2000 Series |
Program Entry Guide | 11.0
Point Codes
EN
| 39
Bosch Security Systems | 7/05 | 35114F
Table 5: continued
Display Selection
Description
6
Controlled, All,
Delay
When control panel is All On (armed), short or open starts entry delay if no
Trouble option. Refer to Section 11.3 Digit 3, Point Options.
All points must be normal (not faulted) or bypassed before control panel can
be All armed.
If an alarm occurs on these points within 2 minutes of a closing (exit time
expired, Excursion/Exit included), the system sends a RECENT CLOSING
message with the Alarm Report.
If these points are faulted at the end of exit delay, the system waits a period
equal to entry delay before sending an Alarm Report. If the system is not
turned off, it sends an EXIT ERROR message with the Alarm Report.
Missing Controlled points generate an alarm response when on, a trouble
response when off.
RF Tamper for a Controlled point generates an alarm response when on, a
trouble response when off.
7
Controlled, All,
No Delay
(Follower)
When the control panel is All On (armed), and entry or exit delay times
expire, a short or open causes an alarm response. These points follow the
entry and exit delay and are ignored when faulted during these time periods.
All points must be normal (not faulted) or bypassed before the control panel
can be All armed.
If an alarm occurs on these points within 2 minutes of a closing (exit time
expired, Excursion/Exit included), the system sends a RECENT CLOSING
message with the Alarm Report.
If these points are faulted at the end of exit delay, the system waits a period
equal to entry delay before sending an Alarm Report. If the system is not
turned off, it sends an EXIT ERROR message with the Alarm Report.
Missing Controlled points generate an alarm response when on, a trouble
response when off.
RF Tamper for a Controlled point generates an alarm response when on, a
trouble response when off.
8
Controlled, Part, Delay
When control panel is All or Part On (armed) short or open starts entry
delay if no Trouble option. Refer to Section 11.3 Digit 3, Point Options.
Part points must be normal (not faulted) or bypassed before control panel
can be Part armed.
If an alarm occurs on these points within 2 minutes of a closing (exit time
expired, Excursion/Exit included), the system sends a RECENT CLOSING
message with the Alarm Report.
If these points are faulted at the end of exit delay, the system waits a period
equal to entry delay before sending an Alarm Report. If the system is not
turned off, it sends an EXIT ERROR message with the Alarm Report.
Missing Controlled points generate an alarm response when on, a trouble
response when off.
RF Tamper for a Controlled point generates an alarm response when on, a
trouble response when off.
Содержание 2000 Series
Страница 1: ...EN Program Entry Guide Control Panels 2000 Series ...
Страница 14: ...2000 Series Program Entry Guide 3 0 Reports EN 14 Bosch Security Systems 7 05 35114F Notes ...
Страница 26: ...2000 Series Program Entry Guide 6 0 Open Close EN 26 Bosch Security Systems 7 05 35114F Notes ...
Страница 30: ...2000 Series Program Entry Guide 8 0 Bell EN 30 Bosch Security Systems 7 05 35114F Notes ...
Страница 34: ...2000 Series Program Entry Guide 10 0 Address Configuration EN 34 Bosch Security Systems 7 05 35114F Notes ...
Страница 50: ...2000 Series Program Entry Guide 11 0 Point Codes EN 50 Bosch Security Systems 7 05 35114F Notes ...
Страница 52: ...2000 Series Program Entry Guide 12 0 Point Text EN 52 Bosch Security Systems 7 05 35114F Notes ...
Страница 58: ...2000 Series Program Entry Guide 14 0 User Test EN 58 Bosch Security Systems 7 05 35114F Notes ...
Страница 62: ...2000 Series Program Entry Guide 16 0 RF Parameters EN 62 Bosch Security Systems 7 05 35114F Notes ...
Страница 64: ...2000 Series Program Entry Guide 17 0 Program Lock EN 64 Bosch Security Systems 7 05 35114F Notes ...