view the
R134a log.
4.
Press
�
to reset the R134a log.
The following screen is displayed.
5.
Enter the password:
73738
.
"