Inspection and maintenance
Condens 7000 WP – 6721841195 (2022/01)
34
10.4
Clean the burner
▶ Removing the burner gasket.
Fig. 39 Removing the burner gasket
▶ Removing the burner.
Fig. 40 Removing the burner
▶ Check the burner and gas distributor plate for pollution and cracking.
▶ Clean the burner with compressed air or a soft brush if necessary.
10.5
Cleaning the heat exchanger
NOTICE
Risk of damage to the heat exchanger due to improper cleaning.
▶ Do not use chemical agents to clean the heat exchanger.
▶ Only use one brush with plastic bristles for cleaning.
▶ Cover ignition unit [1].
▶ Remove loose dirt with a vacuum cleaner.
▶ Loosen any other dirt with a brush and remove it with a vacuum
cleaner.
▶ Purge the heat exchanger with water [2].
Fig. 41 Cleaning the heat exchanger
10.6
Cleaning the siphon
▶ Remove the flexible hose, and possibly the tee, from the siphon.
▶ Unscrew the union nut of the siphon in the boiler and completely
screw open [1].
▶ Remove siphon [2].
Fig. 42 Remove the boiler siphon
▶ Flush the siphon.
▶ Fill the siphon completely with water.
▶ Reattach the siphon.
▶ Check whether the neck of the siphon is properly connected to the
condensation catch pan.
▶ Tighten the union nut hand tight.
0010035719-001
0010035717-001
0010035230-001
1.
2.
0010040938-001
2.
1.